Adamczewski AD-MM 500 FE Bedienungsanleitung

Display device, control unit and data logger
AD-MM 500 FE
Manual
Version 1.0 / 2021-05-19

Adamczewski GmbH Manual AD-MM 500 FE
Contents
1 About this manual 3
2 Safety 4
3 Product description 6
4 Technical data 8
4.1 Supply......................................... 8
4.2 Housing ........................................ 8
4.3 Environmental conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.4 EMC .......................................... 8
4.5 Electrical safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.6 RS485-Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.7 Configuration interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.8 Network interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.9 USB-Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.10Display......................................... 9
4.11 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5 Assembly and commissioning 10
6 Operation and menu navigation 11
6.1 Key functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.2 Normal operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.3 Scroll display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.4 Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6.4.1 Select slave and function . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6.4.2 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.4.3 Info....................................... 17
6.4.4 Backup to USB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7 Configuration 18
7.1 Logging ........................................ 18
7.2 Displays ........................................ 21
7.3 Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7.4 Channels........................................ 27
8 Modbus 29
9 Wiring diagrams 32
10 Appendix 34
2 / 36 1.0 2021-05-19

Adamczewski GmbH Manual AD-MM 500 FE
1 About this manual
This manual is part of the product.
•Read the manual carefully before using the device.
•Keep the manual for the entire service life of the product and have it available for reference.
•Pass the manual on to any subsequent owner or user of the product.
Structure of the warnings
Please consider the documentation. This symbol is intended to warn you of
possible hazards that could arise during assembly, commissioning and use.
•Here, actions to avoid the danger are available.
•...
Structure of the hazard warnings
Danger to life or serious injury. Disconnect the system and the unit from the
power supply before starting work..
•Here, actions to avoid the danger are available.
•...
3 / 36 1.0 2021-05-19

Adamczewski GmbH Manual AD-MM 500 FE
2 Safety
Intended use
The operating, maintenance and servicing conditions prescribed in this man-
ual must be strictly observed. Maintenance conditions must be strictly ad-
hered to.
The AD-MM 500 FE is intended for connection to an RS-485 interface to which other devices are
connected in bus mode.
The AD-MM 500 FE can be connected to a PC or laptop via the configuration interface.
The AD-MM 500 FE is intended for installation in front panels of control cabinets.
The AD-MM 500 FE has a connection for the supply voltage and can be supplied with AC voltage
up to 250V AC or 24V DC.
Any other use is not in accordance with the intended use!Unauthorised conversions and modi-
fications to the product lead to considerable safety risks and are prohibited for safety reasons!
ADAMCZEWSKI elektronische Messtechnik GmbH is not liable for any damage resulting from
this or for damage or for damage resulting from improper use.
Malfunctions that may impair safety must be eliminated immediately! The installer must make the
manual available to the operator. The installer and the operator must have read and understood
the manual before starting their work.
Foreseeable misuse
In particular, this product must not be used in the following cases:
•In potentially explosive atmospheres. When operating in potentially explosive atmospheres,
sparking may cause deflagration, fire or explosion.
•Use on humans and animals.
Safe handling
This product complies with the state of the art and the recognised safety regulations. Each unit
is tested for function and safety before delivery.
Only operate this product when it is in perfect condition, taking into account the manual, the usual
regulations and guidelines as well as the applicable safety regulations and accident prevention
regulations.
Extreme environmental conditions affect the function of the product.
4 / 36 1.0 2021-05-19

Adamczewski GmbH Manual AD-MM 500 FE
•Protect product from shocks
•Use product indoors only
•Protect product from moisture
Qualification of the staff
Installation, commissioning, operation, maintenance, decommissioning and disposal may only be
carried out by technically qualified personnel. Work on electrical parts may only be carried out by
trained in accordance with the applicable regulations and directives.
Changes to the product
Unauthorised modifications to the product can lead to malfunctions and are prohibited for safety
reasons.
Use of spare parts and accessories
The use of unsuitable spare parts and accessories can damage the product. Please use only
original spare parts and accessories from the manufacturer.
Disclaimer
The manufacturer accepts no liability or warranty for damage or consequential damage resulting
from failure to comply with the technical regulations, instructions and recommendations. The
manufacturer is not liable for any costs or damage incurred by the user or third parties as a result
of the use of this appliance, especially in the event of improper use, misuse or malfunctions of
the connection, malfunctions of the appliance or connected devices.
5 / 36 1.0 2021-05-19

Adamczewski GmbH Manual AD-MM 500 FE
3 Product description
The AD-MM 500 FE is a display, control unit and data logger for front panel installation.
The display is a 3.5” TFT display with graphics capability.
The AD-MM 500 FE can be connected via its RS-485 interface to one or more units of the ADAM-
CZEWSKI elektronische Messtechnik GmbH or to units of other manufacturers. Any data from
these devices can be displayed and/or logged to an internal SD memory card. The stored data
can be transferred to a USB stick at any time for further analysis.
The AD-MM 500 FE communicates with the connected devices via the Modbus protocol and is
always the Modbus master.
The freely definable displays and display elements can only be created or
changed with the Configuration program AD-Studio . If these are to be created
or changed by the customer, the USB adapter VarioPass available from the
manufacturer is required
.
Features
•Display unit, operating unit and data logger for front panel installation
•Display via graphic-capable TFT display
•RS-485 interface with Modbus-RTU protocol
•Interface for configuration or firmware update
•Creation of own displays with the Configuration program AD-Studio
•Up to 10 configurable displays
•Up to 40 configurable display elements in total
•Up to 12 configurable display elements per display
•Up to 32 configurable Modbus channels.
•Display element types. Numeric, bar, LED, time graph, drag pointer.
•Display element properties such as position, size, labelling, colours freely definable.
•Display element functions such as colour change through hysteresis or window function
definable.
Scope of supply
•AD-MM 500 FE
•All required pluggable terminals.
•This instruction manual
For configuration with the Configuration program AD-Studio you need the optional programming
adapter VarioPass.
6 / 36 1.0 2021-05-19

Adamczewski GmbH Manual AD-MM 500 FE
Order code
AD-MM 500 FE RS-485 interface, configuration interface, USB port, Ethernet.
VarioPass (option) USB adapter for configuration and firmware update of the AD-MM 500 FE .
Display and operating elements
The AD-MM 500 FE has a colour graphics-capable TFT display for showing the data and three
buttons for operation and configuration.
TFT-Display
Up SetDown
Figure 3.1: Display and operating elements of the AD-MM 500 FE
key ’Up’ Scroll up; increment digit
key ’Down’ Scroll down; decrement digit
key ’Set’ Confirm input
7 / 36 1.0 2021-05-19

Adamczewski GmbH Manual AD-MM 500 FE
4 Technical data
4.1 Supply
Name Value
Supply voltage 20 ... 253 V AC/DC
Max. Power consumption 2.0W / 4.0VA
4.2 Housing
Name Value
Dimensions (WxHxD) 96x96x63 mm
Panel cut-out 92x92 mm
Protection class front cover IP 54
Protection class terminals IP 20
Connection technology removable screw terminals
Construction panel housing
Weight 350 g
4.3 Environmental conditions
Name Value
Ambient temperature 0 ... 50 ◦C
Storage and transport -10 ... 70 ◦C (avoid condensation)
Degree of contamination 2
4.4 EMC
Name Value
Product family standard EN 61326
Emitted interference EN 55011, CISPR11 Class B
4.5 Electrical safety
Name Value
Product family standard EN 61010-1
8 / 36 1.0 2021-05-19

Adamczewski GmbH Manual AD-MM 500 FE
4.6 RS485-Interface
Name Value
Connector 3-pin socket 3.81mm pitch
Standard RS-485
Function Modbus Master
Protocol Modbus-RTU
Max. Number of participants 32
Max. Bus length 100 m
Bus termination 120 Ohm (both ends at bus end)
4.7 Configuration interface
Name Value
Connector jack socket 3mm
Standard UART, manufacturer specific
Function Configuration
4.8 Network interface
Name Value
Connector RJ45 socket
Standard Ethernet
Function reserve for later extensions
4.9 USB-Interface
Name Value
Connector socket type A for USB stick
Standard USB 1.0, 2.0
Function data transfer
4.10 Display
Name Value
Type 3.5” TFT
Resolution 320x240 Pixel
4.11 Operation
Name Value
Type 3 short-travel keys
9 / 36 1.0 2021-05-19

Adamczewski GmbH Manual AD-MM 500 FE
5 Assembly and commissioning
Electrical connection
The terminals of the auxiliary voltage inputs are dangerous to touch
.
•Disconnect the mains voltage and secure it against reconnection.
•Ensure that the connections are protected against accidental contact.
•Protect all connections against electrostatic discharge.
Commission the appliance
•Switch off the power supply.
•Check that there is no voltage.
•Mount the unit.
•Connect power supply and RS-485.
•Switch on power.
•Configure the unit. See chapter 6 for details.
•Check function.
10 / 36 1.0 2021-05-19