Advanced Axis AX-ASW-16 Bedienungsanleitung

www.advancedco.com
Switch LED Modules
24V
-+
485
B A
PSU
MONITOR
+ --+
-+ + -
-+ + -
-+
1234567
ON
AX-ASW-16 AX-I/O-48
AX-LED16RY AX-LED32R /AX-LED32Y

www.advancedco.com2
Table of Contents Page
1INTRODUCTION / OVERVIEW............................................................................................................................3
1.1PRODUCT DESCRIPTION..................................................................................................................................3
2MODULE INSTALLATION...................................................................................................................................4
2.1AXISAX ENCLOSURE MOUNTING ......................................................................................................................4
2.2AX-LZA CABINET MOUNTING .........................................................................................................................5
2.3AX-I/O-48 OTHER CABINET MOUNTING ..........................................................................................................6
2.3.1AX-GCAB Mounting .................................................................................................................................6
3MODULE DIP SWITCH CONFIGURATION.........................................................................................................7
3.1ADDRESSING (4 DIP SWITCHES).....................................................................................................................7
3.2485 COMMS EOL &DISABLE PSU MONITOR (2 DIP SWITCHES)......................................................................7
3.2.1485 Comms (P-BUS) EOL .......................................................................................................................7
3.2.2Disable PSU (Power Supply Unit) Monitor...............................................................................................8
4MODULE WIRING................................................................................................................................................8
4.124 VDC POWER WIRING.................................................................................................................................8
4.2485 (AX SERIES P-BUS) WIRING ...................................................................................................................9
4.324 VDC &485 (AX SERIES P-BUS) DAISY CHAIN WIRING..............................................................................9
4.4PSU (POWER SUPPLY UNIT)MONITOR WIRING .............................................................................................10
4.5AX-I/O-48 INPUT /OUTPUT WIRING ..............................................................................................................10
5SWITCH LED MODULE PROGRAMMING........................................................................................................11
5.1LED PROGRAMMING ....................................................................................................................................14
5.2SWITCH PROGRAMMING................................................................................................................................17
5.3BUZZER OPERATION PROGRAMMING.............................................................................................................18
6MODULE SLIDE-IN LABELS.............................................................................................................................19
7SPECIFICATIONS..............................................................................................................................................20

www.advancedco.com
www.advancedco.com 3
1 Introduction / Overview
1.1 Product Description
This manual covers the installation and operation of the AxisAX Switch LED Modules (AX-ASW-16, AX-I/O-48, AX-
LED16RY, AX-LED32R and AX-LED32Y).
AX-ASW-16 Switch LED Module, incorporating 16 switches and 48 LEDs
AX-I/O-48 Switch LED Driver Module, incorporating 16 switch inputs and 48 LED Drive Outputs
AX-LED16RY LED Module, incorporating 16 red and 16 yellow LEDs
AX-LED32R LED Module, incorporating 32 red LEDs
AX-LED32Y LED Module, incorporating 32 yellow LEDs
The Switch LED Modules are field configurable switch input and LED status indicator modules for use with
Advanced AxisAX fire alarm control panels. Each fire alarm control panel can accommodate a maximum of sixteen
(16) Switch LED Modules in any combination.
In addition to the switch and LED functionality, each module has an on-board programmable buzzer (piezo) for local
alerting of system status, events, etc.
The AxisAX Switch LED Modules are extremely flexible and easy to configure/program utilizing the Advanced PC-
NeT field configuration tool, which works in a Windows® environment. Switches can be programmed to bypass
(disable/enable) points, zones, and/or groups. They can also be programmed to turn On/Off relay points, NAC
circuits, city connections, or they can be configured to provide complete HOA (Hand-Off-Auto) control functionality.
When interfacing to AxisAX audio and command centers, controls can be configured for all call, selective zone/area
paging, individual message selection, fire fighter telephone selection, etc. LEDs can be programmed for a number
of different status indications by points, zones and/or groups within the system, including alarm, supervisory,
trouble, switch active, relay active, etc. In addition, the LEDs can be programmed for primary and secondary status
events, along with flash rates based on last known status/event (i.e.: off, on steady, 1/2 or 1 second flash). Easy
slide-in label pockets are provided on all modules, except the AX-I/O-48, allowing switches and LEDs to have
customized labeling based on installation usage.

www.advancedco.com4
2 Module Installation
2.1 AxisAX Enclosure Mounting
The Switch LED Modules can be mounted into any available inner (AX-CTL-1 outer) door aperture of an AxisAX
enclosure (see figure 1).
AX-CTL-1
AX-CTL-1V, 2V or 4V AX-CTL-1L, 2 or 4
AX Command Center (3x5)
AX Command Center (3x3)
Figure 1 – Switch LED Module Enclosure Mounting
Inner (AX-CTL-1
outer) door
opening/slot

www.advancedco.com
www.advancedco.com 5
Note: The AX-ASW-16 switch LED module cannot be installed on the outer door of the AX-CTL-1 panel, as
there is no method of disabling (enable/disable key switch control) operation of the 16 switches associated
with the module.
To install a Switch LED Module in an AxisAX panel aperture (opening/slot), simply remove the nuts and washers
holding the blank aperture in place and replace it with the Switch LED Module (see figure 2).
2.2 AX-LZA Cabinet Mounting
In addition to being mounted in an AxisAX enclosure, Switch LED Modules can also be mounted in an Advanced
local zone annunciator cabinet. Advanced has three sizes of local zone annunciator cabinets, an AX-LZA-CAB1,
AX-LZA-CAB2 and an AX-LZA-CAB4. The AX-LZA-CAB1 has a single aperture (opening/slot), while the AX-LZA-
CAB2 has two apertures (openings/slots) and the AX-LZA-CAB4 has four apertures [openings/slots] (see figure 3).
Note: AX-LZA-CAB’s are available in gray or red colors.
AX-LZA-CAB1 AX-LZA-CAB2
Figure 3 – Remote Switch LED Module Cabinet
Figure 2 – Switch LED Module Enclosure Aperture Mounting
AX-LZA-CAB4

www.advancedco.com6
To install a Switch LED Module in a local zone annunciator cabinet, remove the inner plate of the AX-LZA-CAB by
removing the four (4) screws holding the inner plate to the cabinet and removing the inner plate ground wire from
the cabinet pluggable ground stud. Place the Switch LED Module between the four (4) module mounting studs and
secure with the provided washers and nuts (see figure 4). Replace the inner plate and ground wire to the AX-LZA-
CAB.
Note: For detailed AX-LZA-CAB mounting instructions refer to installations instructions provided with the
AX-LZA-CAB.
2.3 AX-I/O-48 Other Cabinet Mounting
In addition to being mounted in cabinets previously mentioned, the AX-I/O-48, Switch LED Driver Module, can also
be installed in an Advanced AX-GCAB (Listed general cabinet) or an ANSI/UL Listed 3rd party annunciator
enclosure.
2.3.1 AX-GCAB Mounting
Mount the Advanced AX-GCAB, general purpose UL Listed enclosure, in a clean, dry environment. Remove the
AX-I/O-48 module from its shipping package and securely install it within the AX-GCAB enclosure with the stand-
offs and screws provided with the AX-I/O-48 module (see figure 5).
AX-LZA-CAB1
Inner Door
AX-LZA-CAB2
Inner Door
Figure 4 – Switch LED Module Remote Cabinet Mounting
Figure 5 – AX-I/O-48 General Purpose Cabinet Mounting
AX-LZA-CAB4
Inner Door

www.advancedco.com
www.advancedco.com 7
3 Module DIP Switch Configuration
3.1 Addressing (4 DIP Switches)
Each Switch LED Module must be connected to the AxisAX panels P-BUS (RS-485 serial communication bus),
located on the AX-CTL base card. As the Switch LED Modules reside on the AX-CTL P-BUS, each module must
be configured with a unique address (see figure 6). The address setting corresponds to P-BUS programming criteria
utilized within the Advanced PC-NeT, field configuration program.
As previously stated, up to 16 (sixteen) Switch LED Modules (any combination) can be connected to a single AxisAX
AX-CTL base card, P-BUS.
Note: Only 16 (16) Switch LED Modules can be connected to a single AxisAX AX-CTL base card.
3.2 485 Comms EOL & Disable PSU Monitor (2 DIP Switches)
In addition to the DIP switches provided for module addressing, each Switch LED Module has two additional DIP
switches, DIP switch 6 and 7. DIP Switch 6 is for activating an onboard resistor to allow for AX-CTL base card P-
BUS (RS485) end-of-line filtering. Dip switch 7 is for allowing the monitoring of a remote power supply.
3.2.1 485 Comms (P-BUS) EOL
The P-BUS (RS485 communications bus) of the AX-CTL base card requires a 150Ωend-of-line filtering resistor to
be placed on the last (furthest) P-BUS module connected to this Style 4 (Class B) communications bus. If a Switch
LED Module is the last module on the P-BUS, set DIP switch 6 on the module to “ON”, thereby activating the
internal 150Ωend-of-line filtering resistor (see figure 6). If the Switch LED Module is not the last module on the P-
BUS, leave DIP switch 6 in its “OFF” position.
Note: DIP switch 6 on the Switch LED Module should only be in set to its “ON” position if the Switch LED
Module is the furthest (last) P-BUS module from the AxisAX AX-CTL base card.
Figure 6 – Switch LED Module DIP Switch

www.advancedco.com8
3.2.2 Disable PSU (Power Supply Unit) Monitor
Each Switch LED Module requires 24 VDC filtered and regulated power at 60mA maximum current draw. The 24
VDC power can be obtained from either the AX-CTL base card (AUX-2, non resettable power output), if available,
or from an ANSI/UL Listed fire alarm power supply. If power is from an ANSI/UL Listed fire alarm power supply, the
Switch LED Module has the capability of monitoring a normally closed trouble contact of the Listed power supply,
thereby providing power supply status reporting at the AxisAX panel.
If monitoring an ANSI/UL Listed fire alarm power supply, leave DIP switch 7 set to the “OFF” position and wire the
two PSU Monitor terminals to the normally closed trouble relay contact of the Listed power supply (see figure 6 and
7). If not monitoring an ANSI/UL Listed fire alarm power supply, set DIP switch 7 to the “ON”, “Disable PSU
Monitor” position (see figure 6).
Note: Normally when the Switch LED Module is mounted to an aperture (opening/slot) location in an AxisAX
panel, power for the module is obtained from AUX 2 of the AX-CTL base card. If the power is originating
from AUX 2 of the base card, set DIP switch 7 to the “ON”, “Disable PSU Monitor” position.
4 Module Wiring
This equipment is constructed with static sensitive components. Observe anti-static
precautions at all times when handling printed circuit boards. Wear an anti-static ground
(earth) strap connected to the system enclosure ground.
The Switch LED Module must be grounded; this is normally achieved via the secured mounting of
the module to the installation cabinet aperture (opening/slot). Should another method of mounting
be utilized a dedicated ground must be provided.
4.1 24 VDC Power Wiring
As previously indicated, each Switch LED Module requires 24 VDC filtered and regulated power. Wire 24 VDC
(60mA maximum) to terminals + and – of the switch LED module (see figure 8).
Figure 7 – Switch LED Module PSU Monitor Wiring
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE DEVICES
Must be
Grounded

www.advancedco.com
www.advancedco.com 9
Note: When utilizing multiple Switch LED Module’s, within the same enclosure, 24 VDC power and the P-
BUS (485) communications can be daisy chained from the first Switch LED Module to the next module, then
from that module to the following module, etc.
4.2 485 (AX Series P-BUS) Wiring
Connect the P-BUS (RS485 serial communications) terminals A and B of the AxisAX AX-CTL base card to the 485 A
and B input terminals of the Switch LED Module (see figure 8). If this is the last module connected to the AX-CTL
P-BUS (RS485 serial communications), set DIP switch 6 (485 Comms EOL) one the Switch LED Module to the
“ON” position (see figure 6).
Note: When utilizing multiple Switch LED Module’s, within the same enclosure, 24 VDC power and the P-
BUS (485) communications can be daisy chained from the first Switch LED Module to the next module, then
from that module to the following module, etc.
4.3 24 VDC & 485 (AX Series P-BUS) Daisy Chain Wiring
When utilizing multiple Switch LED Modules within the same enclosure, the 24 VDC power and P-BUS (485)
communications can be daisy chained from one module to the next module.
Wire 24 VDC and the P-BUS (RS485 communications) to the screw terminal inputs on the first Switch LED Module
(see figure 8). Plug the supplied 10-Way (IDC) ribbon cable into the PL2 (10 pin) serial connection on the Switch
LED Module, connect the other end of the 10-Way (IDC) ribbon cable into the PL3 (10 pin) serial connection on the
next Switch LED Module (see figure 9). This method of distributing both the power and communications can be
continued to other Switch LED Modules, however power requirements must be monitored to confirm there is
enough power to supply all of the connected modules.
Figure 8 – Switch LED Module Wiring

www.advancedco.com10
4.4 PSU (Power Supply Unit) Monitor Wiring
Each Switch LED Module has the capability of monitoring a normally closed trouble contact of a remote ANSI/UL
Listed fire alarm power supply, thereby providing power supply status reporting from a remote location back to the
AxisAX panel.
If monitoring a remote power supply, leave DIP switch 7 set to the “OFF” position and wire the two PSU Monitor
terminals to the normally closed trouble relay contact of the Listed power supply (see figure 10).
4.5 AX-I/O-48 Input / Output Wiring
In addition to the power supply and P-BUS wiring, each AX-I/O-48, Switch LED Driver Module, has 16 hardwired
switch inputs and 48 hardwired LED drive outputs. Wire inputs 01 thru 16, + and –, to ANSI/UL Listed switch. Wire
LED drive outputs 01 to 48, + and –, to the associated ANSI/UL Listed LED. The LED drive output, + and -, is
current limited (see figure 11).
Figure 9 – Switch LED Module Daisy Chain Wiring
24V
-+
485
B A
PSU
MONITOR
-+
1234567
ON
24V
-+
485
B A
PSU
MONITOR
-+
1234567
ON
Figure 10
–
Switch LED Power Supply Monitor Wiring
Dieses Handbuch passt für folgende Modelle
4
Inhaltsverzeichnis
Andere Advanced Steuereinheit Handbücher
Beliebte Steuereinheit Handbücher anderer Marken

Festo
Festo Compact Performance CP-FB6-E Stücklistenhandbuch

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Bedienungsanleitung

JS Automation
JS Automation MPC3034A Bedienungsanleitung

JAUDT
JAUDT SW GII 6406 Series Kurzanleitung

Spektrum
Spektrum Air Module System Bedienungsanleitung

BOC Edwards
BOC Edwards Q Series Bedienungsanleitung