Advice TOPV1000 Bedienungsanleitung

Top Vision UPS
User Manual
TOPV1000/ TOPV 1500
TOPV 2000/ TOPV 3000
Online UPS
Uninterruptible Power Supply System

1
Table of Contents
1. Important Safety Warning
2
1-1. Transportation 2
1-2. Preparation 2
1-3. Installation 2
1-4. Operation 2
1-5. aintenance, service and faults 3
2. Installation and setup
4
2-1. Rear panel view 4
2-2. Setup the UPS 6
3. Operations ..
9
3-1. Button operation 9
3-2. LCD Panel 9
3-3. Audible Alarm 11
3-4. LCD display wordings index 11
3-5. UPS Setting 11
3-6. Operating ode Description 14
3-7. Faults Reference Code 14
3-8. Warning indicator 15
4. Troubleshooting ...
16
5. Storage and Maintenance .
18
6. Specifications 19

2
1. Important Safety Warning
Please comply with all warnings and operating instructions in this manual strictly. Save this
manual properly and read carefully the following instructions before installing the unit. Do
not operate this unit before reading through all safety information and operating
instructions carefully
1-1. Transportation
Please transport the UPS system only in the original package to protect against
shock and impact.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed.
Please allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or
near heater.
Do not block ventilation holes in the UPS housing.
1-3. Installation
Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances such as hair dryers to UPS output sockets.
The UPS can be operated by any individuals with no previous experience.
Connect the UPS system only to an earthed shockproof outlet which must be
easily accessible and close to the UPS system.
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof
outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the
UPS system.
When installing the equipment, it should ensure that the sum of the leakage
current of the UPS and the connected devices does not exceed 3.5mA.
1-4. Operation
Do not disconnect the mains cable on the UPS system or the building wiring
outlet (shockproof socket outlet) during operations since this would cancel the
protective earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS
output sockets or output terminals block may be electrically live even if the UPS
system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.

3
1-5. Maintenance, service and faults
The UPS system operates with hazardous voltages. Repairs may be carried out
only by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the
mains (building wiring outlet), components inside the UPS system are still
connected to the battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the
batteries and verify that no current is present and no hazardous voltage exists in
the terminals of high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations.
Unauthorized persons must be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the
ground. Before touching, please verify that no voltage is present!
Batteries may cause electric shock and have a high short-circuit current. Please
take the precautionary measures specified below and any other measures
necessary when working with batteries:
remove wristwatches, rings and other metal objects
use only tools with insulated grips and handles.
When changing batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the
skin and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid
fire hazards.
Do not dismantle the UPS system.

4
1000VA(L) 2000VA(L) TOWER 3000VA(L) TOWER
IEC Type
1000VA(L) / 1500VA(L)
RACKMOUNT 2000VA(L) RACKMOUNT 3000VA(L) RACKMOUNT
IEC Type
IEC Type
IEC Type
Programmable outlets: connect to non-critical loads.
1. Output receptacles: connect to mission-critical loads.
2. AC input
3. Input circuit breaker
4. Network/Fax/ odem surge protection
5. Emergency power off function connector (EPO)
6. USB communication port
7. RS-232 communication port
8. SN P intelligent slot
9. External battery connection (only available for L model)
10.Output terminal
11.Output circuit breaker
12.Input terminal

5
2-2. Setup the UPS
Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension
cords.
For 208/220/230/240VAC models:
The power cord is supplied in the UPS package.
For 110/115/120/127VAC models: The power cord is attached to the UPS. The input
plug is a NE A 5-15P for 1K, 1KL, 1.5K and 1.5KL models, NE A 5-20P for 2K and 2KL
models.
Note:
For Low voltage models
: Check if the site wiring fault indicator lights up in LCD
panel. It will be illuminated when the UPS is plugged into an improperly wired utility power
outlet (Refer to Troubleshooting section).
Step 2: UPS output connection
For socket-type outputs, there two kinds of outputs: programmable outlets and
general outlets. Please connect non-critical devices to the programmable outlets and
critical devices to the general outlets. During power failure, you may extend the
backup time to critical devices by setting shorter backup time for non-critical devices.
For terminal-type input or outputs, please follow below steps for the wiring
configuration:
a) Remove the small cover of the terminal block
b) Suggest using AWG14 or 2.1mm
2
power cords. Suggest using WG12-10 or
3.3mm
2
-5.3mm
2
power cords for NE A type.
c) Upon completion of the wiring configuration, please check whether the wires are
securely affixed.
d) Put the small cover back to the rear panel.
Step 3: Communication connection
Communication port:
USB port RS-232 port Intelligent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect the
communication cable one end to the USB/RS-232 port and the other to the communication
port of your PC. With the monitoring software installed, you can schedule UPS
shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SN P or AS400 card. When
installing either SN P or AS400 card in the UPS, it will provide advanced communication
and monitoring options.
PS. USB port and RS-232 port can’t work at the same time.
Step 4: Network connection
Network/Fax/Phone surge port
Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel
of the UPS unit. Connect from “OUT” outlet to the equipment with another
modem/fax/phone line cable.

6
3. Operations
3-1. Button operation
Button Function
ON/ ute Button
Turn on the UPS: Press and hold ON/ ute button for at least 2
seconds to turn on the UPS.
ute the alarm: After the UPS is turned on in battery mode, press
and hold this button for at least 5 seconds to disable or enable the
alarm system. But it’s not applied to the situations when warnings
or errors occur.
Down key: Press this button to display previous selection in UPS
setting mode.
Switch to UPS self-test mode: Press ON/ ute buttons
simultaneously for 5 seconds to enter UPS self-testing while in AC
mode, ECO mode, or converter mode.
OFF/Enter
Button
Turn off the UPS: Press and hold this button at least 2 seconds to
turn off the UPS in battery mode. UPS will be in standby mode
under power normal or transfer to Bypass mode if the Bypass
enable setting by pressing this button.
Confirm selection key: Press this button to confirm selection in
UPS setting mode.
Select Button
Switch LCD message: Press this button to change the LCD
message for input voltage, input frequency, battery voltage,
output voltage and output frequency. It will return back to default
display when pausing for 10 seconds.
Setting mode: Press and hold this button for 5 seconds to enter
UPS setting mode when UPS is off.
Up key: Press this button to display next selection in UPS setting
mode.
ON/ ute +
Select Button
Switch to bypass mode: When the main power is normal, press
ON/ ute and Select buttons simultaneously for 5 seconds. Then
UPS will enter to bypass mode. This action will be ineffective when
the input voltage is out of acceptable range.

7
3-2. LCD Panel
Display Function
Backup time information
Indicates the backup time in pie chart.
Indicates the backup time in numbers.
H: hours, : minute, S: second
Fault information
Indicates that the warning and fault occurs.
Indicates the warning and fault codes, and the codes are listed
in details in 3-5 section.
ute operation
Indicates that the UPS alarm is disabled.
Output & Battery voltage information
Indicates the output voltage, frequency or battery voltage.
Vac: output voltage, Vdc: battery voltage, Hz: frequency
Load information
Indicates the load level by 0-25%, 26-50%, 51-75%, and
76-100%.
Indicates overload.
Indicates the load or the UPS output is short circuit.
Programmable outlets information
Indicates that programmable management outlets are working.
ode operation information
Indicates the UPS connects to the mains.
Indicates the battery is working.
Indicates the bypass circuit is working.
Indicates the ECO mode is enabled.

8
Indicates the Inverter circuit is working.
Indicates the output is working.
Battery information
Indicates the Battery level by 0-25%, 26-50%, 51-75%, and
76-100%.
Indicates the battery is fault.
Indicates low battery level and low battery voltage.
Input & Battery voltage information
Indicates the input voltage or frequency or battery voltage.
Vac: Input voltage, Vdc: battery voltage, Hz: input frequency
3-3. Audible Alarm
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
Bypass Mode Sounding every 10 seconds
3-4. LCD display wordings index
Abbreviation Display content eaning
ENA Enable
DIS Disable
ESC Escape
HLS High loss
LLS Low loss
BAT Battery
CF Converter
EP EPO
FA Fan
TP Temperature
CH Charger

9
3-5. UPS Setting
There are three parameters to set up the
UPS.
Parameter 1: It’s for program alternatives.
There are 8 programs to set up: output
voltage setting, frequency converter
enable/disable, output frequency setting,
ECO enable/disable, ECO voltage range
setting, Bypass enable/disable, Bypass
voltage range setting, programmable
outlets enable/disable, programmable
outlets setting and exit.
•01: Output voltage setting
Interface Setting
For 208/220/230/240 VAC models, you may choose the
following output voltage:
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac
240: presents output voltage is 240Vac
For 110/150/120/127 VAC models, you may choose the
following output voltage:
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac
127: presents output voltage is 127Vac
•02: Frequency Converter enable/disable
Interface Setting
CF ENA: converter mode enable
CF DIS: converter mode disable
•03: Output frequency setting
Interface Setting
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode enable, you may choose the
following output frequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz
Parameter 1
Parameter Parameter 3
Dieses Handbuch passt für folgende Modelle
3
Inhaltsverzeichnis
Andere Advice UPS Handbücher
Beliebte UPS Handbücher anderer Marken

Pylontech
Pylontech Victron & Pylontech US5000 Bedienungsanleitung

Tecnoware
Tecnoware EVO DSP PLUS MM 6.8 Bedienungsanleitung

Mecer
Mecer ME-1000-WTU Bedienungsanleitung

Mustek
Mustek PowerMust 530(B) Plus Installations- und Betriebshandbuch

Emerson
Emerson Liebert NXL series Bedienungsanleitung

MAKELSAN
MAKELSAN BOXER SERIES Bedienungsanleitung