Marvair ComPac AVHDA I&O Manual 03/2019 Rev.3
1.4 Capacities, Weights and Filter Sizes
Complete electrical and performance specications and dimensional drawings are in the Product Data
Sheet.
Note: Follow local codes and standards when designing duct runs to deliver the required airow.
Minimize noise and excessive pressure drops caused by duct aspect ratio changes, bends, dampers and
outlet grilles in duct runs.
Basic Model Cooling BTUH1EER2Rated Air Flow (CFM)3
AVHDA90 89,000 10 3,500
1Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air. 2EER=Energy Efciency Ratio
3CFM=Cubic Feet per Minute
Ratings are with no outside air. Performance will be affected by altitude.
Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models. Operation of units at a different volt-
age from that of the rating point will affect performance and air ow.
Table 1. AVHDA Efficiency and Capacity Ratings at ANSI/AHRI Standard 390
Return Air
DB/WB Sensible Cooling Capacity Outside Air Temperature ºF (ºC)
75 (24) 80 (27) 85 (30) 90 (32) 95 (35)
79/66
BTUH
40,671 40,148 39,613 39,093 38,561
75/61 42,039 40,581 39,164 37,706 36,248
80/63 43,700 42,201 40,662 39,164 37,665
85/65 48,641 46,940 45,279 43,578 41,918
Table 2. Sensible Capacities - Single Compressor
Return Air
DB/WB Sensible Cooling Capacity Outside Air Temperature ºF (ºC)
75 (24) 80 (27) 85 (30) 90 (32) 95 (35) 100 (38) 105 (41) 110 (43) 115 (46) 120 (49) 125 (52)
79/66*
BTUH
73,746 72,487 71,203 69,958 68,689 67,427 66,204 64,956 64,351 63,780 63,209
75/61 77,983 76,678 75,416 74,126 72,843 71,567 70,298 69,071 68,443 67,817 67,192
80/63 87,060 85,763 84,439 83,158 81,884 79,477 76,184 72,802 71,200 69,598 67,996
85/65 98,806 97,367 95,972 94,552 93,174 91,805 90,411 89,060 88,371 87,782 87,194
Table 3. Sensible Capacities - Dual Compressor
Basic Model Outdoor Temperature
75ºF / 24ºC 80ºF / 26.5ºC 85ºF / 29ºC 90ºF / 32ºC 95ºF / 35ºC
AVHDA90AC 46,980 45,360 43,740 42,120 40,500
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
Table 4. Single Compressor Cooling Performance (BTUH) at Various Outdoor Temperatures
Basic Model Outdoor Temperature
75ºF / 24ºC 80ºF / 26.5ºC 85ºF / 29ºC 90ºF / 32ºC 95ºF / 35ºC
AVHDA90AC 103,240 99,680 96,120 92,560 89,000
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
Table 5. Dual Compressor Cooling Performance (BTUH) at Various Outdoor Temperatures
Basic Model Fan Watts Fan CFM EER @ 55 F OAT Outside Air Temperature ºF (ºC)
50 (10) 55 (13) 60 (16) 65 (18) 70 (21)
AVHDA90AC 730 3500 125 110,128 91,140 72,153 53,165 34,178
Based upon indoor setpoint temperature of 79 (26).
Table 6. Economizer Cooling Performance
MODEL Description INCHES MILLIMETERS PART NO. FILTERS PER UNIT MERV RATING
AVHDA90 Exterior Access Return Air Filter 25" x 16" x 2" 635 x 406 x 51 80137 3 8
Interior Access Return Air Filter 15" x 20" x 2" 381 x 508 x 51 92365 3 8
Table 7. Return Air Filter Sizes