Alpha Communications AlphaECall 100 Series Merkblatt

AlphaECall™ 100 Series
Emergency Call System
Installation & Conguration Manual
Alpha Communications®
http://www.alphacommunications.com
42 Central Drive
Farmingdale, NY 11735-1202
Phone: 631-777-5500
Fax: 631-777-5599
http://www.alphacommunications.com
Copyright© 2016-2018 Alpha Communications®. All Rights Reserved.
AWD146 – Rev 1.2
August 2018
1
This publication is informational only and may not be copied in part or in whole or distributed in any form without
express written consent of Alpha Communications® and is subject to change or revision without notice. Alpha
Communications® assumes no responsibility for errors that may appear in this publication.

Chapter 1 - Introduction...............................................................................................................................4
What is AlphaECall™ 100?...................................................................................................................... 4
Typical AlphaEcall™ 100 System Components: ...................................................................................4
Master Annunciator Panel.....................................................................................................................................4
Annunciator Controller ....................................................................................................................4
Duty Stations..........................................................................................................................................................4
Call Devices............................................................................................................................................................5
Corridor Lights.......................................................................................................................................................5
Additional Signaling Devices................................................................................................................................5
Chapter 2 - System Requirements..............................................................................................................6
Wire Types ................................................................................................................................................6
Installation Procedures ........................................................................................................................... 6
System Operation ....................................................................................................................................6
Chapter 3 - Master Module Assembly.........................................................................................................7
Installing Modules in Frames.................................................................................................................. 7
Wiring ELM116 Modules ..........................................................................................................................7
Labeling the ELM116 modules................................................................................................................ 7
Chapter 4 - Wiring Diagrams .......................................................................................................................8
Typical System Wiring Diagram..............................................................................................................8
Troubleshooting .......................................................................................................................................12
Table of Contents
2

Chapter 1 - Introduction
»What is AlphaECall™ 100?
The AlphaEcall™ 100 Series Emergency Call System has been designed to incorporate the most needed features for
• Assisted and Independent Living facilities
• Elderly Housing
• Hotels
• Clinics
• Doctor’soces
• Commercial Buildings
oranywherethataudibleandvisualemergencyornoticationsignalingisrequiredinacompact,aesthetic,andeconom-
ical package.
Designedwith16pointspermodule,thesystemisversatileandscalabletotsmalltoverylargeapplications.Themaster
annunciatorfeatureslonglifeLEDindicatorsforlowermaintenanceaswellasaToneOswitch.Amodulardesignallows
for easy expandability and integration of additional features.
IfyouhaveanyquestionsduringinstallationaboutAlphaECall™100Seriespleasefeelfreetocontactusatanytimeby
going to:
https://www.alphacommunications.com/support
»Typical AlphaEcall™ 100 System Components:
»Master Annunciator Panel
The Annunciator panel is modular in design and typically includes a tone unit (part# TSMEx) consisting of a tone speaker
withaToneObutton,andemergencylightmodule(s)(part#ELM116) that can display up to 16 points each. Depending
on the amount of ELM116modulesrequired,mountingframesareavailablein2,3,4,6,and8modulesizes.Theframes
canbecombinedtoprovidevirtuallyanysizemaster.Masterassembliescanbemountedasushorsurfaceunits.
Certaincongurationscanbemadeinadeskmountconguration.Theuniquemodulardesignallowsforverticalorhori-
zontalorientationtoprovidemaximumversatilityinlimitedspacerequirements.PanelsareavailableinWhite,Titanium,or
DarkBrowncolorstocomplimentthefacilitydécor.ThemodularcongurationalsoallowsforintercomandRoomStatus
systemintegration.Systemscanbeequippedwithmultiplemasterpanelsand/orsub-masterstationstoannunciate
smallerzoneswithinalargersystem.
»Annunciator Controller
EachMasterrequiresanAC219 Controller and an SS106 transformer to be mounted within 100 ft (30m) of each master.
The controller supplies regulated 24VDC power to the system, detects incoming emergency calls, and generates the alert
tone.
»Duty Stations
Up to four (4) Duty Stations (model# RS101S),orremoteaudible/visualannunciators,canbeinstalledtoalertstalocated
awayfromthemasterstationthatacallisactiveinthesystem.Thesestationsareequippedwithanautomaticallyreset-
tingToneObutton.
3

»Call Devices
The AlphaEcall™ 100 Series system is compatible with the SF117/2A and SF119/2AEmergencyPullStations,SF154A
PushButtonStations,andseveralotherlatchingcontacttypedevices.Manyotherdevicetypesareavailableforspecial-
izedneeds.PleasecontactAlphaCommunications®forcompatiblesolutions.
»Corridor Lights
Several Corridor Lights are available for the AlphaEcall™ 100 Series system. CDL101LED 1 bulb, CDL101B 1 bulb
w/24VDCpiezobuzzer,CDL1181bulbw/24VDChornbuzzer,CDL102LED 2 bulb, CDL123B 1 bulb w/ 24VAC horn
buzzerandmore.Maintenance-freeLEDcorridorlightsarealsocompatibletoprovideforspecialsystemrequirements.
»Additional Signaling Devices
TheAlphaEcall™systemcanbeusedwithadditionalBuzzers,Strobes,andFloorBellstoaddressfacilityneeds.
AdditionalEquipmentsuchaspagingnotication,auto-dialersandcalllogging/reportsystemsarealsoavailable.The
AC219 controller has an integrated “Form C” relay to provide a N.O. or N.C. dry contact switch for external signaling
devices when an alarm is received by the system.
4

Chapter 2 - System Requirements
»Wire Types
Allwiringshouldbe#18AWGexceptfortheselective“L”wireswhichcanbe#22AWG.Eitherstrandedorsolidcorewire
isacceptable.Noshieldedortwistedpairtypewireisrequired.
»Installation Procedures
All components must be installed in a cool, clean and dry location. All connections must be clean and secure to insure reli-
ableoperation.Someinstallationsorlocalcodesmayrequireinstallationofannunciatorcontrollersinaprotectivejunction
box with its transformer and the transformer’s primary 120VAC connections.
»System Operation
TheAlphaEcall™100Seriessystemisdesignedasasingleprioritylevel,emergencycallsystem.WiththeAC219Annun-
ciator Controller, mechanically latching devices of various sorts are used to send an alert to a master station or multiple
masterstationsconnectedinparallel.TheAlphaEcall™100Seriessystemcansupportcorridorlights,zonelights,and
cantriggeroorbells,strobes,andmanyotheraudibleand/orvisualannunciators.Whenanycallisactive,thetonelight
willlightandthetonewillsound.Tosilencethetone,presstheToneObutton;theToneOlightandthetonewillshuto
andremainountilALLcallsarereset.Allcallresetsmustbedoneattheoriginatingstation(s).
»IMPORTANT NOTES
• Toensuresystemreliabilityandlongevity,pleasecheckthatallhardwareisinstalledandconguredaspermanu-
facturer’srecommendationsandmanufacturer’sdistancelimitationsandcablingrequirementsareobserved.
• Whenplanningyourinstallation,considerdistancelimitations,andpotentialelectromagneticinterference(EMI)
sources.
• AsthisisconsideredaLifeSafetysystem,itisrecommendedthataqualityBatterybackup/surgeprotector/power
lterbeusedforalldevicesandcomponentsconnectedto110VACpower.
• Systems being used for emergency call, door monitoring, or any other critical application should have their devices
tested regularly for proper operation.
5

Chapter 3 - Master Module Assembly
»Installing Modules in Frames
AlphaEcall™100Seriesmodulesaredesignedforhorizontalor
verticalorientationtoallowvariouscongurations.
The retaining clip for each module uses a pair of rectangular holes
in the frame, shown to the left, to retain the module.
The holes in the four corners of the frame are used to connect the
frametotheushorsurfacebackboxwiththe(4)screwssupplied
with the back box.
Pushthetabsatthebottomofthemoduleintotheframe,position
the module, then snap the retaining clip into the appropriate holes.
»Wiring ELM116 Modules
Attach all incoming selective “L” wires to their respective terminals.
Note: Terminal #1 in the upper left corresponds to the upper left
label position from the front view.
Connect the Dwire from the AC219 to any one of the COM (D+)
terminals and use the additional terminals to branch to additional
modules (if needed). This is the power in (+24VDC) for the master.
If running wires to additional masters they can be doubled up at
these terminals if necessary, but using junction blocks in a central
location is a cleaner way to do this. It is also an easier way to allow
troubleshooting and future changes if necessary.
»Labeling the ELM116 modules
Carefully pry the clear plastic lens at one side from the module
front and remove the paper insert.
Writedirectlyonthepaperinsertorapplymachinegenerated
labels in the white spaces provided.
Whennished,putthepaperinsertinthelenscoverandreinstall
the lens to the module using gentle pressure around the edges.
6

Chapter 4 - Wiring Diagrams
»Typical System Wiring Diagram
7

»Optional Equipment Wiring Examples
8

»Optional Equipment Wiring Examples
9

»Wiring Multiple Master Stations
10
Inhaltsverzeichnis
Andere Alpha Communications Notrufnummer Handbücher
Beliebte Notrufnummer Handbücher anderer Marken

Paso
Paso PA8506-V Bedienungsanleitung

JNY Safetycare
JNY Safetycare FDC Bedienungsanleitung

Rath
Rath 2100-TL9 Bedienungsanleitung

Eldat
Eldat Easywave Fon Alarm Bedienungsanleitung

Merak
Merak MMk-656 Bedienungsanleitung

Assistive Technology Services
Assistive Technology Services TOUCH N TALK FD Montageanleitung