Congratulations on your purchase of an Athena Series C Temperature/Process Controller. It is designed for ease of use and reliability
wherever accurate control is required.
After following the instructions for installation, simply step through and set your operating parameters using the controller’s easy menu
system. The instrument may then be automatically or manually tuned to your process for optimum setpoint control.
As you look through this manual, you will notice
blue italicized text
appearing with, or adjacent to, the operating information. These
notes impart important information about the controller and may answer questions you may have about its setup or operation. If you
still have questions or require any assistance, please contact your Athena representative or call technical support at 1-800-782-6776.
Outside the USA, please call (+1) 610-828-2490.
After unpacking, inspect the instrument for any physical damage that may have occurred in shipping. Save all packing materials and
report any damage to the carrier immediately.
Field-Selectable Inputs including Thermocouple, RTD, Current or Voltage
Process Control via On/Off Through Full PID Operation
Autotuning - Heat or Cool
Eight-Segment Ramp/Soak to prevent thermal shock
On/Off Output with Adjustable Hysteresis and Deadband to maintain tight process control
Field-Configurable Process or Deviation Alarms
Bumpless, Auto-Manual Transfer
NEMA 4X Front Panel, “Watertight”
Selectable Ramp to Setpoint
Alarm Inhibit
Loop Break Alarm Capability
Available Options Include Serial Communications, Contact/ Digital Input, Remote Analog Setpoint, Transducer Excitation, Auxiliary
Output, Dual Alarms, or Electromechanical Relay Alarm.
In addition to presenting a potential fire hazard, high voltage and high temperature can damage equipment and
cause severe injury or death. When installing or using this instrument, follow all instructions carefully and use
approved safety controls. Electrical connections and wiring should be performed only by suitably trained personnel.
Do not locate this instrument where it is subject to excessive shock, vibration, dirt, moisture, oil, or other liquids. The
safe operating temperature range for this unit is 32°F to 140°F (0°C to 60°C).
This unit has been tested and found to be compliant with“NEMA Type 4X Enclosure - For Indoor Use Only.”When
properly installed, this controller will maintain the integrity of a NEMA enclosure and remain“Watertight.”This rating
is only applicable when the controller is properly installed into a suitably rated NEMA Type 4X housing.
E66598 Temperature Indicating and
Regulating Equipment.
E66598 Temperature Indicating and
Regulating Equipment.

3
Installation 4
Dimensions and Mounting 4
Wiring 5
Wiring for Options 6
Output Types 12
Operation 13
Front Panel Controls 13
Power On 13
Security Levels 16
Operating Modes 16
Menu System Overview 17
Parameter/Menu Descriptions 1 9
Input Menu 1 9
Temperature Input 20
Process (Linear) Input 21
Display Menu 22
Output Menu 23
Control Menu 24
PID Output and Control Menus 25
On/Off Output and Control Menus 26
Alarm Menu 28
Ramp and Soak Menu 30
Supervisor Menu 31
Calibration Menu 3 2
Options Menu 3 3
Communications Menu 34
Contact / Digital Input Menu 35
Auxiliary Output Menu 36
Autotune Damping 38
AutoTuning 3 8
Manual Tuning 4 0
Operation in Manual Mode 41
Error Codes 4 2
Technical Specifications 4 3
Recalibration Procedures 4 5
Glossary 4 6
FAQs 48
Default Parameters/Process Parameters 5 0
Warranty/Repairs 5 1
DATE DESCRIPTION REVISION
TITLE
DWG
DATE SCALE DRAWN CHECKED
Model 18C, 19C, 25C Operation Manual
900M505U01
1/22/2020 A

4
Measurements between centerlines of panel cutouts are the minimum recommended.
Unpacking and Inspection
1. Inspect shipping carton for obvious signs of mishandling.
2. After removing the controller from the shipping carton, inspect it carefully for damage. Never attempt to install and use a damaged
unit.
3. Verify that the ordering code number indicated on the side of the controller matches what was ordered.
Figure 1. Recommended Panel Layout for Multiple Controllers
C
LC
L
C
L
C
L
4.700"
(119.4 mm)
4.300" (109.2mm)
C
LC
L
C
L
C
L
4.300" (109.2mm)
2.850"
(72.4 mm)
Recommended Panel Cutout
3.622" SQ (92 mm SQ)
Recommended Panel Cutout
3.622" x 1.772"
(92 mm x 45 mm)
25C
18C

5
Figure 2. Case Dimensions
Prior to mounting the Series C in your panel, make sure that the cutout opening is of the right size, and deburred to enable a smooth
fit. A minimum of 4” (100 mm) of depth behind the panel is required.
If the unit has been shipped with
mounting catches already installed in the top and bottom slots in the case housing, they must be removed to allow insertion of the controller into the panel cutout.
Figure 3. Series C Mechanical Components
BEZEL
GRIP
CASE
GASKET
PANEL
MOUNTING
CATCH
Remove static-protective wrapping material from the instrument. Avoid
inducing static charges to controller while handling and mounting. Insert
the controller into the panel cutout from the front of the panel. Place the
mounting catches into the appropriate mounting slots at the top and
bottom of the case housing and tighten the mounting screws to secure
the controller firmly to the panel.
Note: For some panels, it may be necessary to first remove the
controller chassis from the case housing to access the mounting
catches from the inside. Press the grips on each side of the bezel firmly
until the tabs release and slide the chassis out of the housing. Install
the housing and secure it with the mounting screws to the panel. To
re-insert the controller chassis back into its case, press both bezel grips
simultaneously and slide the controller into the housing until the tabs
engage.
01
02
A1
A2
F1
F2
PV
SV
1800
1800
01 02 A1 A2 F1 F2
PV
SP
1900
1900
4.654"
(118.21 mm)
3.937"
(100 mm)
0.717"
(8.21 mm)
3.600"
(91.44 mm)
3.950"
(100.33 mm)
3.950"
(100.33 mm)
XT25
01
02
A1
A2
F1
F2
PV
SV
18C
19C

6
IMPORTANT: All electrical wiring connections should be made only by trained personnel, and in strict accordance
with the National Electrical Code and local regulations.
The Series C controller has built-in circuitry to reduce the effects of electrical noise (RFI) from various sources.
However, power and signal wires should always be kept separate. We recommend separating connecting wires
into bundles: power; signal; alarms; and outputs. These bundles should then be routed through individual conduits.
Shielded sensor cables should always be terminated at one end only.
If additional RFI attenuation is required, noise suppression devices such as an R.C. snubber at the external noise
source may be used. If you wish, you may order this suppressor directly from Athena, part number 235Z005U01.
Figure 4. Contact Identification
Make sure that you are using the appropriate thermocouple and extension wire.
Connect the negative lead (generally colored red in ISA-type thermocouples) to
contact #19; connect the positive lead to contact #20. Extension wires must be the
same polarity as the thermocouple.
Figure 5. Thermocouple Input Wiring
The Series C accepts input from 2- or 3-wire, 100 ohm platinum resistance temperaure
detectors (RTDs). Connect 2-wire RTDs to contacts #19 and #20, with a jumper across
contacts #18 and #20. Keep leads short and use heavy gauge copper extension wire, if
necessary, to minimize lead resistance. For long runs, 3-wire RTDs should be used.
Figure 6. RTD Wiring

7
Voltage Inputs: Connect the positive voltage input to contact #20; the
negative input to contact #19.
Current Inputs: Connect the positive current input to contact #20; the
negative input to contact #19.
Figure 7. Process and Linear Input Wiring
The Series C power supply accepts 100 to 250 Vac and 100 to 250
Vdc line power without any switch settings or polarity considerations.
All connections should be made in accordance with the National
Electrical Code and local regulations, using only NEC Class 1 wiring
for all power terminals.
It is advisable, but not necessary, to fuse one leg of the incoming
power line, contact #9 or #10, with a 2AG, 0.5 amp rated fuse. It is
recommended that only instrument power is fused - not power to the
load.
Figure 8. Power Wiring Connection
This optional hardware module provides alarm drive outputs. LED indicators A1 and A2 are used to indicate
alarm conditions as configured in the Alarm Menu.
Option Description:
Option T Dual alarm, N.O.
Load Limits:
Max. Load Current 1 A rms
Min. Load Current 0.5 mA rms
Power Factor Range 0.2 to 1.0 (can drive small motors, solenoids, valves, and contactors)
Max. Surge Current
Non-repeating for 1 second 7.5 A
Max. I2T for fusing (0.01 sec) 4.5 amp-squared seconds (1 A - ABC1 typical fuse)
Figure 10. Wiring for Dual Alarm Outputs
Load
Load
1 amp fuse
1 amp fuse
20-240 Vac
20-240 Vac

8
Option Description: Dual 24 V outputs with clamping diodes
Source current is limited to 25 mA (1000 ohm resistor)
Open circuit voltage is 25 volts
Isolation: Isolation 300 volts ac/dc either output to instrument
Figure 12. Wiring for Dual 24V dc Alarm Outputs
Option Description:
NO (Normally open) relay contact is closed when either alarm is active.
The relay life is greater than 100,000 operations at 5 operations per second switching full load.
*Connect load and supply voltage per the following table:
Figure 13. Wiring for Relay Normally Open Alarm Output
Resistive DC 30 Vdc
Inductive DC (L/R = 7ms) 20 Vdc
Resistive AC 250 Vac
Inductive AC (pF = 0.4) 150 Vac
Motor, AC, 1/6 hp 250 Vac
Tungsten Lamp, 360 W 120 Vac
Load 5 amp fuse
Load 5 amp fuse
Supply voltage*
Supply voltage*

9
Option Description: Provides a one-to-one connection between the controller and an RS-232 port.
Computers, PLCs, or dumb terminals may be used to set and access controller data.
Figure 14. Wiring for RS-232 Communications
Option Description: Provides one-to-many communications.
Terminate the controller furthest from the computer by connecting a 120-ohm, 1/4-watt resistor between ter-
minals 23 and 24.
Figure 15. Wiring for RS-485 Communications

10
Option Description:
The Setpoint Variable or Process Variable is transmitted to a remote device (chart recorders, indicators, data
recorders, computers, process controllers, etc.) with 1 of 4 different interfaces:
Option PA: 4-20 mA
Option PB: 1-5 V
Option PC: 0-20 mA
Option PD: 0-5 V
The output signal is scalable in the Auxiliary Output Menu. Multiple remote indicators may be driven by the
controller. However, current and voltage outputs cannot be used simultaneously.
For current (mA) options, the remote indicators are connected in series. The sum of the input resistance for
all remote indicators must be less than 400 ohms. For voltage options, the remote indicators are connected
in parallel.
The sum of the currents for all remote indicators must be less than 10 mA.
Figure 18. Wiring for Auxilliary Output
Option Description:
The transducer excitation option provides power to remote transducers. The transducer outputs, in turn,
provide a signal to the controller input which can be scaled in the appropriate engineering units.
Option 1: 10 Vdc
Option 2: 12 Vdc
Option 3: 15 Vdc
Option 4: 5 Vdc
All options will provide at least 20 mA. The transducer circuitry is thermally protected from short circuits.
Figure 16. Wiring for Transducer Excitation
Andere Handbücher für 18C Series
1
Dieses Handbuch passt für folgende Modelle
2
Inhaltsverzeichnis
Andere Athena Controller Handbücher

Athena
Athena SERIES 16 Bedienungsanleitung

Athena
Athena 18C Series Bedienungsanleitung

Athena
Athena SERIES 16 Bedienungsanleitung

Athena
Athena S Series Bedienungsanleitung

Athena
Athena C10 Series Gebrauchs- und Pflegehandbuch

Athena
Athena 16C series Bedienungsanleitung

Athena
Athena 1ZC Series Bedienungsanleitung

Athena
Athena RMB/1 Bedienungsanleitung

Athena
Athena 2000 Series Bedienungsanleitung