Autani CORE/Manager Bedienungsanleitung

Document: 80309
Revision-01, July 2020
Autani LLC
7090 Columbia Gateway Drive, Suite 140, Columbia, MD 21046, USA,
(443) 320-2233 | (240) 755-0092 (fax) www.autani.com.
This document contains the Proprietary and Confidential Information of Autani LLC. Any use of this
information without the expressed written consent of Autani, LLC is prohibited. Copyright Autani LLC,
2010-2020. All rights reserved. Please refer to www.autani.com/legal for licensing, intellectual property,
and other legal notices and information.
User Manual
Autani CORE/Manager

Page | 2
Table of Contents
1. CORE/Manager Overview .....................................................................3
1.1. Specifications for CORE/Manager ...............................................................4
1.2. Package Contents ........................................................................................4
1.3. Regulatory Information ...............................................................................5
1.4. Product Warranty........................................................................................5
2. System Overview..................................................................................6
3. Mounting Instructions ..........................................................................8
3.1. Space Requirement .....................................................................................8
3.2. Mounting the CORE/Manager onto a Wall .................................................9
3.3. Mounting the CORE/Manager onto a Ceiling............................................11
3.4. Removing the CORE/Manager from Wall Plate.........................................13
4. Hardware Connections .......................................................................14
5. Commissioning the CORE/Manager ....................................................17
5.1. LED Ring Status..........................................................................................17
5.2. Reset Button Functionality........................................................................18
5.3. Selecting a Connection Method ................................................................19
5.3.1. Local Area Network (LAN) Access .............................................................. 21
5.3.1.1. Log In Over the LAN using Local IP address .............................................. 21
5.3.1.2. Changing to a Static IP Address ................................................................ 22
5.3.2. Verifying the Remote Access Capability .................................................... 24
5.3.3. Remote Access via the Worldwide Web .................................................... 25
5.3.3.1. Create a New Account .............................................................................. 26
5.3.4. First Time Login to EnergyCenter® through Remote Access Web Portal ...... 28
5.3.5. Using a USB Stick to Configure Static Network Settings (Optional) ........... 31
5.4. Accessing EnergyCenter® and Commissioning Devices.............................33
5.4.1. Log In to Autani Portal and EnergyCenter® ............................................... 33
5.4.2. Adding Devices for the First Time.............................................................. 34
5.4.3. Example: Label Devices and Assign Locations............................................ 36
5.4.4. Example: Select Device Settings (through Setup) ...................................... 36
5.4.5. Example: Select Device Settings (through Details) .................................... 37
5.4.6. Example: Associate Sensors with Devices.................................................. 38
5.4.7. Example: Create Groups ............................................................................ 38
5.4.8. Example: Set Up Email Alert Notifications................................................. 39
6. Troubleshooting .................................................................................40

Page | 3
1. CORE/Manager Overview
The Autani CORE/Manager appliance is a rugged, industrial control processor that is the heart
of innovative integrated energy management systems powered by EnergyCenter® software.
The CORE/Manager coordinates all energy management functions utilizing autaniNet wireless,
wired Ethernet, and optional wired connectivity to third party systems to securely manage
building functions.
The compact Autani CORE/Manager receives input from environmental sensors, local
controls, and metering devices throughout a facility. Based upon sensor input, schedule, local
input, curtailment, and event information, adjustments to lighting, HVAC, fans, and plug load
devices are managed in real time to minimize energy waste and maximize savings.
The Autani CORE/Manager is a shared appliance designed for use with all of Autani’s
EnergyCenter® products.
The major features of the CORE/Manager are:
Remote monitoring and control of lighting, HVAC, fans, and plug load devices.
Metering and demand response.
Sensor data collection, monitoring, and reporting.
Optional connectivity to BACnet systems.
Easy installation and commissioning: simply mount, connect, power, and go!
Secure 2.4GHz wireless communication with other network devices via autaniNet.
Comprehensive data storage and analytics provide for optimal energy use and savings.
Scalable system can manage a single building up to an entire campus.
Graphical view of real-time and historical energy use provides actionable information to
users.

Page | 4
1.1. Specifications for CORE/Manager
AVAILABLE MODELS
Mounting: Wall, Ceiling, or Table-top
Storage: mSATA SSD
Endpoint Capacity: ~120, additional
endpoints can be added via Autani
CORE/Manager add-ons
Operating System: Secure Linux-based
variant
POWER SUPPLY
Voltage: 120VAC input / 12VDC output
Power: 13 watts max.
I/O SUPPORT
LAN: 1x10/100/1000 Ethernet, TCP/IP v4
USB: 1 USB 2.0 and 1 USB 3.0 host
interfaces
PROTOCOLS
Wireless: 802.15.4 with mesh networking
Ethernet: HTTP/HTTPS
Security: Internal firewall, isolated
wireless and internal processors
UDP: 59370, 59371, 54261
TCP: 443
(required for remote access, outbound
secured VPN connection).
RADIO NETWORK (autaniNet)
IEEE 802.15.4-2003 2.4GHz ISM
Range: Up to 1500’ LOS transmit/receive
ENVIRONMENT
Operating Temperature: 10° to 40° C
Storage Temperature: -25° to 65° C
RECOMMENDED WEB BROWSERS
Google Chrome
Mozilla Firefox
PHYSICAL
Dimensions (HxWxD): 7.85”x7.81”x1.97”
Color: Autani White/Black
Weight: 1.6 lbs (0.7 kg)
INFORMATION LABELS
Located inside the device; remove the top
cover to see.
1.2. Package Contents
Autani CORE/Manager
Wall Plate
Back Plate
12V Power Supply
10’ Ethernet Cable
Mounting Screws
Documents: User Manual, License Key sheet

Page | 5
1.3. Regulatory Information
CORE/Manager,this device contains:
FCC ID: V8NZRB1000152
IC: 7737A-ZRB1000152
15.105 statement (for digital devices)
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the interference by
one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
1.4. Product Warranty
3 year limited warranty from Autani. For further information, please refer to terms and
condition on www.autani.com.
Autani Support.
Phone: 443.320.2233 x2
Address: 7090 Columbia Gateway Drive, Suite 140, Columbia, MD 21046
Autani Sales
Phone: 443.320.2233 x1
General Inquiries: information@autani.com
Hours of Operations: Monday to Friday, 9am to 5pm, Eastern Standard Time

Page | 6
2. System Overview
SINGLE SYSTEM CONNECTED TO EDGE DEVICES

Page | 7
MULTIPLE CORES CONNECTED TO MANAGER

Page | 8
3. Mounting Instructions
The Autani CORE/Manager can be mounted to a ceiling tile or wall, and should be mounted
within a range of 1000 feet line of sight to the controlling/communication devices, and near a
120VAC wall outlet. When using fixture controllers with the CORE/ Manager, please consult
with Autani support to determine the distance between edge devices and the CORE/Manager,
as these ranges may vary based on the edge device that is used.
NOTE: The CORE/Manager should NOT be installed near any type of heat sources. Specifically,
heating systems or areas that are receiving direct sunlight for the majority of the day.
3.1. Space Requirement
The CORE/Manager should be mounted with minimum clearances for ventilation and signal
transmission, as shown below.

Page | 9
3.2. Mounting the CORE/Manager onto a Wall
1. Position the wall plate on a wall and mark the four mounting holes. Remove the wall
plate and pre-drill the mounting holes.
2. Insert wall anchors into the mounting holes, and position the wall plate to align with the
mounting holes.
3. Insert the screws through the wall plate into the mounting holes. Tighten the screws.

Page | 10
4. Insert the CORE/Manager into the groove on the wall plate. It will snap into place.
Inhaltsverzeichnis