www.productivity2000.com Tech Support 770-844-4200
4
WARNING: To minimize the risk of potential safety problems, you should follow all appli-
cable local and national codes that regulate the installation and operation of your equip-
ment. These codes vary from area to area and it is your responsibility to determine which
codes should be followed, and to verify that the equipment, installation, and operation are
in compliance with the latest revision of these codes.
Equipment damage or serious injury to personnel can result from the failure
to follow all applicable codes and standards. We do not guarantee the products
described in this publication are suitable for your particular application, nor do we
assume any responsibility for your product design, installation, or operation.
If you have any questions concerning the installation or operation of this equipment,
or if you need additional information, please call Technical Support at 770-844-4200.
This publication is based on information that was available at the time it was print-
ed. At AutomationDirect.com® we constantly strive to improve our products and services,
so we reserve the right to make changes to the products and/or publications at any time
without notice and without any obligation. This publication may also discuss features that
may not be available in certain revisions of the product.
Typical Relay Life
Voltage & Type of Load Operations at 4A Load Current
30VDC Resistive
30VDC Solenoid
120VAC Resistive
120VAC Solenoid
100,000
100,000
100,000
100,000
General Specifications
Operating Temperature 0° to 60°C (32° to 140°F),
Storage Temperature -20° to 70°C (-4° to 158°F)
Humidity 5 to 95% (non-condensing)
Environmental Air No corrosive gases permitted
Vibration IEC60068-2-6 (Test Fc)
Shock IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation 1800VAC applied for 1 second
Insulation Resistance >10MΩ@ 500VDC
Heat Dissipation 3W
Enclosure Type Open Equipment
Module Keying to Backplane Electronic
Module Location Any I/O slot in a Productivity2000 System.
Field Wiring
Use ZIPLink Wiring System or removable terminal
block (not included). See “Wiring Options” on
page 3.
EU Directive
See the “EU Directive” topic in the Productivity
Suite Help File. Information can also be obtained
at: www.productivity2000.com
Connector Type (not included) 18 position removable terminal block
Agency Approvals
UL 61010-1 and UL 61010-2-201 File E139594,
Canada and USA
CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-
2-201 Safety)*
*Meets EMC and Safety requirements. See the D.O.C. for details.
Removable Terminal Block Specifications
Part Number P2-RTB P2-RTB-1
Number of
Positions 18 Screw Terminals 18 Spring Clamp Terminals
Wire Range
30–16 AWG (0.051–1.31 mm²)
Solid / Stranded Conductor
3/64 in. (1.2 mm) Insulation Maximum
1/4 in. (6–7 mm) Strip Length
28–16 AWG (0.081–1.31 mm²)
Solid / Stranded Conductor
3/64 in. (1.2 mm) Insulation Maximum
19/64 in. (7–8 mm) Strip Length
Conductors “USE COPPER CONDUCTORS, 75°C” or Equivalent.
Screw Driver
Width 0.1 inch (2.5 mm) Maximum*
Screw Size M2 N/A
Screw Torque 2.5 lb∙in (0.28 N∙m) N/A
*Recommend Screw Driver TW-SD-MSL-1