BA SYSTEMS BAS 918S Bedienungsanleitung

BA Systems—Petershvilevej 1—DK-3200 Helsinge—http://www.basystems.dk
BAS 918S/929S Manual
Manual
BAS 918S/929S

BA Systems—Petershvilevej 1—DK-3200 Helsinge—http://www.basystems.dk 2
BAS 918S/929S Manual
Table of content
Introduction...............................................................................................................3
Materials included.....................................................................................................4
Product mount ..........................................................................................................5
Installation ................................................................................................................6
Terminals description.............................................................................................9
Functional description ..........................................................................................10
Option Module connection ...................................................................................14
Modbus................................................................................................................15
BACnet ................................................................................................................15
BAS918S configuration........................................................................................16
BAS929S configuration........................................................................................17
Scheme list ..........................................................................................................18
Scheme introduction ............................................................................................19
Scheme 1, Central heating...................................................................................20
Scheme 2, Central heating and Hot water tank....................................................26
Scheme 3, Central heating with Heat Exchanger .................................................35
Scheme 4, Central heating with Heat Exchanger and Hot water tank ..................41
Scheme 5, Dual Central heating ..........................................................................50
Scheme 6, Dual Central heating with Heat Exchanger.........................................58
Basic Controller operation.......................................................................................66
Menu structure.....................................................................................................66
Scheme selection ................................................................................................67
Scheme activation ...............................................................................................68
Regulation mode..................................................................................................69
Scheme setup......................................................................................................70
Info Screen .........................................................................................................72
Watch Screen ......................................................................................................72
Setup for IP access.................................................................................................73

BA Systems—Petershvilevej 1—DK-3200 Helsinge—http://www.basystems.dk 3
BAS 918S/929S Manual
Introduction:
Thank you for choosing a BAS 918S/929S controller.
Please make sure that you have received the correct
controller version and all the materials included.
The difference between the two controllers are only the
supported I/O. Please look at the following illustrations.
The controller is scheme-based. This means that a set
of preinstalled control schemes may be selected. Each
scheme is shown as a process diagram named
Scheme. The installation to be used is the selected.
Once a scheme has been selected it can be
customized. Please see the description of the different
schemes later in this manual.
On the next pages in this manual you will be guided
through the physical installation and maneuvering
the single button user interface.
Technical data
Power supply 24VAC/DC or 240VAC
Power < 6W
Digital outputs Solid state relay
BAS918S: 6 channals
BAS929S: 11 channels
Max 1A ved 240VAC/DC, must
be protected against inductive
loads.
Thermal Storage -20 °C to +70 °C
Operational -10°C to +60°C
Analog outputs BAS918S: 2 channals
BAS929S: 4 channals
Port 1..4: 0/2-10VDC
Port 3,4:, 0/4..20mA
Humidity Max. 90% RH,
Non condensing
Analog inputs BAS918S: 8 channals
BAS929S: 10 channals
Port 1..10: 0-1600 ohm (PT1000)
Port 1,3,5,7,9,10: 0/2-10V
Port 9,10:0/4-20 mA DC
Port 9,10:0..44900 ohm (NTC)
Mechanical ABS/PC, IP21
115.4 x 185.7 x 53 mm
570 g
Communication 10/100 Mbit ethernet
USB-Host or USB-Device
Optional internal module:
KNX, LON, MBUS, WMBUS
eller RS485
Real time clock ±12 minutter pr year at 20°C.
The RTC can run more than
1 year without power
applied. Can be adjusted
over the IP (ethernet)
connection, either directly or
through the SCADA system.
Digital inputs 4 x potential free contacts or max
12VDC.
User interface 3.5 inch colorscreen and
two-way scroll wheel with
pushbuttom select.

BA Systems—Petershvilevej 1—DK-3200 Helsinge—http://www.basystems.dk 4
BAS 918S/929S Manual
Materials included:
1. Produkt socket
2. Produkt front
3. 4 pcs. of , 3.9mm x 32 mm screws for wall mount
4. Cable relief bracket for cable retention at socket
5. 2 pcs. of 3.0mm x 8 mm screws for cable relief bracket mounting (4)

BA Systems—Petershvilevej 1—DK-3200 Helsinge—http://www.basystems.dk 5
BAS 918S/929S Manual
Product mount:
The socket (1) may be wall mounted using 4 screws (3). Cable insertion may be done form
behind into the socket or from the connector end of the front. See illustration below.
Cut out area when
cables inserted
from behind
Cut out area when cables inserted
from this end
Use a sharp knife to cut the plastic along or within the lines of the markings. When
cutout is made in the connector end of the front, cables are inserted here and may be
retained in the socket using the cable releif bracket.
screw (3)
screw (3)
screw (3)
screw (3)
Cable relief bracket

BA Systems—Petershvilevej 1—DK-3200 Helsinge—http://www.basystems.dk 6
BAS 918S/929S Manual
Installation:
Generic socket connections are defined in placement and function in the following draw-
ings and descriptions.
This indicates the maximum I/O configuration for the BAS9XXS controller. Please note
that the variant you have bought may have reduced configuration.

BA Systems—Petershvilevej 1—DK-3200 Helsinge—http://www.basystems.dk 7
BAS 918S/929S Manual
Controller profile:

BA Systems—Petershvilevej 1—DK-3200 Helsinge—http://www.basystems.dk 8
BAS 918S/929S Manual
Controller front:
Dimensions for wall mount are indicated from above drawing.

BA Systems—Petershvilevej 1—DK-3200 Helsinge—http://www.basystems.dk 9
BAS 918S/929S Manual
Terminal descriptions:
Terminal
label
Definition Notes
240VAC 2 terminals
N = Nul
L = phase (Line)
100V-240V AC, 50Hz or 60Hz
Power supply. May be substituted by
24VAC or 24VDC
24VAC/DC 2 terminals
N = Nul / DC-
L = fase / DC+
24VAC, 50Hz - 60Hz or 24VDC, minimum 10W
When connected, 240VAC is discon-
nected in the controller internally.
May supply 24VDC/4W when
240VAC is sourcing power.
DOX (1-11) 2 terminals per I/O channels, Electronic relay. No
polarization required.
AC or DC
maximum 240VAC @ 1A
maximum 400VDC @ 1A
3750V Rms isolation
DIX (1-4)
DICOM
Potential free contact inputs with one common termi-
nal (DICOM) to be used in relation with each DIX
terminal.
DICOM is a 5V DC voltage, sourc-
ing maximum 50mA out. Protected
against voltage inputs up to +75V
peak. AC voltage protection only by
resistive fuse.
STPB 4 terminals for Stepper motor connection, maximum
4W drive capability. Up to 24V drive.
24VAC/DC power supply for extend-
ed drive capability. Max 20W pr
channal.
STPA Secondary Stepper motor connection. As above. 2 terminals combined with AO cur-
rent output capability. Not coexist-
ing, i.e. controller mounted with ei-
ther AO current output or second
stepper motor capability
OPX (1-3) 3 terminals for communication module support Module to be mounted from factory
and must be ordered when the con-
troller is ordered.
Modules available:
MBUS
RS485
KNX
LON
WMBUS
AOX (1-4) 2 terminaler for each analog output channel. Must be
polarized as indicated by + and – signs.
Output type
0/2-10V with max 10mA load
0/4 –20mA current loop, channel 3 and 4 only,
combined with Stepper motor output A.
When using current mode the – ter-
minal is still to be used at the primary
terminal block.
Protected against reverse polarity and
input voltages up to 40V
AIX (1-10) 2 terminals for each I/O channel. Must be polarized
as indicated by + and – signs.
Capability per I/O number:
Channel 1..10: 0-1600 ohm (PT1000)
Channel 1,3,5,7,9,10: 0/2-10V
Channel 9,10:0/4-20 mA DC
Channel 9,10:0..44900 ohm (NTC)
Protected against reverse polarity and
input voltages up to 40V.

BA Systems—Petershvilevej 1—DK-3200 Helsinge—http://www.basystems.dk 10
BAS 918S/929S Manual
Functional description:
Power supply
The Controller is supplied by the terminals 240VAC, accepting 90VAC-264VAC, 50Hz - 60Hz.
or
By the terminals 24VAC/DC, accepting 24VAC/50Hz/10% and alternatively 24VDC/25%.
If both power inputs are connected, the internal circuit will select the 24V source. The 240V
source is then disconnected internally.When 240VAC supply is used, the 24V pin set will
output 24V DC. Maximum power output is 4W.
In the center of the controller socket, 2 set of 10 pole terminal blocks are placed. By default all
terminals in each block has been shorted by a mounted shorting circuit (alternative circuits
can be ordered). The intension with this is to assemble Nul (-) and Phase (+) connections
internally distributing connections from here. Only one supply line into the controller is then
required. Alternative use will also apply.
Digital outputs
All ports are galvanic isolated from other channels as well as from the internal controlling
circuit. The circuit for one output (2 signal wires) is an Electronic relay, which may connect AC
or DC signals. This relay will apply a voltage drop of approximately 1V in closed state. When
operating a digital signal, this 1V drop may corrupt the signal level interpretation. In this case
a secondary relay must be inserted. Please see visualization below.
0
Circulation Pump
0-10V
RUN
.
DO2B
DOXB
D01B
BAS9XXS CONTROLLER
.
DOXA
D01A
DO2A
RUN
0
Circulation Pump
DO2B
0-10V
BAS9XXS CONTROLLER
.
DOXA
DOXB
D01B
D01A
DO2A
.
SECONDARY RELAY
3
1
2
4
24VAC/DC
0V
"DO" RELAY CONNECTED HAS
1V DROP OVER THE TERMINALS