Power supply .......................................................................................... 230/240 VAC 50/60 Hz +/- 10%
Power consumption ......................................................................................................................3,1 W
Range of relay contact switching free of voltage ............................................................. 10A 250V resistive
Insulation ........................................................................................................................... Class II
Types of gas detected ................................................................................. Natural Gas - for Natural gas
LPG- for LPG model
Detection sensor ....................................................................................................................... Catalytic
Alarm sensitivity ......................................................................................................... At 10% of L.E.L.
Precision of the detector ............................................................................................................. 1% FS
Sensor’s faults detected by Fault Circuit ................................................... Interruption, short circuit, or wear
Test Phase Duration ............................................................................................................. 60 seconds
Audible and visual signal alarm by ............................................................. LED diode and buzzer 85 dB at 1 m
Selection of relay working mode ........................................................................................ through Jumper
Test buttons ........................................................................................................................... built-in
Command electrovalve ................................................................................................ class A o classe B
Functioning Temperature ............................................................................................... -10°C to +40°C
Functioning Humidity ......................................................................................... 0÷90% RH not condensed
Degree of protection ...................................................................................................................... IP42
Dimensions ......................................................................................................................... 120x80x37
CHECK the integrity of the probe after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of thedetectorforpurposesotherthantheintendedoneisconsidered improper,andas aresultofwhichBEINAT
S.r.l. therefore disclaims any responsibility for possible damages caused to people, animals or objects.
INSTALLATION
When performing the installation, please remind that if you pierce the RGX1002 container, it will lose its properties
and its conformity to REGULATIONS.
TERMS and EXPECTATIONS: The installation of the RGX1002detector, its ordinary and extraordinary maintenance,
and its out of service removal at the end of the functional life guaranteed by the manufacturer, must be carried out
by authorized and/or specialized personnel.
Do not allow it to become wet.
The detector can be seriously damaged when immersed in water.
Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.
Avoid abrupt temperature fluctuations.
Sudden temperature variations can cause condensation and the probe could work poorly.
Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.
Absolutely avoid using any cloth dipped in thinners, alcohol and chemical detergents.
Disposal of the device
Concerning the conservation, the protection and the improvement of the quality of the environment, as well as for the
protection of human health and the careful and rational use of natural resources, the device has to be the object of
aselective collection for he disposal of electronic equipmentsand can not be disposed withthecommon domestic waste.
The user thus has the obligation to separate the device of the other waste to ensure that it is recycled in a sure way
for preserving the environment For more details on the sites that are involved in the collection, contact the local
administration or the distributor of this product.
Precautions
Functional Features Of Gas Sensors
The installation of the RGX1002 detector, its ordinary and extraordinary maintenance, and its out of service
removal at the end of the functional life guaranteed by the manufacturer, must be carried out by authorized and/
or specialized personnel.
The CATALYTIC technology sensor duration is guaranteed for 6 years (in clean air).
The detector’s functioning temperature ranges from -10°C to + 40°C.
WARNING!
The CATALYTIC probe does not tolerate a gas detection exceeding 100% of L.E.L., with consequent natural
death of the sensor.
Each immediate puff of gas that exceeds 100% of L.E.L. takes away months of life from the sensor.
The detector must be tested by simulating the presence of gasby issuing it from apre-calibrated testing aerosol.
A common cigarette lighter near the sensor does not guarantee excellent functioning.