II. MOUNTING INSTRUCTIONS (General)
INDOOR MOUNTING ONLY -
To achieve optimum protection, the air curtain should be
mounted on the inside of the building, ush to the wall and
as close to the top of the door opening as possible. To ensure
peak performance, keep the air stream free of obstructions.
The air curtain will not perform properly if negative air
pressure exists in the building. Under these conditions,
a means for makeup air to the building must be provided
so that the air pressure on both sides of the opening is in
balance.
Before mounting the air curtain, check the supporting structure
to verify that it has sucient load-carrying capacity to support
the weight of the air curtain(s). The mounting hardware
(supplied by others) should be capable of supporting a
minimum of three (3) times the weight of the air curtain.
See Table 1.
IMPORTANT: A minimum of 4”is required above the top rear
corner of the air curtain for the installation and removal of the
inlet screen, and to ensure proper airow.
A. When determining the mounting location for the air
curtain(s), make sure that nothing interferes with the
curtain of air developed when the discharge vanes
are directed from 0° to 20° toward the door opening. If
the air stream strikes any obstruction (the top edge of the
doorway, a door opening device, etc.), the eectiveness
of the air curtain will be greatly reduced. See Figure 2.
B. For optimum performance, the bottom of the air curtain
(discharge nozzle) should be no more than 1” above
the top of the door opening with the air curtain(s)
mounted ush to the wall. If the air curtain must be
mounted higher, it must be spaced out from the
wall 3/8”for every inch the air curtain is above the door
opening. See Figure 3. For optimum protection, any void
between the air curtain and the wall should be sealed
along the full length of the air curtain.
C. Do not block (obstruct) the air intake screen. Insucient
airow can cause the unit to overheat.
D. The air curtain(s) shall:
1. Have a minimum clearance of at least 4”
from the sides and 4" from the top.
2. Have a minimum clearance of at least 6’
between the bottom of the air curtain and the oor.
3. Be installed Indoors Only.
E. Proceed to either Section III - WALL MOUNTING or
Section IV - SUSPENDED MOUNTING
Figure 2 - General Mounting
Figure 3 - Wall Mounting Location
TABLE 1 - Weight Chart
A. PREPARATION
1. Locate the wall mounting plates, in the carton that
contained the unit. See Figure 4. For units over 72",
there are more than two wall mounting plates.
2. Use ¼"-20 bolts to attach the wall mounting plates
to the back of the air curtain.
III. WALL MOUNTING
20°
AIR
Discharge
Nozzle
A
I
R
A
I
R
INTERIOR
EXTERIOR
6' minimum
AIR
Airstream
4" minimum
side & top
clearance from
combustible
material
MODEL
Net Weight
MODEL
Net Weight
AI10
Amb.
AI10
Elec.
AI10
Steam
AI10
Hot
Water
AI08
Amb.
AI08
Elec.
AI08
Steam
AI08
Hot
Water
AI10-E-1036 85 88 110 107 AI08-E-1036 48 53 68 68
AI10-E-1042 94 97 122 119 AI08-E-1042 53 58 76 75
AI10-E-1048 110 113 141 138 AI08-E-1048 58 63 83 83
AI10-E-1060 119 122 156 153 AI08-E-1060 69 74 99 99
AI10-E-2072 170 176 216 210 AI08-E-1072 79 89 117 117
AI10-E-2084 188 194 240 234 AI08-E-2084 106 116 149 149
AI10-E-2096 220 226 278 272 AI08-E-2096 116 126 164 164
AI10-E-2108 229 235 293 287 AI08-E-2108 127 137 180 180
AI10-E-2120 238 244 306 300 AI08-E-2120 138 148 196 196
AI10-E-3132 305 314 384 375
AI10-E-3144 330 339 415 406