GAS CONNECTIONS
1. The installation of this appliance must
conform with all applicable local codes.
In the absence of local codes, the installa-
tion must conform to the latest level of the
National Fuel Gas Code, ANSI Z223.1.
In Canada, the installation must be in ac-
cordance with the current CAN/CGA
B149.1 and B149.2.
2. This appliance will ship without the regu-
lator connected. Note all black pipe con-
nections require an approved gas pipe
thread sealent.
3. This appliance is designed to work with
either natural gas or LP gas. Verify that
the appliance and the incoming gas supply
are compatible. Check the rating plate.
4. The gas supply line must be the same size
or larger than the gas inlet of the appli-
ance. Your appliance has an ½” NPT
gas inlet connection. We recommend the
supply line be ¼” NPT larger than the gas
inlet of the appliance.
5. Sealant used on pipe joints must be ap-
proved for use with combustible gases.
6. An installer provided manual shut-off
valve must be installed in the gas supply
line ahead of the appliance. This shout-
off must be easily accessible in case of
emergency.
7. All gas cooking equipment must have a
pressure regulator on the incoming service
line for safe and efficient operation.
Such a gas pressure regulator has been
provided with this appliance. Incoming
gas pressure should be checked with a
manometer. The correct manifold pres-
sure for natural gas is 5.0” wc. For LP
gas the correct manifold pressure is 10”
wc.
8. Incoming line pressure upstream of the
appliance should be 1.0” wc greater than
the operating manifold pressure. Service
pressure may fluctuate for a variety of rea-
sons. Under no circumstances should the
factory supplied regulator be removed or
by-passed.
9. The factory supplied pressure regulator
will withstand an input pressure of ½ PSI
(12” w.c.). If the incoming pressure ex-
ceeds the maximum rating a step-down
regulator is required.
10. The appliance and its individual shut-off
valve must be disconnected from the gas
supply line during any pressure testing in
excess of ½ PSI [3.5 kPa].
11. The appliance must be disconnected from
the gas supply by closing its individual
shut-off during any pressure testing less
than ½ PSI [3.5 kPa].
12. Check to see that all installer –supplied
pipes and fittings are clear of direct,
threading chips or other foreign particles
before connecting the appliance to the
supply line. Such particles will clog ori-
fices and/or valves when pressure is ap-
plied. Service to clean such clogs is not
covered by your warranty.
13. The incoming gas supply is brought from
the inlet pipe. This is the only connection
required via the installer-supplied shut-off
valve.
14. If the appliance is to be installed with
flexible couplings and/or a “quick discon-
nect” the installer must use a commer-
cially approved AGA Design certified
flexible connector at least ½” NPT that
complies with ANSI Z21.41. In Canada
the connector must comply with CAN
16.10-88 and the “quick disconnect” de-
vice must comply with CAN 16.19M-79
and installed with a strain relief device.
15. Before putting the appliance into service
test all gas connections for leaks. Use a
soapy solution. DO NOT USE AN OPEN
FLAME TO CHECK FOR LEAKS. Such
INSTALLATION