7.0 DEFAULT ETTING – AND WHAT EACH MENU DOE
Page 9 of 11
Default Default
Un 415 Set L-L system volts PFC ON Selects whether steps are on AUTO-HOLD-ON-OFF
t 1 Set CT ratio :1 CPI 1 Target Cosphi
Pt 1 Set VT ratio :1 St 10S Switching Time
Ai NO Automatic Initialisation?YES/NO OUt AUTO Selects what each output does.
AUTO-Fon-Foff—AL( starts up ventilation fan )
Expert Menus 200 – 600
To get into these please call your
supplier
200 MEA URING 400 CAPACITOR DATABA E
201 415 Sets system Voltage Level Un
( repeat of Un in Menu 100 )
401 75 secs Set discharge time to prevent
re-energisation on quick switching sequence
202 1 Sets CT ratio:1 (repeat of Menu
100)
402 5 var
(1.max)
Manual entry of kvar values per step
203 1 Set VT ratio:1 (repeat of Menu
100)
403 AUTO
All
steps
Select what each output does
Same as Out setting in 100 menu
204 10% Tolerance % of Un Voltage Setting 404 0 Step switch counter
Initial value 0 increases with each switching
205 YES Select L-L or L-N as measurement
voltage
500 ALARM
206 90º Select Phase Angle U - I 501 YES Select if alarm display is cancelled when fault cleared or
not
207 NO Ai ( Automatic Initialisation) start 502 YES THD Alarm setting YES = on
NO =off
208 NO Activate Step kvar Recognition 503 5% % setting for THD alarm if on
209 AUTO Frequency setting for low quality
networks
504 NO Select if steps are switched off if THDU above target level
210 0ºC Temp setting offset 505 60 secs Select time delay of THDU alarm
506 NO Freeze exits if no CT current
300 CONTROL 507 YES YES=Service alarm operates when max operating hours or
switchings on any step is reached.
301 60% % value of kvar for step switching. 508 80,000 Set No. of contactor operations for Alarm
302 1.00 Target PF 1 509 9,000 Set No. of operating Hours for Alarm
303 0.95i Target PF 2 510 NO Temperature sensor is set to monitor temp and show it in
the LCD Display.
304 NO Target PF when exporting 511 NO Select if Digital input is n/c or n/o
305 10 S Switch Time per step in seconds 512 NO Temp. Alarms 513/514 ON/OFF
306 2S Step switch swap over time 513 30ºC Temp Setting for exit relay nominated as fan control
307 YES Activation of Step swap over 514 70ºC Emergency switch off of steps one by one if temp exceeds
target setting – default = 70ºC
308 NO Stop Automatic kvar step
detection
515 NO Target Cosphi setting
309 YES Blocking defective Capacitor Steps 516 YES YES= Alarm for defective step if no step kvar output after
3 attempts
310 ON AUTO-OFF-HOLD setting 517 YES Step power loss alarm
311 1 Selection of switching sequence.
1=Auto.,2=Last in first
out,3= ombifilter ,4=Progressive
600 ALARM RE ET
312 0 Reactive kvar offset 601 NO All alarms back to factory default
313 1 Assymetrical Switching
fast in slow out etc.
602 NO Resets all recorded data of kvar per step+kvar output of
each step
314 NO Switch off steps if cosphi is
leading. Used for aux.generators
603 NO Resets Operating Hours to zero
604 NO Resets Average PF
605 NO Rests Highest Ambient Temp
606 NO Reset all alarms
607 NO Displays software version
608 NO Gives password