40MUAA: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
Connectors
Table 2 — Unit Configuration Settings
*NOTE: Auto detection is available after serial number 0223V26809. With this feature active, the system detects the wiring
method according to the 3 control scenarios automatically with all SW1 dip switches set to default.
NOTE: After the serial number (0223V26809) the auto detection feature is available; prior to the serial number cutoff, the
control scenario needs to be set for Scenario 1(SW 1-1 ON) and Scenario 3(SW 1-1 and SW 1-4 ON).
Dial Code Control Scenario Function ON OFF
SW1-1*
OFF for 2 ON for 1 and 3
Please note: SW 1-4
needs to be ON as well
for Scenario 3
Control Function 24 V Communication [Default] Auto Detect or RS485 S1-S2
Communication
SW1-2 1,2 Anti-cold blow protection option NO [Default] YES
SW1-3 1,2,3 Single cooling / heating and cooling
options Cooling [Default] Cooling & Heating
SW1-4*
OFF for 1 and 2 ON for 3
Please note: only active
for scenario 3 when
used with SW 1-1 ON
Control Function Scenario 3 [Default] Auto Detect or Scenario 1
SW2-1 1
Compressor Running Compensation
(Demand working with heat pump+
Electric heat)
Compressor slower speed [Default] Faster Compressor
SW2-1 2
Temperature differential to activate
first stage auxiliary heat (the GAP of
T1 and Ts) Wire controller demand
with heat pump + Electric heat
working together
2F [Default] 4F
SW2-2 2 Electric heat on delay YES [Default] NO
SW2-3 2 Electric auxiliary heating delay to start
time 30 minutes [Default] 15 minutes
SW2-4 2 Compressor/Auxiliary heat outdoor
ambient lockout
The compressor does not operate if
the outdoor temperature is lower than
the temperature represented by S3
[Default] The heater does not operate if
the outdoor temperature is greater than
the temperature represented by S3
Rotary
Switch S3 2Set outdoor temperature Limitation
(for auxiliary heating or compressor)
0 means that the temperature
protection is not turned on, the dial
range is 1 through F, 1 equals -4°F
and it increased up to 46°F
SW3-1 1
Maximum continuous runtime allowed
before system automatically stages
up capacity to satisfy set point. This
adds 1 to 5°F to the user set point in
the calculated control point to
increase capacity and satisfy user set
point
30 minutes [Default] 90 minutes
SW3-2 1 Cooling and heating Y/Y2 compressor
speed adjustment. Compressor slower speed [Default] Faster Compressor
SW3-3 1
Compressor Running (demand
working with heat pump+ Electric
heat)
Compressor slower speed [Default] Faster Compressor
SW3-3 2
Temperature differential to activate
second stage auxiliary heating (the
GAP of T1 and Ts) Wire controller
demand with heat pump + Electric
heat working together
4F [Default] 6F
SW3-4 1,3 Fan speed of the COOLING mode
when 24V thermostat is applied for. Turbo Off
SW4 1,2,3 Electric heat nominal CFM adjustment
Available settings are 000/001/010/
011. Each digit corresponds an
individual switch position
(e.g. [SW4-1 OFF, SW4-2 ON,
SW4 -3 OFF] = 010).
S4-1 1,3 Default ON
[Default] For single stage
supplemental heat, W1 and W2 are
connected
For dual stage supplemental heat, W1
and W2 are controlled independently.
S4-2 1,3 DH function selection [Default] Dehumidification
control not available
Dehumidification feature is enabled
through thermostat