Ductable air-cooled scroll
chillers and heat pumps
8
5. TECHNICAL CHARACTERISTICS
HEE version
30PA/PH 90HEE 100HEE 120HEE 160HEE 180HEE
Cooling
capacities
Net cooling capacity (kW) 18,40 21,00 25,50 31,40 35,70
Net power input (kW) 7,20 7,95 9,10 11,50 13,60
Net efficiency EER 2,55 2,64 2,81 2,74 2,62
Seasonal efficiency ESEER 2,89 2,99 3,20 3,14 3,03
Heating
capacities
Net heating capacity (kW) 21,40 23,90 29,30 36,40 42,50
Net power input (kW) 7,10 7,90 9,50 11,90 13,90
Net efficiency COP 3,03 3,03 3,08 3,05 3,05
Seasonal efficiency
Average climate
SCOP 2,98 2,95 3,29 3,18 3,09
ŋs Heat 116% 115% 129% 124% 121%
Prated (kW) 15,92 17,74 21,94 26,77 30,87
Seasonal efficiency
Warmer climate
SCOP 3,41 3,58 3,82 3,67 3,65
ŋs Heat 134% 140% 150% 144% 143%
Prated (kW) 13,09 14,68 18,01 22,41 25,89
Outdoor
circuit
plug-fan
Nominal air fl ow (m3/h) 6500 7000 10000 12200 14000
Nominal available static pressure (mm.w.c.) 20
Maximum available static pressure (mm.w.c.) 63,7 70,3 45,6 65,1 62,7
Number / diameter 1 / 500 1 / 560 2 / 560
Motor output (kW) 2,7 2,8 3,0 2 x 3,0
Power input (kW) 1,33 1,21 1,87 2,20 2,52
Speed (r.p.m.) 1700 1780 1500 1500
Indoor
circuit
Nominal water fl ow (m3/h) 3,2 3,7 4,5 5,4 6,2
Pressure drop (m.w.c.) 1,6 2,1 1,6 2,4 3,1
Minimum water fl ow (m3/h) 2,5 2,9 3,4 4,1 4,6
Maximum water fl ow (m3/h) 6,6 7,4 9,1 11,3 12,8
Type of hydraulic connections Rosca gas
Diameter of connections 1 1/4” M 1 1/2” M
Compressor
Type Scroll
Number of compressors / stages / circuits 1
Oil type Copeland 3MAF 32 cST, Danfoss POE 160 SZ, ICI Emkarate RL 32 CF, Mobil EAL Artic 22 CC
Volume of oil (l) 3,0 3,3 3,3 3,3 6,2
Refrigerant
Type R-410A
Global warming potential (GWP) 2.088
Charge (kg) 6,0 6,3 6,8 8,9 9,2
Environment impact (tCO2 e) 12,5 13,2 14,2 18,6 19,2
Electrical
characteristics
Electrical power supply 400 V / III ph / 50 Hz (±10%)
Power supply 3 Hilos + Tierra + Neutro
Maximum
absorbed
current
Compressor (A) 15,2 17,3 20,5 25,4 30,5
Fan (A) 4,2 4,3 4,6 9,2 9,2
Control (A) 0,9 0,9 0,9 0,9 0,9
Total (A) 20,3 22,5 26,0 35,5 40,6
Dimensions
Length (mm) 1117 1398 2113
Width (mm) 860 860 860
Height (mm) 1447 1727 1447
Weight Empty (kg) 294 351 368 450 455
In operation (kg) 298 358 376 465 468
Cooling capacity calculated in accordance with the EN-14511-2013 standard given for outlet water temperature conditions of 7ºC and 35ºC outdoor temperature.
Heating capacity calculated in accordance with the EN-14511-2013 standard given for outlet water temperature conditions of 45ºC and 6ºC WB outdoor temperature.
Total power input by compressor, motorised fan and electronic control under nominal conditions, calculated in accordance with the EN-14511-2013 standard. Options are not
included.
European Seasonal Energy Efficiency Ratio (ESEER) obtained in accordance with the calculation conditions established by the certification body EUROVENT.
Values calculated in accordance with the EN-14825-2013 standard given for bivalente temperature of -5ºC in average climate and 2ºC in warmer climate.
Motors that are more energy efficient than what is established by the ErP 2015 standard.
Climatic warming potential of a kilogram of fluorinated greenhouse gas in relation to a kilogram of carbon dioxide over a period of 100 years.