CIAT CIATControl OPC Server Bedienungsanleitung

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [1]
V05.2012
CIATControl OPC Server
OptimumcontrolforHysyssystemsolutionsforoffices,
hotelsandseniorcitizenresidences
Installationandoperating
instructions
Description:
•StandardOPCcommunicationsolution
•Centralisationofthesystem'svariousCIATControlsonanOPC‐compatibleBMS
•Largerangeoflicencesformonitoring:
o1CIATControl
o2to5CIATControls
oOver5CIATControls
•Quick,intuitiveinstallation
Includes:
•InstallationCD
•Dongle(licence)
•Installationandoperatinginstructions
Tobecarriedoutbytheintegrator:
•InstallationoftheOPCserverontheBMS
•CIATControlIPconfiguration
•CIATControldeclarationviatheOPCserverconfigurator
•SelectionofpointstobeindicatedontheBMS

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [2]
V05.2012
1. LISTOFEQUIPMENT
No.DescriptionQuantityComment
1InstallationCD1Minimumrequirements:
WindowsXP/7/Server2008compatible
Processor:1.6Ghz
RAM:1Gb
Diskspace:1Gb
CDplayer
1USBportavailable
.NetFrameworkversion2.0
2Dongle(licence)1TobeconnectedtotheUSBport
3Installationandoperatinginstructions1‐
2. INSTALLINGTHESOFTWARE
InserttheinstallationCDintheCDplayer.
Doubleclickontheicontolaunchtheinstallation.Thefollowingwindowappears.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [3]
V05.2012
Followtheinstallationinstructionsandclickon"Finish"afterselecting"Yes,Iwanttorestartmycomputernow".
Note:makesureyoucloseallyouropendocumentsbeforeclickingon"Finish".
Afterrestartingyourcomputer,theOPCserverwillbeoperational.
Connectthedongletoactivatethelicence.
3. CONFIGURINGTHESTATIONS
1/ConfiguringtheCIATControls
ConfigureeachCIATControlwithafixedIPaddress.
Todothis,identifyyourselfasa"User",clickon"Parameters"andselectthe"Ethernetconfiguration"tab.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [4]
V05.2012
ConnectanRJ45cabletooneofthe2EthernetportsontheCIATControl.
Note:eachCIATControlhasadefaultDHCPsetting.
OnceanaddresshasbeenassignedtotheCIATControl,theactiveboardisdisplayed.
Select"Static"andentertheinformationsuppliedbythenetworkadministrator(orthatassignedbytheDHCPserver):
‐IPaddress
‐Subnetmask
‐Gateway
Clickon"Send"toconfirmtheconfiguration.
Note:ifseveralCIATControlsarepresentonthenetwork,pleasemodifythecomputername(defaultname:
CIATCONTROL)toauniquenametoavoidconflicts.TheCIATControlwillneedtoberestartedafterthenamehasbeen
modified.
CarryoutthesameoperationoneachCIATControl,takingcaretoassigndifferentfixedIPaddressesforeach
CIATControl.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [5]
V05.2012
2/ConfiguringtheOPCserver
In"Start","Programs",clickon"OPCServerConfigurator".
Thefollowingwindowopens.
Clickon"NEW"toaddaCIATcontrol.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [6]
V05.2012
EnteranameforthisequipmentanditsfixedIPaddress,thenclickon"OK".
Clickon"PING"tocheckthecommunicationwiththeequipment.
Itsstatusswitchesto"Success".
RepeattheoperationforeachCIATControl.
WhenalltheCIATControlshavebeenconfigured,closetheapplicationbyclickingonthecrossinthetopright.
TheOPCserverisnowconfigured.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [7]
V05.2012
AnyOPCclientcanconnecttheOPCservertoaccessthevaluesforalltheCIATControlsavailableonthesystemand
declaredontheserver.
Notes:
OtheractionsarepossiblefromtheOPCserverconfigurator:
‐"MODIFY":usedtomodifythenameorIPaddressoftheequipment
‐"DELETE":usedtodeletetheequipment
‐"REFRESH":usedtostartapingforalltheequipmentonthelist
‐"SETTINGS":usedtoconfiguretheOPCserverparameters
The"SETTINGS"menuisusedtomodifythefollowingparameters:
‐Booleanvalueistrue:appliestoallOPCitemscreatedwiththebooltype;iftheboxischecked,thevalue
codedfortrueis1;iftheboxisnotchecked,itis‐1.
‐Reconnectevery:frequencyofreconnectiontoastationdeclaredabsentonthenetwork.Whenastationis
declaredabsentafteralossofcommunication,theOPCserverusesthisfrequencytocheckthatthestation
hasreturnedtothenetwork
‐Refreshtime:waitingtimeactivatedwitheacheventpriortostationupdate.Thisisused,forexample,when
addingitemstothestationformonitoring:itisusedtosendthelistofitemstobemonitoredonceallthe
itemshavebeendeclared,ratherthanupdatingthestationeachtimeanitemisadded/deleted.Inparticular,
thissavestimewheninitialisingtheOPCserver
‐Disconnectiontime:waitingtimepriortodisconnectionofthelinkbetweentheOPCserverandthestationfor
whichnoitemsarereadbytheOPCserver
‐Dataservertestfrequency:cyclicaltesttocheckforthepresenceofthestation(useofthepingcommand)
‐TCPtimeout:configurationofthetimeoutperiodontheTCPcontrolwhencheckingforthepresenceofthe
stationonthenetwork
‐Nativetypeisstring:appliestoOPCitemsforwhichthetypeisdefinedasstringiftheboxischecked.
Otherwisethetypeisundefined
‐Addressseparator:characterusedtoseparatethedifferentfieldsoftheOPCaddress(devicefield,network
field,variablefield,etc.)
4. USE
TheOPCserverlaunchesautomaticallywhenanOPCclientattemptstocommunicatewiththeCIAT.CIATControlOPC
Server.DAserver.
AnyOPCclientcannowselecttheitemshewishestomonitor(seesections7to10fortheitemsavailableforeachtype
ofequipment).
TheOPCserverhasthefollowingbuttons:
‐Stations…:usedtocheckthestationsinterrogatedbytheOPCclient;itispossibletorefreshtheconnections
orattempttoreconnectifthereisalossofcommunicationwithoneofthestations.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [8]
V05.2012
‐Exit:usedtoclosetheOPCserver.Ifequipmentisaddedtotheserver,itisrecommendedtoshutdownthe
serverbeforeconfiguring,otherwiseanymodificationswillonlybetakenintoaccountoncetheOPCserveris
restarted.
‐Group:usedtoindicatetheitemsreadbytheOPCclient.Thefulladdressisindicated,aswellastherefresh
timeandvalue.
‐Badaddresses:usedtoindicateincorrectaddressesread/writtenbytheOPCclient.Iftheseaddressesdonot
exist,theywillbedirectlyplacedinthismenu.
‐Groupdetails:givesageneraloverviewoftheOPCserveraswellasthevalueoftheparameterssetintheOPC
serverconfigurator.
‐Filter:usedtoapplyafiltertotheitemslistedinthetable.Simplyenterthecharacterspresentintheaddress
ofeachitem.Thefilterrefreshesautomatically.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [9]
V05.2012
ImportantnotesfortheinstallationprocedureviaOPC:
‐Thevalueswrittenintheequipmentparametersarenotstoredinthedatabase.Whenreplacingthe
modules(inoperativemodule),theparametervaluesshouldbechangedagain.Onlythevaluessetviathe
CIATControlscreenarestoredinthedatabase.
‐TakecarewhenwritingtheparametervaluesforV3000typemodules.Whenaparameterismodified,the
V3000restartsautomatically.Itthenlosesthecontextinwhichitwasswitchedto"Auto"mode.Itwillnot
switchbacktothemoderequestedbythetimeschedulewhenthemodenextswitches.Topreventthis,the
OPCclientmustsendthecommandtotheV3000inordertomakeitswitchbacktothemodeitwasin
beforetherestart.
‐TheitemsavailableforeachpieceofequipmentaredisplayedinFrenchonly.
5. UNINSTALLING
Touninstallthesoftware,theOPCservermustbeshutdown,whichrequiresalltheOPCclientstobeclosed.
Doubleclickonthe"CIAT"iconinthebottomrightofthetaskbar.
Thefollowingwindowopens.Clickon"Exit"andconfirmthattheapplicationhasclosed.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [10]
V05.2012
In"Configurationpanel",clickon"ProgramandFunctions"(Win7)or"Add/Removeprograms"(WinXP/Win
Server2003/2007).
Select"CIATControlOPCServer"andclickonuninstall.Thefollowingwindowopens.Followtheinstructions.
Inhaltsverzeichnis
Andere CIAT Steuereinheit Handbücher

CIAT
CIAT MAGISTER Series Bedienungsanleitung

CIAT
CIAT V3000 KNX Gebrauchs- und Wartungshandbuch

CIAT
CIAT XtraConnect 2 Leitfaden

CIAT
CIAT microciat MRS2.2A Leitfaden

CIAT
CIAT CS1B Bedienungsanleitung

CIAT
CIAT Vectic Bedienungsanleitung

CIAT
CIAT Magister 2 Series Leitfaden

CIAT
CIAT AeroCONNECT 1B Gebrauchs- und Wartungshandbuch
Beliebte Steuereinheit Handbücher anderer Marken

Festo
Festo Compact Performance CP-FB6-E Stücklistenhandbuch

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Bedienungsanleitung

JS Automation
JS Automation MPC3034A Bedienungsanleitung

JAUDT
JAUDT SW GII 6406 Series Kurzanleitung

Spektrum
Spektrum Air Module System Bedienungsanleitung

BOC Edwards
BOC Edwards Q Series Bedienungsanleitung