Condair UDC Bedienungsanleitung

Condair sensor and controller range
2601066-B EN 2107
INSTALLATION AND
OPERATION MANUAL
Humidication and Evaporative Cooling

Thank you for choosing Condair
Installation date (MM/DD/YYYY):
Commissioning date (MM/DD/YYYY):
Site:
Model:
Serial number:
Proprietary Notice
This document and the information disclosed herein are proprietary data of Condair Group AG. Neither this docu-
ment, nor the information contained herein shall be reproduced, used, or disclosed to others without the written
authorisation of Condair Group AG, except to the extent required for installation or maintenance of recipient's
equipment.
Liability Notice
Condair Group AG does not accept any liability due to incorrect installation or operation of the equipment or due
to the use of parts/components/equipment that are not authorised by Condair Group AG.
Copyright Notice
© Condair Group AG, All rights reserved.
Technical modications reserved.

3Contents
Contents
1 Condair UDC
6
1.1 Functional description 6
1.2 Safety 6
1.3 Delivery 6
1.4 Mounting location 7
1.5 Installation 7
1.6 Product specications 8
1.7 Wiring diagram/Conguration 10
1.8 Operation of the UDC 11
2 Condair CDC, CDC-NA, CDC-ST and CDC-SL
18
2.1 Functional description 18
2.2 Safety 18
2.3 Delivery 18
2.4 Mounting location 19
2.5 Installation 19
2.6 Product specications 20
2.7 Wiring diagrams/Conguration 22
2.8 Connecting the CDC, CDC-NA, CDC-ST or CDC-SL to Condair units 24
3 Condair CRC and CRC-NA
37
3.1 Functional description 37
3.2 Safety 37
3.3 Delivery 37
3.4 Mounting location 38
3.5 Installation 38
3.6 Product specications 38
3.7 Wiring diagrams/Conguration 41
3.8 Connecting the CRC or CRC-NA to Condair units 42
3.9 Operation of the CRC-NA 54

4Contents
4 Condair DCC and DCC-NA
55
4.1 Functional description 55
4.2 Safety 55
4.3 Delivery 56
4.4 Mounting location 56
4.5 Installation 56
4.6 Product specications 57
4.7 Wiring diagrams/Conguration 59
4.8 Connecting the DCC and DCC-NA to Condair units 61
4.9 Operation of the DCC / DCC-NA 63
5 Condair RCC and RCC-NA
68
5.1 Functional description 68
5.2 Safety 68
5.3 Delivery 68
5.4 Mounting location 69
5.5 Installation 69
5.6 Product specications 70
5.7 Wiring diagrams/Conguration 72
5.8 Connecting the RCC and RCC-NA to Condair units 73
5.9 Operation of the RCC or RCC-NA 78
6 Condair CHD, CHD-S and CHD-NA
83
6.1 Functional description 83
6.2 Safety 83
6.3 Delivery 83
6.4 Mounting location 84
6.5 Installation 84
6.6 Product specications 85
6.7 Connecting the CHD, CHD-NA or CHD-S to Condair units 88
6.8 Operation of the CHD, CHD-S and CHD-NA 94
7 Condair CHR and CHR-NA
95
7.1 Functional description 95
7.2 Safety 95
7.3 Delivery 95
7.4 Mounting location 96
7.5 Installation 96
7.6 Product specications 97
7.7 Wiring diagrams 99
7.8 Connecting the CHR or CHR-NA to Condair units 100
7.9 Operation of the CHR 106

5Contents
8 Condair MHD
108
8.1 Functional description 108
8.2 Safety 108
8.3 Delivery 108
8.4 Mounting location 109
8.5 Installation in the duct 109
8.6 Product specications 110
8.7 Connecting the MHD to Condair units 112
9 Condair MHR
117
9.1 Functional description 117
9.2 Safety 117
9.3 Delivery 117
9.4 Mounting location 117
9.5 Installation 118
9.6 Product specications 118
9.7 Connecting the MHR to Condair units 120
10 Condair CDA and CDA-S
127
10.1 Functional description 127
10.2 Safety 127
10.3 Delivery 127
10.4 Mounting location 128
10.5 Installation 128
10.6 Product specications 129
10.7 Connecting the CDA or CDA-S to Condair units 131
11 Condair APS and APS-NA
137
11.1 Functional description 137
11.2 Safety 137
11.3 Delivery 137
11.4 Mounting location 138
11.5 Installation 138
11.6 Product specications 139
11.7 Connecting the APS or APS-NA to Condair units 141

6Condair UDC
1 Condair UDC
1.1 Functional description
The universal controller Condair UDC is a programmable controller and sensor for duct installation. It
has 2 control loops with 2 PI sequences each. The Condair UDC has an RS485 communication interface
which enables programming with a PC and the Easyset program. The Condair UDC uses the universal
X2 operating system.
Note: Ex factory the Condair UDC is congured as a humidity and temperature sensor.
1.2 Safety
Please observe all local regulations concerning electrical installations.
The installation work must be performed only by adequately qualied personnel (electrician or work-
man with equivalent training).
Warning - danger of electric shock! Before starting the installation work the unit to which the Condair
UDC will be connected must be disconnected from the mains and may be reconnected to mains only
after all installation work has been completed.
Warning! The electronic components inside the Condair UDC and the humidier are very susceptible
to electrostatic discharges. For the protection of these components, measures must be taken during all
installation work to prevent damage caused by electrostatic discharge (ESD–protection).
1.3 Delivery
The delivery includes:
– Universal duct controller Condair UDC
– Cable gland
– Fixing material
– Duct ange
– Installation manual

7Condair UDC
1.4 Mounting location
The Condair UDC is installed directly on the duct.
– Mounting in the extract air duct (recommended):
Mount the UDC in the extract air duct close to the air outlet of the room but downstream from a
extract air fan if one is present.
– Mounting in the supply air duct:
Mount the UDC in the supply air duct at least 3 meters downstream from the nearest fan and coil
and with a minimum distance of 5x the humidication distance to the steam distributor (see manual
of the humidier).
1.5 Installation
1. At the place of location drill a hole with a diameter of 16 mm (5/8") into the duct (see dimensional
drawing).
2. Stick the supplied self-adhesive gasket concentrically over the hole in the duct and attach the duct
ange to the ventilation duct using the self-tapping screws supplied.
3. Insert the probe of the universal controller through the duct ange into the duct and secure it with
the lock nut.
4. Loosen the screw on the housing cover and open the cover.
5. Lead connecting cable through the cable gland into the controller and connect wires to the terminals
according to the wiring diagram.
6. Close cover and x it with the screw (do not tighten screw too much).

8Condair UDC
1.6 Product specications
1.6.1 Technical data
Power Supply
Operating voltage 24 VAC ±10%, 50/60 Hz,
class 2, 2.0 A, 48 VA max.
24 VDC ±10%
Power consumption Max. 5 VA
Electrical connections Terminal connectors,
for wires 0.34…2.5 mm2 (AWG 24…12)
Clock backup 24 hours
Signal inputs
Analog inputs UI1, UI2
Input signal DC 0-10V or 0…20mA
Resolution 39 mV or 0.078 mA
Impedance Voltage: 98kΩ, Current: 240Ω
Temperature sensor AES-HT-Ax NTC
Range Int. NTC: 0…50 °C (32…122 °F)
Ext. NTC: -40…140 °C (-40…284 °F)
Resolution Int. NTC: 0…50 °C (32…122 °F)
Measuring accuracy
-20
(-4)
-40
(-40)
0
±0.5
(0.9)
±1.0
(±0.9)
∆T
°C
(°F)
°C
(°F)
0
(32)
20
(68)
40
(104)
60
(140)
80
(176)
100
(212)
120
(248)
Humidity sensor AES-HT-Ax Capacitive sensor
Range 0…100 % rH
Measuring accuracy
100
0
±1
±2
±3
±4
±5
%rF
%rh
%hr
%rF
%rh
%hr
20 30 40 50 60 70 80 90 100
Max. rH tolerance at 25 °C (77°F)
Hysteresis ± 1%
Repeatability ± 0.1%
Stability < 0.5% / year
Signal outputs
Analog Outputs AO1, AO2
Analog signal DC 0-10V or 0…20mA
Resolution 39 mV, 0.078 mA
Maximum load Voltage: ≥1kΩ, Current: ≤250Ω

9Condair UDC
Relay outputs
Interrupter type Micro-breaker
AC voltage 0…48 VAC, 2(1.2)A max.
Observe local regulations
DC voltage 0…30 VDC, 2A max.
Insulation strength
between relay contacts and system electronics 2000V AC according to 60 730-1
between adjacent contacts 1250V AC according to 60 730-1
Environment
Operation According to IEC 721-3-3
Climatic Conditions Class 3 K5
Temperature 0…50 °C (32…122 °F)
Humidity <95 %rH., not condensing
Transport and storage According to IEC 721-3-2 and IEC 721-3-1
Climatic Conditions Class 3 K3 and Class 1 K3
Temperature -25…70 °C (-13…158 °F)
Humidity <95 %rH., not condensing
Mechanical Conditions Class 2M2
Standards
CE compliant to: EMC Standard and EMEI Stan-
dard 73/23/EEC
EN 61 000-6-1/ EN 61 000-6-3
Product standards
Automatic electrical control devices for domes-
tic use and similar applications.
EN 60 730 -1
Special requirements for temperature-depen-
dent controls.
EN 60 730 - 2 - 9
Degree of protection IP30 according to 60 529
Pollution class II (EN 60 730-1)
Protection class III (IEC 60536)
Overvoltage category I (EN 60 730-1)
General
Housing material PC and ABS
Weight (including packaging) 380g (13.4oz)

10 Condair UDC
1.6.2 Dimensions
ø14 x 157
(ø0.55 x 6.2)
47 (1.9)
ø14 (0.6)
68 (2.7)
98 (3.9)
ø14 (0.6)
60 (2.4) 35 (1.4)
45 (1.8)
4.2 (0.2)
Dimensions in mm (inches)
Duct ange
1.7 Wiring diagram/Conguration
Data
AEC-PM2
JP3
JP2
JP1
JP4
JP1/JP2
3
2
1
VDC
3
2
1
mA
JP3
3
2
1
0...10 V
0...20 mA
2...10 V
4...20 mA
3
2
1
AES4
AEX2
JP4 = OPxx-VC
120Ω
1
1
V+
Power AODO RT/DI
OPxx-VC
GND GNDAO1NO DO1 NC AO2 OP1 OP2 OP3 OP4UI6
Signal type Signal range
Termination
Flashing interval status LED
Sec. Sec. Sec.Sec. Sec.Sec. Sec.
24 VAC/DC
GND
Temperature
Humidity