Condair 2583810 Bedienungsanleitung

Humidication and Evaporative Cooling
2585293-K EN 2202
Gateway Board for
BACnet and LonWorks
Supplemental Installation and Operation Manual
For use with RS, EL, DL, and
ME humidifiers with
Software version 5.9.x.x and 5.10.x.x

Thank you for choosing Condair
Installation date (MM/DD/YYYY):
Commissioning date (MM/DD/YYYY):
Site:
Model:
Serial number:
Contact
Condair Ltd.
2740 Fenton Road, Ottawa, Ontario K1T3T7
TEL: 1.866.667.8321, FAX: 613.822.7964
EMAIL: na.info@condair.com, WEBSITE: www.condair.com
Proprietary Notice
This document and the information disclosed herein are proprietary data of Condair Ltd. Neither this document, nor
the information contained herein shall be reproduced, used, or disclosed to others without the written authorization
of Condair Ltd., except to the extent required for installation or maintenance of recipient's equipment.
Liability Notice
Condair Ltd. does not accept any liability due to incorrect installation or operation of the equipment or due to the
use of parts/components/equipment that are not authorized by Condair Ltd.
Copyright Notice
© Condair Ltd., All rights reserved.
Technical modications reserved

3Contents
Contents
1 Introduction 4
1.1 Notes on this addendum manual 4
1.2 Functions overview 5
2 For your safety 6
3 Network integration via the optional LonWorks and BACnet Gateway boards 8
3.1 Notes for the planning engineer 8
3.1.1 Overview 8
3.1.2 Principle Network diagrams 9
3.1.2.1 Principle BACnet network 9
3.1.2.2 Principle LonWorks network 11
3.2 Installation work 12
3.2.1 Installing the BACnet/LonWorks gateway board on the Integrated Controller 12
3.2.2 Wiring 13
3.3 Conguration 14
3.3.1 Conguring the Condair Integrated Controller 14
3.3.1.1 Setup control settings 14
3.3.1.2 Monitoring of bus communication 15
3.3.1.3 BMS Timeout and Modbus settings 16
3.3.2 Gateway conguration 17
3.3.2.1 Requirements for gateway conguration 17
3.3.2.2 Congure the IP settings 18
3.3.2.3 Modifying the BACnet conguration 23
3.4 Communication tables 26
3.4.1 DL - BACnet (Integrated Controller software version 5.9.x.x) 26
3.4.2 DL - LonWorks (Integrated Controller software version 5.9.x.x) 29
3.4.3 ME - BACnet (Integrated Controller software version 5.9.x.x and 5.10.x.x) 32
3.4.4 ME- LonWorks (Integrated Controller software version 5.9.x.x and 5.10.x.x) 35
3.4.5 RS - BACnet (Integrated Controller software version 5.9.x.x) 38
3.4.6 RS - LonWorks (Integrated Controller software version 5.9.x.x) 42
3.5 Troubleshooting 46
3.5.1 Operating trouble list 46
3.5.2 LED functions 48
4 Appendix 51
4.1 Object abbreviations 51
5 Ordering form 52

4Introduction
1 Introduction
1.1 Notes on this addendum manual
Condair devices equipped with an Integrated Controller can either be connected via the corresponding
interface on the Integrated Controller (BACnet on-board) to a BACnet IP network or a BACnet MS/TP
network or via the optional LonWorks or BACnet gateway boards (ProtoCessor gateway) to a LonWorks,
BACnet IP or BACnet MS/TP network to a building management system.
This manual describes how to install and congure the optional LonWorks and BACnet gateway boards
(see chapter 3) to connect the corresponding Condair devices to a building management system.
This addendum manual is intended for use by engineers and properly trained technical personnel. Please
read this manual thoroughly before installing and conguring the BACnet or LonWorks based network.
If you have questions after reading this documentation, please contact your Condair representative.
They will be glad to assist you.
Symbols used in this manual
CAUTION!
The catchword "CAUTION" used in conjunction with the caution symbol in the circle designates notes
in this manual that, if neglected, may cause damage and/or malfunction of the unit or other mate-
rial assets.
WARNING!
The catchword "WARNING" used in conjunction with the general caution symbol designates safety
and danger notes in this manual that, if neglected, may cause injury to persons.
DANGER!
The catchword "DANGER" used in conjunction with the general caution symbol designates safety and
danger notes in this manual that, if neglected, may lead to severe injury or even death of persons.

5Introduction
Safekeeping
Please safeguard this addendum manual in a safe place, where it can be immediately accessed. If the
equipment changes hands, the documentation must be passed on to the new operator.
If the documentation gets mislaid, please contact your Condair representative for replacement.
Language versions
This addendum manual is available in various languages. Please contact your Condair representative
for information.
1.2 Functions overview
The following table gives you an overview of the supported protocols and functions.
Optional BACnet
Gateway board
Optional LonWorks
Gateway board
BACnet IP and BACnet MS/TP BTL certied yes no
BACnet IP yes no
BACnet MS/TP Master Mode yes no
BACnet MS/TP Slave Mode yes no
LonWorks certied no yes
Remote"RS draining" yes yes
BACnet Service COV (Change of Value) yes no
Please refer to the objects tables for detailed information.

6For your safety
2 For your safety
General
Every person working with the Condair Integrated Controller must have read and understood this ad-
dendum manual, and the installation manual and operation manual of the Condair Integrated Controller,
before carrying out any work.
Knowing and understanding the contents of the manuals is a basic requirement for protecting the person-
nel against any kind of danger, to prevent faulty operation, and to operate the unit safely and correctly.
All icons, signs and markings applied to the unit must be observed and kept in readable state.
Qualication of personnel
All work described in this addendum manual may only be carried out by specialists who are well
trained and adequately qualied and are authorised by the customer.
For safety and warranty reasons any action beyond the scope of this manual must be carried out only
by qualied personnel authorised by the manufacturer.
It is assumed that all persons working with the Condair Integrated Controller are familiar and comply
with the appropriate local regulations on work safety and the prevention of accidents.
Intended use
The optional LonWorks or BACnet gateway boards are intended exclusively for connecting the Condair
Integrated Controller to a LonWorks or BACnet based network. Any other type of application, without
the written consent of the manufacturer, is considered as not conforming with the intended purpose and
may lead to the Condair Integrated Controller becoming dangerous.
Operation of the equipment in the intended manner requires that all the information contained in this
addendum manual as well as in the installation manual and operation manual of the Condair
Integrated Controller are observed.
Danger that may arise from the Condair Integrated Controller
DANGER!
Risk of electric shock!
The electrical compartment where the Integrated Controller is located may have live mains
voltage connected for other uses of the device. Live parts may be exposed when the control
unit is open. Touching live parts may cause severe injury or danger to life.
Prevention: Before commencing any work on the control unit disconnect the mains supply voltage to
the humidier via the electrical isolator in the mains supply line, and secure electrical isolator in "Off"
position against inadvertent switching on.

7For your safety
Safety reporting
All persons working with the Condair Integrated Controller are obliged to report any alterations to the
system that may affect safety to the owner without delay and to secure such systems against ac-
cidental power-up.
Prohibited modications to the unit
No modications must be undertaken on the optional LonWorks or BACnet gateway boards and on
the Condair Integrated Controller without the express written consent of the manufacturer.
For the replacement of defective components use exclusively original accessories and spare parts
available from your Condair representative.

8Network integration via the optional LonWorks and BACnet Gateway boards
3 Network integration via the optional LonWorks and
BACnet Gateway boards
3.1 Notes for the planning engineer
3.1.1 Overview
The optional LonWorks or BACnet gateway boards allow the integration of the Condair Integrated Con-
troller into a BACnet IP, BACnet MS/TP or a LonWorks network. The optional LonWorks or BACnet
gateway boards feature a serial-interface gateway which converts the information from the host RTU
Modbus protocol to a specied secondary protocol.
Important: Please note that the gateway board is congured for the latest software version of the In-
tegrated Controller. To guarantee correct data communication it is therefore mandatory to update the
software of the Integrated Controller to the latest version before installing the gateway board. Please
contact your Condair distributor regarding a software update of the Integrated Controller.
The following protocol options are available and must be specied when ordering:
Part Number Protocols Part Description
2583810 BACnet IP BMS Set Master BACnet IP ME
2583813 BACnet MS/TP BMS Set Master BACnet MS/TP ME
2583808 LonWorks BMS Set Master LonWorks ME
2583809 BACnet IP BMS Set Master BACnet IP RS
2583812 BACnet MS/TP BMS Set Master BACnet MS/TP RS
2583807 LonWorks BMS Set Master LonWorks RS
2582291 BACnet IP BMS Set Master BACnet IP DL
2583811 BACnet MS/TP BMS Set Master BACnet MS/TP DL
2582290 LonWorks BMS Set Master LonWorks DL
2586239 BACnet IP BMS Set Master BACnet IP EL
2586240 BACnet MS/TP BMS Set Master BACnet MS/TP EL
2587508 LonWorks BMS Set Master LonWorks EL
Please refer to the BACnet object or Lonworks SNVT tables in chapter 3.4 for detailed information re-
garding the available read out and settings functions.

9Network integration via the optional LonWorks and BACnet Gateway boards
3.1.2 Principle Network diagrams
3.1.2.1 Principle BACnet network
The principle diagram below shows the connection of the Condair Integrated Controller to an Ethernet
network.
Principle BACnet IP network
Abb. 1: Principle BACnet IP network
Ethernet (BACnet IP)
CAT6A cable (or higher) with RJ45 termination
BACnet gateway board
(connected to integrated controller
inside control unit)

10 Network integration via the optional LonWorks and BACnet Gateway boards
Principle BACnet MS/TP network
Abb. 2: Principle BACnet MS/TP network
Ethernet (BACnet IP)
GND
+
–
BACnet MS/TP to BACnet IP
Router RS485 Network (BACnet MS/TP)
Shielded twisted-pair cable:
– 120 Ohm impedance
– Terminate shield at one end only
BACnet gateway board
(connected to integrated controller
inside control unit)
Dieses Handbuch passt für folgende Modelle
11
Inhaltsverzeichnis
Andere Condair Tor Handbücher
Beliebte Tor Handbücher anderer Marken

LST
LST M500RFE-AS Bedienungsanleitung

Kinnex
Kinnex Media Gateway Bedienungsanleitung

2N Telekomunikace
2N Telekomunikace 2N StarGate Bedienungsanleitung

Mitsubishi Heavy Industries
Mitsubishi Heavy Industries Superlink SC-WBGW256 Bedienungsanleitung

ZyXEL Communications
ZyXEL Communications ZYWALL2 ET 2WE Bedienungsanleitung

Telsey
Telsey CPVA 500 - SIP Bedienungsanleitung