COOPER FIRE CTPR3000 Bedienungsanleitung

TOUCHSCREEN REPEATER PANEL
INSTALLATION MANUAL
CTPR3000
Cooper Fire Systems
Security House,
Vantage Point Business Village
Mitcheldean
Gloucester
GL17 0SZ
United Kingdom
TEL: +44(0)1594 541900
FAX: +44(0)1594 541910

Introduction to the Manual
This manual provides information on the installation, operation and
maintenance of the Panel System.
NOTICE
The operating system of the panel may be revised as a result of
enhancements to the system software or hardware. Revisions to this
manual will be issued and supplied on request and should be logged
in the table supplied on the contents page.
Introduction

Contents Page
1.0 System Design & Installation
Introduction 7
Technical Specification 8
Cable and Wiring 10
Installation 11
Fixing details 12
External Connections 13
Networking 14
2.0 Commissioning the Panel
Commissioning 16
3.0 Panel Controls and Indicators
Touch Screen Display 20
Panel Operation 21
Public Access Level 1 22
Evacuate (Access Level 2) 23
Silence Alarms 24
Mute Buzzer 25
Pre-Alarms 26
Panel Controls and Indicators 19
Faults 27
Enable / Disable 27
Print (Function not availible) 28
Lamp Test 29
View Events 30
Send Log to PC 31
Erase Log 32
System Details 33
Load Logo from PC 34
Repeater Mode 35
Printer Settings 36
Change Panel Number 38
Number of Panels in Network 39
Change Date/Time 40
Change Panel Text 41
Change Passcode 42
Relay Control 43
Programable Input 44
Network 45
Language 46
Network Protocol 47
Power Supply 48
Password Protection 49
4.0 Appendix
System Wiring 51
Contents
Document Drg Ref PR203-68-532-01

Contents

Contents
Contents Page

System Installation and Design
Section 1
6

Introduction
Analogue Touchscreen Repeater Panel CTPR3000
The CTPR3000 fire detection repeater panel provides sophisticated ‘touch
screen’ functionality yet achieves a simple end-user interface operation
within a compact panel design. The CTPR3000 is designed to work with
Cooper Analogue Addressable Fire alarm Control Panels as a network
repeater. It is fully compliant with the statutory requirement of EN60950
(LVD) and EN50130 (EMC) and includes an integral monitor PSU compliant
with the latest requirements of EN54 pt4 together with a wide range of user
controllable functions; make the panel suitable for a wide range of projects.
The Cooper repeater panel is easy to install and commission all text is
transmitted via the network and is automatically updated and as the
following features
• Plug and play. All information is downloading through the network
• Touch Screen Display
• Integrated Network capability allows networking with Cooper latest range of analogue
addressable Fire Alarm Control Panels
• Multi language capability
• 2 programmable Auxiliary relays
• 24 Volts 500ma output
• Programmable input is available
• External Printer outputs
• Up to 1000 event log
• Optional local and external PSU
• PSU approved to EN54 pt4
• Utilises 2 core cables and up to 125 repeaters can be connected to the network
• Programmable as an active or Passive Repeater can be power locally or external 24
volts power supply
7

Technical Specification
Power Specification
Mains Fuse : 1.6A Slow Blow
Nominal Voltage : 230 Vac + 10%, -15%
Nominal Current : 75mA
The Panel is protected by an internal thermal device, this requires no maintenance
Batteries
Number of Batteries : 2
Manufacturer: :YSP12-7
Capacity : 7 Ah
Battery Fuse : 4A Quick Blow (F4)
Maximum battery current; : 3.5 Amps
Standby current (mA) : 100 (1 loop )
Inputs
Programmable Input (TB10)
Link input to activate
Outputs
Programable Auxiliary Relays
The programable auxiliary relays provide fused volt free change over contacts. These
contacts are not monitored.
Max Load : 24 Volts 1 Amp
Fuse (PTC4) : 1.1 Amps polyswitch
Programable Fault Relays
The programable fault relays provide fused volt free change over contacts. These
contacts are not monitored.
Max Load : 24 Volts 1 Amp
Fuse (PTC3) : 1.1 Amps polyswitch
24V Input Supply
Nominal Voltage : 24 Volts ±10%
Fuse (PTC1) : 1.1 Amps polyswitch
Maximum current : 800 mA
Any power taken from the alarm system will effect the standby duration
24V Output Supply
Nominal Voltage : 24 Volts ±10%
Fuse (PTC2) : 1.1 Amps polyswitch
Maximum current : 500 mA
(TB8)
(TB7)
(TB1)
(TB2)
8

Mechanical Specification
Weight including batteries : 9 Kg
Weight excluding batteries : 4 Kg
Dimensions (Standard batteries) : 395mm(L) x 270mm(H) x 115mm(D)
Type of Material (backbox) : Mild Steel (Power Coated)
Type of Material (Facia) : PC/ABS
Flammability Rating : UL 94 V0
Total Number of knockouts : 11
Diameter of Knock out : 20mm
TERMINAL BLOCKS : DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE SCREWS ON
THE TERMINAL BLOCK
Technical Specification
9

Cable & Wiring
Only the cable types listed below are allowable for loop connections.
DRAKA Cables (Part Number 910234)
Technical Specification
When choosing your preferred cable type, you must take note of the following cable and
wiring requirements.
1. The cable must be 2 core screened with an over sheath.
2. Maximum loop length with any of the above cables is 1KM
3. Multicore cable should not be used for detector wiring.
4. The screen or drain wire of the network cable should not be considered as a
safety earth.
5. Screen continuity must be maintained throughout the entire network circuit
including at each junction point.
6. Where the network cable passes between buildings, screen continuity should not
be maintained from building to building. A booster device must however be used
irrespective of cable length and should be fitted at a suitable point in the link
between buildings. The cable screen should be connected to the earth of one
panel in each building.
10
Cabling Application Applicable Standards
Circuit integrity Structured Wiring
Alarm/Lighting Cable Part Number 910234
Patent Protected Design
ISO/IEC 11801:95
EN 50173:95
Fire Propagation Test : UL 1581 VW1;
IEC60332.3;
Cct Integrity tests: IEC 60331; BS5839: 2002
Cable construction
Conductor
Insulator Material
Number of Twisted Pairs
Glass Tape
Screen Material
Braid
Sheath Material
Bare Cu
Wire
PE/Sil Rbr
1
Mica
Ali/Mylar
TCWB
OHLS
Outside Diameter of Conductor
Outside Diameter of Insulation
Outside Diameter of Sheath
Weight OHLS
Sheath Colour (OEM Specified)
Sheath Printing (up to 24
characters)
0.65 mm
1.70 mm
5.3 mm
15.8 kg/km
Various
Batch No. &
Metre marking
Cable Properties Electrical Characteristics @ 20 ºC
Min. Installation Bend Radius
Min. Installed Bending Radius
Max. Installation Tension
Max. Installed Tension
InstTemp. Range Installed
Operating Temp. Range
8 x Dia
4 x Dia
50N
Zero
0 to 0ºC
-20 to 60ºC
Return Loss Rl
Characteristic impedance @
10MHz
DC Conductor Loop Resistance
Max. Resistance unbalance
Nominal Velocity of Propagation
Insulation Resistance (500V)
300/500v rated
>IEC dB
100±5Ù
30 Ù/100m
?2%
57%
?5000
MÙ.km
Fire tests BS 5839: 2002 & IEC60331
Continued Data Operation @ 950°
Smoke test
Approvals
>3 Hours
passed
passed
Inhaltsverzeichnis
Beliebte Touch-Screen Handbücher anderer Marken

Elecro Engineering
Elecro Engineering Poolsmart Plus Montageanleitung

Johnson Controls
Johnson Controls IQ4 HUB Bedienungsanleitung

Elo TouchSystems
Elo TouchSystems ET2270L Bedienungsanleitung

Elo TouchSystems
Elo TouchSystems ET1002L Bedienungsanleitung

Elo TouchSystems
Elo TouchSystems 3201L Bedienungsanleitung

Duratec
Duratec S15 Bedienungsanleitung