a: constant (default value is 1)
b: constant (default value is 0)
So, if there is no user setting for a and b ==> Y = X
The Y value will be compared with Lo and Hi threshold.
Status bytes of sensor Node
Just exchange the sensor module but node has not been reset ==>
please take out the battery for 20s then install it again to reset node to
recognize the new sensor module
Error, sensor port M12F shorted to GND
Error, sensor port M12F shorted to Vcc
Error, sensor port M12F shorted each other
Just exchange the sensor module but node has not been reset ==>
please take out the battery for 20s then install it again to reset node to
recognize the new sensor module
Error, sensor port M12F shorted to GND
Error, sensor port M12F shorted to Vcc
Error, sensor port M12F shorted each other
Logic status of parameters
Hi-Byte is Logic status of parameter 1
If parameter 1's value > high threshold 1 => Hi-Byte of Logic status = 1
If parameter 1's value < low threshold 1 => Hi-Byte of Logic status = 0
If parameter 1 is digital => Hi-Byte of Logic status = parameter 1's value
Timer up 1 = (Total time when Hi-Byte of Logic status = 1)
Timer down 1 = (Total time when Hi-Byte of Logic status = 0)
RisingEdge counter 1 = (Counter value when Hi-Byte of Logic status changes from 0 to 1)
FallingEdge counter 1 = (Counter value when Hi-Byte of Logic status changes from 1 to 0)
Lo-Byte is Logic status of parameter 2
If parameter 2's value > high threshold 2 => Lo-Byte of Logic status = 1
If parameter 2's value < low threshold 2 => Lo-Byte of Logic status = 0
If parameter 2 is digital => Lo-Byte of Logic status = parameter 2's value
Timer up 2 = (Total time when Lo-Byte of Logic status = 1)
Timer down 2 = (Total time when Lo-Byte of Logic status = 0)
RisingEdge counter 2 = (Counter value when Lo-Byte of Logic status changes from 0 to 1)
FallingEdge counter 2 = (Counter value when Lo-Byte of Logic status changes from 1 to 0)
Ambient Temperature Sensor Module (ATH)
Feature of measuring humidity in environment:
Humidity measuring range & accuracy: 0 .. 100 %RH, +/- 2.0%
Resolution ±0.1%
Long-term Drift ±0.25%RH/year
Feature measuring ambient temperature:
Temperature Range -40oC to +125oC
Accuracy ±0.4oC
Resolution ±0.1oC