•Press the Tick button, the first ‘#’ changes to ‘0’. Press the Up or Down buttons to adjust it to the correct value.
•Press the Right button when the first digit is correctly entered. The digit previously entered now shows as ‘#’ for security.
•Repeat this process for the other digits of the PIN number. Press the Left button to move back to adjust one of the previous
digits.
•When the Tick button is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, the
PIN must be re-entered.
•If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed.
ACCESSING THE RUNNING CONFIGURATION EDITOR
•The Running Configuration Editor is accessible without stopping the generator. All protections remain active whilst the ‘Running
Configuration Editor is accessed.
•Press and hold the Tick button to enter the Running Configuration Editor.
EDITING A PARAMETER
NOTE: If the editor is left inactive for the duration of the Page Timer, it is automatically exited to ensure security.
•Enter either editor as described above.
•Press the Up or Down buttons to select the section to view/change. The current selected section highlights in green.
•Press the Left or Right buttons to select the Subsection/Parameter to be edited. The current selected item highlights in
green.
•To edit the parameter, press the Tick button to enter the edit mode. The parameter is no longer highlighted green to indicate
editing.
•Press the Up or Down buttons to change the parameter to the required value.
•Press the Tick button to save the value. The parameter highlights green to indicate that it has been saved.
•To exit the editor and save the changes, press and hold the Tick button.
SELECTING THE DSE8910 OR DSE8920 SOFTWARE APPLICATION
•Ensure the generator is at rest and the module by pressing the Stop/Reset Mode button.
•Enter the Running Configuration Editor as described above.
•Press the Up or Down buttons to navigate to the MODEL TYPE section. The section highlights in green when selected.
•Press the Right button to select the MODEL SELECTION parameter. The parameter highlights in green when selected.
•To edit the parameter, press the Tick button to enter the edit mode. The parameter is no longer highlighted green to indicate
editing.
•Press the Up or Down buttons to change between DSE8910 and DSE8920, by default DSE8920 is selected.
•Press the Tick button to change the software application, a confirmation box appears.
•Press the Left or Right buttons to select YES to confirm software application change. When prompted, remove the power
supply to the module and then reapply the power supply. The module powers up in the newly selected software application.