04P 06P Attrib. Register content Description
#2 #2 O R/W CH1 Input mode setting Input mode: Default = H’0000. Take CH1 for example:
Mode 0 (H’0000): Pt100: -180°C ~ 800°C
Mode 1 (H’0001): Ni100: -80°C ~ 170°C
Mode 2 (H’0002): Pt1000: -180°C ~ 800°C
Mode 3 (H’0003): Ni1000: -80°C ~ 170°C
Mode 4 (H’0004): 0~300Ω
Mode 5 (H’0005): 0~3000Ω
Mode 6 (H’0006): JPt100 (-180°C ~ 500°C)
Mode 7 (H’0007): Cu50 (-50°C ~ 150°C)
Mode 8 (H’0008): Cu100 (-50°C ~ 150°C)
Mode 9 (H’0009): LG-Ni1000 (-50°C ~ 180°C)
Mode -1 (H’FFFF): Channel 1 unavailable
Note: 04PT-E2 do NOT support mode 6-9.
#3 #3 O R/W CH2 Input mode setting
#4 #4 O R/W CH3 Input mode setting
#5 #5 O R/W CH4 Input mode setting
#6 O R/W CH5 Input mode setting
#7 O R/W CH6 Input mode setting
#7
O R/W Temperature unit setting
Select the temperature unit (Celsius °C / Fahrenheit °F).
Default = H’0(°C)
#8 #8 O R/W CH1 sampling range
Set sampling range:
Range = K1 ~ K100
Default = K10
#9 #9 O R/W CH2 sampling range
#10 #10 O R/W CH3 sampling range
#11 #11 O R/W CH4 sampling range
#12 O R/W CH5 sampling range
#13 O R/W CH6 sampling range
#12 #14 X R Average temperature measured at CH1
Average temperature measured.
Setting Temperature Unit :
●DVP04PT-E2:CR#7
●DVP06PT-E2:CR#27
#13 #15 X R Average temperature measured at CH2
#14 #16 X R Average temperature measured at CH3
#15 #17 X R Average temperature measured at CH4
#18 X R Average temperature measured at CH5
#19 X R Average temperature measured at CH6
#20 #20 X R Present temperature measured at CH1
Present temperature measured.
Setting Temperature Unit :
●DVP04PT-E2:CR#7
●DVP06PT-E2:CR#27
#21 #21 X R Present temperature measured at CH2
#22 #22 X R Present temperature measured at CH3
#23 #23 X R Present temperature measured at CH4
#24 X R Present temperature measured at CH5
#25 X R Present temperature measured at CH6
#26 O R/W
Mode 4 (H’0004): 0~300Ω. Temperature
display decimal digit changes
In mode 4 (0~300Ω), temperature display decimal
changes (0: 1 digit after the decimal place/ 1: 2 digits
after the decimal place). Default= H0
#27 O R/W Temperature unit setting
Select the temperature unit (Celsius °C / Fahrenheit °F).
Default = H’0(°C)
#28 #28 O R/W Adjusted offset value of CH1
Adjusted offset value measured, range K-1000 ~ K1000.
Default = K0
Measured Value = Original Value – Adjusted offset value
Unit Setup:
●DVP04PT-E2:CR#7
●DVP06PT-E2:CR#27
#29 #29 O R/W Adjusted offset value of CH2
#30 #30 O R/W Adjusted offset value of CH3
#31 #31 O R/W Adjusted offset value of CH4
#32 O R/W Adjusted offset value of CH5
#33 O R/W Adjusted offset value of CH6
#40 #40 O R/W Function: Set value changing prohibited Prohibit set value changing, b0~b5 corresponds to CH1 ~
CH6. Default =H’0000
#41 #41 X R/W Function: Save all the set values Save all the set values. Default =H’0000
#43 #43 X R Error status Register for storing all error status. See the table of error
status for more information.