5PD00E1xKNXFI00020100_UM_EN_1.0
the processing of information related to the intensity of the ac-
tivity of the occupants within the monitored areas (to generate a
‘heat map’ of the building areas).
read the following notes for device installation and sensitivity set-
tings parameters.
and temperature of moving objects and people; the lower this
be.
3. Installation instructions
The device can be used for permanent indoor installations in dry
locations and is intended for ceiling mounting.
WARNING
• Device must be installed keeping a minimum distance of 4
mm between electrical power line (not SELV, for example:
mains) and input cables or red / black bus cable.
• The device must be mounted and commissioned by an au-
thorized installer.
• The applicable safety and accident prevention regulations
must be observed.
• The device must not be opened. Any faulty devices should
be returned to manufacturer.
• For planning and construction of electric installations, the
relevant guidelines, regulations and standards of the re-
spective country are to be considered.
• KNX bus allows you to remotely send commands to the
system actuators. Always make sure that the execution of
remote commands do not lead to hazardous situations, and
that the user always has a warning about which commands
can be activated remotely.
Illuminance measurement
Ambient illuminance measurement is performed indirectly, and
calibration is therefore necessary.
The sensor is installed on the ceiling and the detected illumi-
the SW ETS it is possible to set correction parameters for the de-
vice on the basis of an on-site measurement using a lux-meter.
-
sor.
Presence and movement detection
care the following notes for correct installation of the device and
setting of the sensitivity parameters.
• -
perature and the temperature of moving objects and people;
sensor will be.
• For a correct coverage of the sensor surveillance area, avoid
that walls (including glass) or furniture are an obstacle; if this
is not possible, increase the number of sensors in the area
for complete coverage.
• Always mount the sensor on a stable site, not subject to vi-
brations or oscillations that can simulate movement.
•
area can cause false detections, avoid this type of interfer-
ence as much as possible.
• Avoid placing heat-producing appliances such as fan coils,
printers, lamps, etc. in the coverage area. or objects that
move due to wind or air currents.
For more information visit: www.eelectron.com
4. Conguration and commissioning
the device parameters the corresponding application program or
the whole eelectron® product database must be loaded in the
ETS® program.
The commissioning of the device requires the following steps:
• connect the bus KNX (1)
• turn on the bus power supply
• press the programming button (2); the red programming
LED (visible through the device lens) turns ON
• download into the device the physical address and the con-
5. General parameters
KNX PARAMETER SETTINGS
Delay to send telegrams on
power up [s] 5 ÷ 15
Through this parameter is possible to set the delay of transmission of
telegrams after a power on by selecting the time by which the device
is allowed to send telegrams.
In large systems after a power failure or shutdown this delay avoids
a transmission block.
-
gestion during the initialization phase.
The input detection and the values of objects are updated at the end of
the transmission delay time
At the end of ETS programming the device behaves like after a power
on.
Sound sensor disabled / enabled
Enabling the function shows the dedicated page
21