Parameter description
8
08:05 Minimum
temperature heat
supplier
Setting range: OFF (----)
5…80 °C
Factory setting: OFF
Function:
Irrespective of switching differentials, pump turns on only after
the sensor of heat supplier F3 has exceeded the set value.
08:06 Maximum
temperature heat
supplier
Setting range: OFF (----), 30 … 110 °C
Factory setting: 90 °C
Function:
Irrespective of switching differentials, the pump performs a
forced switch-on after the sensor of heat supplier F3 has
exceeded the set value.
08:07 Final switch-off
temperature heat
supplier
Setting range: OFF (----), 70 … 210 °C
Factory setting: OFF
Function:
Irrespective of switching differentials, the pump performs a
forced switch-off after the sensor of heat supplier F3 has
exceeded the set value.
08:08 Maximum
temperature heat
storage tank
Setting range: OFF (----), 50 … 110 °C
Factory setting: 75 °C
Function:
Irrespective of switching differentials, the pump performs a
forced switch-off after the sensor of heat storage tank F1 has
exceeded the set value. This switch-off takes priority over
functions 08:07 and 08:06.
08:09 Burner block
Heat generator
Setting range: 0 ... 2 X2
Factory setting: 1
Function: 0 = OFF
1 = Burner block when pump is active
2 = Burner block only for DHW when pump
is active
08:10 Inhibition heat
generator
Setting range: OFF (----) ... 24h X2
Factory setting: OFF
Function:
After burner block is active, the heat generator is also blocked for
the duration of the set time.
08:11 Activation of heat
balance
Setting range: OFF (----) X3
1 = Heat balancing via sensor on F2
Factory setting: OFF
Function:
The settings of parameters 08:12 to 08:14 are only active if the
heat balance function has been switched on via this parameter.