STANDARD IN-WALL INSTALLATION METHOD - COMPONANT TESTING
If your in-wall installation is correct, but your flush valve is still not functioning correctly,
carrying out the following tests will determine exactly which component is causing the issue.
All components can be replaced easily and quickly.
NB: When testing –note confirmation times of product and wait 60 seconds between tests.
Rapid repeated testing will cause product to enter Stadium Mode, resulting in intermittent
flushing.
Connection Test - this will confirm if controller is working correctly. It will confirm that there
is power and that the connections are correct - Unplug sensor cable and rub thumb over the
4 metal pins. The red light on the controller will start to flash. Stop rubbing the pins when the
red light stops flashing (up to 20 seconds). The solenoid will be activated, you should hear it
clicking, and the urinal will flush.
Outcome of Connection Testing:
•IF NO LIGHTS ON CONTROLLER –CHECK POWER SUPPLY,REPLACE BATTERIES,CHECK CONNECTIONS
ARE CORRECT AND FULLY TIGHTENED (SEE DIAGRAM ON PAGE 1). REPEAT TEST.IF STILL NO LIGHTS,
YOU MAY NEED TO REPLACE THE CONTROLLER;
•IF CONTROLLER LIGHTS UP BUT THE UNIT DOES NOT FUNCTION CORRECTLY -
oWATER CONSTANTLY RUNNING ON CAN MEAN NOT ENOUGH POWER TO SOLENOID;CHECK
POWER SUPPLY,REPLACE BATTERIES,CHECK ALL CONNECTIONS ARE CORRECT AND FULLY
TIGHTENED (SEE DIAGRAM ON PAGE 1);
oOR THAT DEBRIS FROM WATER CONTAMINATION IS PREVENTING THE SOLENOID FROM
CLOSING.CLEAN SOLENOID,FLUSH PIPEWORK THOROUGHLY AND CHECK WATER PRESSURE
DOES NOT/HAS NOT EXCEEDED 500KPA THEN RE-TEST.IF ISSUE PERSISTS,YOU MAY NEED
TO REPLACE SOLENOID*;
•IF CONTROLLER ACTIVATES AND URINAL FLUSHES CORRECTLY –RECONNECT THE SENSOR CABLE TO
REST OF UNIT,WAIT FOR 60 SECONDS BEFORE CARRYING SENSOR TEST (SEE OVER PAGE);