ETI SOU-2 Bedienungsanleitung

SOU-2
E
N
Twilight switch with digital time
switch clock
H
U
C
R
O
S
L
O
R
U
P
L
E
N

- 2 -
3
4
5
6
8
9
10
11
12
14
16
20
22
23
24
25
Contents
Alert ................................................................................................................
Characteristics ...............................................................................................
Technical parameters ....................................................................................
Device description .........................................................................................
Symbol, Connection, Light sensor ...............................................................
Mode precedence, Language settings .........................................................
Menu overview ..............................................................................................
Control description .......................................................................................
Light functions setting .................................................................................
Time and date setting ...................................................................................
Time program ................................................................................................
Setting the switching modes ........................................................................
Setting options ..............................................................................................
Reset ...............................................................................................................
An example of programming .......................................................................
Replacing the battery ...................................................................................

- 3 -
E
N
Warning
Device is constructed for connection in 1-phase
main alternating current voltage 230V and
must be installed according to norms valid in
the state of application. Connection according
to the details in this direction. Installation, connection,
setting and servicing should be installed by qualied
electrician sta only, who has learnt these instruction
and functions of the device. This device contains
protection against overvoltage peaks and disturbancies
in supply. For correct function of the protection of this
device there must be suitable protections of higher
degree (A,B,C) installed in front of them. According to
standards elimination of disturbancies must be ensured.
Before installation the main switch must be in position
“OFF” and the device should be de-energized. Don´t
install the device to sources of excessive electro-magnetic
interference. By correct installation ensure ideal air
circulation so in case of permanent operation and higher
ambient temperature the maximal operating temperature
of the device is not exceeded. For installation and setting
use screw-driver cca 2 mm. The device is fully-electronic
- installation should be carried out according to this fact.
Non-problematic function depends also on the way of
transportation, storing and handling. In case of any signs
of destruction, deformation, non-function or missing
part, don´t install and claim at your seller it is possible to
dismount the device after its lifetime, recycle, or store in
protective dump.

- 4-
Characteristics
SOU-2 features a sundown switch and digital time switch clock with
weekly and annual program. Thanks to this combination, you can
control lighting based on the ambient light level while changing in real
time the lighting intensity toggle range and„lock“ the output when the
light doesn‘t need to be on. This lets you achieve the required eect
(where all night lighting is not necessary - advertisement, parking areas,
walkways) and save on both energy and lamps.
- used to control lighting based on ambient light intensity, on real time
and the on the time control switch
- the advantage of real time is blocking the sundown switch function
when illuminating seems inecient (night time, weekends, etc.)
- adjustable light intensity level 1-50,000 lux
- when no one‘s around, the random switching function simulates the
presence of persons
- external sensor with IP56 rating for mounting on the wall / in a panel
(cover and sensor holder are a part of the supply)
- Switching modes:
- Auto – automatic switching mode:
- Programme
– switches according to program (light functions or
time program).
- Random
– switches randomly in a 10–120 minute interval.
- Holiday
– holiday mode – option of setting up a period for
which the timer will be blocked, i.e. will not switch based on the
set programmes.
- Manual
– manual mode – option of controlling the individual
output relays manually
- Options for automatic switching program:
- lights - switching according to set light intensity range
- time program - switches according to set time program
- 100 memory locations for time programs (common for both
channels).
- Each memory position can switch on/o the relay or set the lighting
intensity toggle range according to lux value.
- Programming can be performed under voltage and in backup mode.
- The relay outputs do not work in backup mode (battery-powered)
- Choice of menu display - CZ / SK / EN / RO / PL / HU / RU (factory
setting EN).
- Choice of automatic daylight savings time transition according to
time zone.
- Backlit LCD display.
- Easy and quick setting with the help of 4 control buttons.
- Pluggable transparent cover on front panel.
- The time switch clock has a battery backup, which retains data in
case of a power outage (reserve backup time - up to 3 years).
- Power supply: 230V
- 2-module, DIN rail mounted

- 5 -
E
N
Technical parameters
Supply terminals:
Supply voltage tolerance:
Consumption:
Supply voltage:
Real time back-up:
Backup battery type:
Summer/winter time:
Output
Number of contacts:
Rated current:
Switched capacity:
Switched voltage:
Mechanical life:
Electrical life (AC1):
Time circuit
Real time back-up when de-ener-
gized:
Accuracy:
Minimum interval:
Program data stored for:
Program circuit
Illumination range:
Sensor failure indication:
Number of program places:
A
1 - A2
AC 230V / 50 - 60Hz
max. 4 VA
-15 %; +10 %
yes
CR 2032 (3V)
automatic
1x changeover (AgSnO2)
8 A / AC1
2000 VA / AC1, 240 W / DC
250 V AC1 / 24 V DC
> 1x10
7
> 1x10
5
up to 3 years
max. ±1s/ day at 23°C
1 min.
min. 10 years
1-50000 Lux
displayed on LCD*
100
daily , weakly, yearly
LCD display, with back light
-10.. +55 °C
-30.. +70 °C
4 kV (supply - output)
any
DIN rail EN 60715
IP 40 z from front panel / IP 20
clips
III.
2
max.1x 2.5, max.2x1.5/ with sleeve
max. 1x2.5
90 x 35.6 x 64 mm
separate page in the catalog
127 g
20 g
EN 61812-1, EN 61010-1, EN 60255-6;
EN 60730-1;EN 60730-2-7
Program period:
Data readout:
Other information
Operating temperature
Storage temperature:
Electrical strength:
Operating position:
Mounting:
Protection degree:
Overvoltage cathegory:
Pollution degree:
Max. cable size (mm2):
Dimensions:
Dimension of sensor:
Weight:
Weight sensor:
Standards:
* ERROR - sensor short circuit

- 6 -
SOU-2
15 16 18
A1 A2 T1 T1
PRG +
MAN
_
MAN2
ESC
OK
RESET
Auto
Supply voltage terminal (A1)(A2)
Display with back-light
Place for seal
Control buttons
Output (15-16-18)
Description
Plug-in module for replacing
backup battery
Terminals -sensor

- 7 -
SOU-2
ManProgAuto + t
E
N
Indicates the day in the week
Indication (1st channel)
Data display / settings menu/measured
light intensity display
Control button PRG / +
Control button MAN1 / -
Control button OK
Switches display date/
measured light intensity
Control button MAN2 / ESC
Reset
CONTROL OF A DISPLAY WITH BACKLIGHT
Power on: Display is illuminated with a backlight for 10 seconds from the last button press. The display continuously
shows the settings – date, time, day of the week, contact state and programme. Permanent on / o is activated by
simultaneous presses of the MAN, ESC, OK buttons. After activating the permanent on/o, the display will ash briey.
Backup mode: After 2 minutes, the display switches to the sleep mode, i.e. shows no information. The display can be
activated by pressing any button.
Time display
Operating modes indication
12/24 hours format /
AM <− ; PM −>
Indication of the switch
program

- 8 -
15 16 18
A1 A2 T1 T1
1 5
16
A2
A1
T1
T1
18 Un
ConnectionSymbol
Light sensor
Sensor 1
External sensor adjusted for wall/panel
mounting
Sensor tolerance: +/- 33%
Sensor resistance upon: Value
<1 Lux >3MΩ
1 Lux 3MΩ
100 Lux 1150Ω
50 000 Lux 51Ω

- 9 -
ProgAuto
PRG OK
+_OK
+_
ESC
Prog
Prog
Prog
Prog
Prog
Prog
Prog
Prog
Prog Prog
OK
Light options language
E
N
Mode precendence
mode precedence
display output mode
ON / OFF
manual control
ON / OFF holiday mode
ON / OFF time program Prog
light light
mode with the highest
priority
Language settings
Light and Time Program can work at the same time on a single channel.
Language selection
language
options
-
long press
(>1s)
- short press (<1s)

- 10 -
Auto Prog Prog Prog
Menu overview
light toggle range
setting
hysterezis setting
delayed on/o
setting
switching logic
setting
setting the display of
the time format
setting the display of
the date format
setting the display of
the week day
setting the switch
from the summer to
the winter time
setting the date
setting the current
time add a program
edit the program
delete a program
light functions setting setting and adjusting
the time program
intensity
hysteresis
delay
logic of sw
time
date
su-wi
week day
date form
time form
add
edit
delete
setting the time
and date
light time/date time prog
Inhaltsverzeichnis
Sprachen:
Andere ETI Schalten Handbücher

ETI
ETI HRH-5 Bedienungsanleitung

ETI
ETI SIT-6E Bedienungsanleitung

ETI
ETI D01 Bedienungsanleitung

ETI
ETI MLBS S Bedienungsanleitung

ETI
ETI EPF-43 Bedienungsanleitung

ETI
ETI CLBS-EH125/01G Bedienungsanleitung

ETI
ETI BU-DUSK-1 Bedienungsanleitung

ETI
ETI HVL EK 000 Bedienungsanleitung

ETI
ETI LBS 160 A CO Bedienungsanleitung

ETI
ETI CRM-4 Bedienungsanleitung