Evikon PluraSens E2408DF Bedienungsanleitung

PluraSens®
Differential pressure transmitter-regulator
E2408DF
User Manual

E2408DF Rev 27.05.2021
Table of contents
Specifications 3
Product description 4
Safety requirements 4
Operating conditions 4
Installation and connections 5
Delivery set 9
Order code for E2408DF options 9
Configuring 9
Return to default settings 10
Emergency mode. 10
Modbus RTU Communication 11
RS485 Communication parameters 13
Warranty 14
Manufacturer contacts 14
2

E2408DF Rev 27.05.2021
Specifications
Sensing method
Thermal microflow
Detection range options
E2408DF-50 -50...+50 Pa
E2408DF-500 -500...+500 Pa
Resolution
0,025% of the range
Gas flow through sensor
< 0,2 ml / minute / Pa
Zero point accuracy
± 0,2 Pa, stability < 0,1 Pa / year
Span accuracy
±1,5% of reading at +23°C, 1000 hPa
Temperature effect
< 0,5% of reading per 10°C
Atmospheric pressure effect
< 0,1 % of reading per hPa
Analog outputs
2 × 4-20 mA or 0-10 V, user settable
Digital interface
RS485, Modbus RTU protocol
Load resistance
RL < (Us - 3 V) / 22 mA for 4-20 mA
RL > 100 kOhm for 0-10 V mode:
Operating conditions
-20...+70 °C, <99 %RH, without
Aggressive gases or oil, residential or business spaces
Power supply
11...30 VDC
90...265 VAC
With integrated mains supply module
Power consumption
< 2 VA
Electromagnetic compatibility
According to 2014/30/EU:
EN 61000-6-3:2020, EN 61326-1:2013(EMC, emissions)
EN 61000-6-1:2019, EN 61000-6-2:2019(EMC, Immunity)
Enclosure
Light beige ABS 82×85×55 mm, IP65
Relays
2 × SPST, max 5 A, 30 VDC / 250 VAC
3

E2408DF Rev 27.05.2021
Product description
Differential pressure transmitter-regulator E2408DF is a member of the new PluraSens®
family of multifunctional measurement instruments. The transmitter is intended for
measurement of pressure of air and non-aggressive gases with superb accuracy and no
offset drift.
The differential pressure is measured by a thermal sensor element using flow-through
technology. Compared with membrane based sensors, the method provides an extended
dynamic range, better long-term stability and improved repeatability, especially near zero.
E2408 features two independent analog outputs OUT1 and OUT2 user-selectable to 4-20
mA or 0-10 V. RS485 Modbus RTU digital communication interface allows easy instrument
configuration and integration into various automation systems. Two relays RE1 and RE2
with closing contacts can be used to switch various actuators.
Safety requirements
Always adhere to the safety provisions applicable in the country of use.
Do not perform any maintenance operation with the power on. Do not let water or foreign
objects inside the device.
Operating conditions
The device should be used in explosion-safe (non ATEX -rated) indoor areas, without
aggressive gases in the atmosphere.
4

E2408DF Rev 27.05.2021
Installation and connections
Unscrew four lid screws and detach the lid from the detector.
Fix the detector on a wall by screws, using cross-shaped mounting lugs supplied with the
instrument (see dimensional drawings below).
To connect the device with measurement point, use the hoses of appropriate diameter (4
or 6 mm) and length. Put one end of the hose on the fitting in the bottom part of the device
and fix the other end in the selected measurement area. The port marked with + (plus)
should be connected with the area of higher pressure (e.g. before air filter), the one marked
with - (minus) should be connected to the lower pressure area (e.g. behind air filter).
NB! The connecting hoses should not be squeezed or folded.
The connection diagram of the device is shown below.
5

E2408DF Rev 27.05.2021
Plug the power cable and connect the analog outputs and/or digital interface terminals to
the relevant devices according to the connection diagram and table.
Version without PSU Version with PSU
Jumpers
J1
OUT1 type (open: 4-20 mA; closed 0-10 V)
J2
OUT2 type (open: 4-20 mA; closed 0-10 V)
X6
Reset Modbus network parameters to default
X4 terminals
OUT1
4-20 mA / 0-10 V output
OUT2
4-20 mA / 0-10 V output
0V
0 V / 24 VAC Neutral (optional)
A
RS485 A / Data +
B
RS485 B / Data -
+U
+24 VDC / 24 VAC Phase (optional)
6

E2408DF Rev 27.05.2021
X5 terminals (optional)
L
90…265 VAC Phase
N
90…265 VAC Neutral
RE1 NO
Relay 1, normally open terminal
RE1 COM
Relay 1, common terminal
RE2 NO
Relay 2, normally open terminal
RE2 COM
Relay 2, common terminal
7

E2408DF Rev 27.05.2021
Make certain that the cable gland is properly tightened to ensure the conformity to IP65
protection class.
The screwless quick connect spring terminals on the E2407 are suitable for a wide range
of wires with cross-section 0,2...1,5 mm2. The recommended wire stripping length is 8...9
mm. Push the spring loaded terminal lever, insert the wire end into the terminal hole and
release the lever.
Use twisted pair cable, e.g. LiYY TP 2×2×0,5 mm2 or CAT 5, to connect the device to the
RS485 network. Use one pair for A and B wires and the second pair for common 0V and
power +U wires. to connect the transmitter to the Fieldbus network.polarity must be
respected when connecting to an external RS485 network.
Overall length of all connections via the RS485 interface should not exceed 1200 m.
Both analog outputs can be independently changed between 4-20 mA and 0-10 V type
using jumpers J1 (OUT1) and J2 (OUT2). By closing pins on a specific jumper the related
output is 0-10 V, with an open jumper the output is 4-20 mA. Power restart is required after
changing the position of the jumpers.
NOTE! The outputs are not galvanically isolated from the external power supply and share
a common 0V. Allowed load resistance limits are stated in the Specifications table. To
power the instrument from an external power source, connect terminals 0V and +U to the
source. If the integrated mains power supply module is used, connect terminals L and N to
the mains.
NOTE! If the instrument is powered from mains, connect to 0V and +U terminals only light
external loads, which consume less than 30 mA in total, as the integrated mains supply
module capacity is limited.
NOTE! Actuator short-circuits should be avoided, to protect the instrument relays use
external fuses or safety switches.
When the detector is fixed and the external devices connected, place the lid back and fix it
with the screws.
8

E2408DF Rev 27.05.2021
Delivery set
●Differential pressure transmitter-regulator E2408DF
●Mounting accessories:
○4 cross-shaped mounting lug with screws and 4 screws with plastic
dowels
Order code for E2408DF options
E2408DF options
Order code
Differential pressure transmitter-regulator, mass flow,
-50...50 Pa, resolution 0,025 Pa
E2408DF-50
Differential pressure transmitter-regulator, mass flow,
-500...500 Pa, resolution 0,25 Pa
E2408DF-500
Integrated 90...265 V mains power supply module
E2408DF-230
Configuring
Differential pressure transmitter-regulator E2408DF shares all functionalities of the
PluraSens® multifunctional transmitter platform. The features and options include:
●Digital output change rate limiting filter
●Digital integrating (averaging) filter
●Temperature measurement channel with internal sensor
●Free assignment of each analog output to chosen parameter
●Flexible setting of analog output scales for each output
●Free assignment of each of two relays to chosen parameter
●Several relay control logic modes (HI or LO with hysteresis, U or П)
●Switch delays and minimum on/off state durations for each relay
●Modbus controlled forced state options for analog outputs and relays.
E2408 can be configured through its RS485 interface by Modbus RTU commands.
9

E2408DF Rev 27.05.2021
Return to default settings
To reset the device’s Slave ID, baud rate and stop bit number to factory settings, proceed as
follows:
1. De-energize the device
2. Connect the X6 jumper
3. Turn on the device
4. De-energize the device
5. Disconnect the X6 jumper
6. Turn on the device
Emergency mode.
The current outputs of the detector may be programmed via Modbus commands (register
255) to signal if the connection with the sensor is lost. The signal may be set to 3,8 mA
(low current) or 21,5 mA (high current).
Bites
Functions
Notes
Default
bit[0]=0/1
sensor present/absent
Read-only
bit[1]=0/1
analog outputs activated/deactivated
1
bit[2]=0/1
in case of sensor absence, turn signalling
off/on (OUT 1)
1
bit[3]=0/1
In case of sensor absence turn on
signalling with low/high current on OUT 1
if bit [2]=0, this bit is ignored
0
bit[4]=0/1
in case of sensor absence, turn signalling
off/on (OUT 2)
1
bit[5]=0/1
In case of sensor absence turn on
signalling with low/high current on OUT 2
if bit [4]=0, this bit is ignored
0
bit[6]=0/1
Current/voltage output detected on OUT 1
Read-only
User defined
bit[7]=0/1
Current/voltage output detected on OUT 2
Read-only
User defined
bit[8]=0/1
LED deactivated/activated
Always 0 for 2408DF
0
bit[9]=0/1
Buzzer deactivated/activated
Always 0 for 2408DF
0
10