Evo HE C22/24 Bedienungsanleitung

C22/24, C22/30, C22/35
Wall mounted, balanced flue, fanned gas boiler
Advanced High Efficiency Boilers
Users Guide
See reverse for evo HE Installation & Servicing Instructions
Manufactured exclusively for Wolseley Centers Ltd. by Ideal Boilers

2evo HE C - User’s
In cases of repeated or continuous shutdown a Gas Safe
Registered Engineer or in IE a Registered Gas Installer (RGII)
should be called to investigate and rectify the condition causing
this and carry out an operational test. Only the manufacturers
original parts should be used for replacement.
Minimum Clearances
Clearances of 165mm (6 1/2") above, 100mm (4") below, 5mm
(1/4") at the sides and 450mm (17 3/4") at the front of the boiler
casing must be allowed for servicing.
The minimum front and bottom clearance allowed when built into
a cupboard is 5mm.
To light the boiler. Refer to Frame 1
If a programmer is fitted refer to separate instructions for the
programmer before continuing.
1. CHECK THAT THE ELECTRICITY SUPPLY TO THE BOILER
IS OFF.
2. Set the mains ON/OFF switch (A) to OFF and the DHW
thermostat knob (J) and CH thermostat knob (F) to maximum.
3. Ensure that all DHW taps are turned off.
4. Switch ON the electricity supply to the boiler and check that
all external controls, e.g. programmer, room thermostat etc.,
are ON.
5. Set the mains ON/OFF switch to ON.
The boiler will commence the ignition sequence, first supplying
heat to preheat the domestic hot water and then to the central
heating, if required.
Note. In normal operation the control unit display (C) will show
codes:
Standby - no demand for heat. CH being supplied.
DHW being supplied. DHW preheat.
Boiler frost protection - boiler will fire if temperature is
less than 3 degrees C.
During ignition, the LED (E) will flash.
During normal running the LED (E) will remain illuminated.
Note. If the boiler fails to light after 3 attempts this fault code
will be displayed.
Press the reset button (D) for 2 seconds then release. The boiler
will repeat the ignition sequence. If the boiler still fails to light
consult a Gas Safe Registered Engineer or in IE a Registered
Gas Installer (RGII).
Operation
Winter conditions - i.e. CH and DHW required.
The boiler will fire and supply heat to the radiators but will give
priority to DHW on demand.
The DHW preheat will operate as described under 'Summer
conditions' during periods when there is no call for CH.
Destination Countries: GB, IE
evo HE C22/24, C22/HE30, C22/HE35
(Natural Gas Only)
C22/HE24 G.C. Appliance No. 47-348-32
C22/HE30 G.C. Appliance No. 47-348-33
C22/HE35 G.C. Appliance No. 47-348-34
Introduction
The evo HE is a wall mounted, room sealed, condensing
combination boiler, featuring full sequence automatic spark
ignition and fan assisted combustion.
Due to the high efficiency of the boiler, condensate is produced
from the flue gases and this is drained to a suitable disposal point
through the plastic waste pipe at the lower rear of the boiler. A
condensate 'plume' will also be visible at the flue terminal.
The evo HE is a combination boiler providing both central heating
and instantaneous domestic hot water.
Safety
Current Gas Safety (Installation & Use)
Regulations or rules in force.
In your own interest, and that of safety, it is the law that this boiler
must be installed by a Gas Safe Registered Engineer, in
accordance with the above regulations.
In IE, the installtion must be carried out by a Registered Gas
Installer (RGII) and installed in accordance with the current
edition of I.S. 813 “Domestic Gas Installations”, the current
Building Regulations and reference should be made to the
current ETCI rules for electrical installation.
It is essential that the instructions in this booklet are strictly
followed, for safe and economical operation of the boiler.
Electricity Supply
This appliance must be earthed.
Supply: 230 V ~ 50 Hz. The fusing should be 3A.
Connection must be made in a way that allows complete isolation
of the electrical supply such as a double-pole switch, having a
3mm (1/8") contact separation in both poles, serving only the
boiler and system controls. Alternatively, a 3-pin UNSWITCHED
socket may be used. The means of isolation must be accessible
to the user after installation.
Important Notes
zThis appliance must not be operated without the casing
correctly fitted and forming an adequate seal.
zIf the boiler is installed in a compartment then the
compartment MUST NOT be used for storage purposes.
zIf it is known or suspected that a fault exists on the boiler then
it MUST NOT BE USED until the fault has been corrected by
a Gas Safe Registered Engineer or in IE a Registered Gas
Installer (RGII).
zUnder NO circumstances should any of the sealed components
on this appliance be used incorrectly or tampered with.
zThis appliance is not intended for use by persons (including
children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they
have been given supervision or instructions concerning use of
the appliance by a person responsible for their safety.
zChildren should be supervised to ensure that they do not play
with the appliance.
All Gas Safe Registered Engineers carry a Gas Safe Register ID card, and have a registration number. Both should be recorded
in the Benchmark Commissioning Checklist. You can check your installer by calling Gas Safe Register direct on 0800 4085500
THE BENCHMARK SERVICE INTERVAL RECORD MUST BE COMPLETED AFTER EACH SERVICE
Ideal Stelrad Group is a member of the Benchmark scheme and fully supports the aims of
the programme. Benchmark has been introduced to improve the standards of installation and
commissioning of central heating systems in the UK and to encourage the regular servicing of all
central heating systems to ensure safety and efficiency.

3evo HE C - User’s
Legend
A. Boiler ON/OFF switch.
C. Display.
D. Reset button.
E. LED.
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of
this appliance care should be taken when handling edges of sheet steel components.
1
BOILER CONTROLS
Summer conditions - i.e. DHW only required.
Set the thermostat knob to OFF.
The boiler will fire periodically for a few seconds to maintain the
DHW calorifier in a preheated condition. The average time
period between firing is 90 minutes. This may vary considerably
due to the surrounding ambient temperature of the boiler. The
boiler will fire whenever there is a demand for DHW.
Note. The pump will operate briefly as a self-check once every
24 hours, regardless of system demand.
Control of water temperature
Domestic Hot Water
The DHW temperature is limited by the boiler controls to 65oC
maximum at low draw-off rate, adjustable via the DHW
thermostat knob (J).
Due to system variations and seasonal temperature fluctuations
DHW flow rates/temperature rise will vary, requiring adjustment
at the draw off tap : the lower the rate the higher the temperature,
and vice versa.
Central Heating
The boiler controls the central heating radiator temperature to a
maximum of 82oC, adjustable via the CH thermostat knob (F).
To shut down the boiler
1. For short periods
Set the mains ON/OFF switch (A) to OFF
2. For longer periods
Set the mains ON/OFF switch (A) to OFF, and switch the
electricity supply to OFF. For longer periods the entire system
should be drained.
To relight the boiler
Repeat the procedure detailed in 'To light the boiler'.
Frost protection
If no frost protection is provided and frost is likely during a short
absence from home, leave the heating controls (if fitted) at a
reduced temperature setting. For longer periods, the entire
system should be drained.
If the system includes a frost thermostat then, during cold
weather, the boiler should be turned OFF at the time switch (if
fitted) ONLY. The mains supply should be left switched ON, with
the boiler thermostat left in the normal running position.
Boiler overheat thermostat
This thermostat will shut down the boiler in the event of
overheating. Should this occur a fault code or will be
displayed. Press the reset button (D) and the boiler will relight.
If the fault recurs, turn off the boiler and consult a Gas Safe
Registered Engineer or in IE a Registered Gas Installer (RGII).
Flame failure
Should this occur a fault code will be displayed.
Press the rest button (D) and the boiler will relight.
If the fault recurs, turns off the boiler and consult a Gas Safe
Registered Engineer or in IE a Registered Gas Installer (RGII).
Loss of system water pressure
The gauge (H) indicates the central heating system pressure. If
the pressure is seen to fall below the original installation pressure
of 1-2 bar over a period of time then a water leak may be
indicated. In this event conduct the re-pressurising procedure
(see Trouble Shooting - Problem 4). If unable to do so or if the
pressure continues to drop a Gas Safe Registered Engineer or
in IE a Registered Gas Installer (RGII) should be consulted.
DO NOT FIRE THE BOILER IF THE PRESSURE HAS
REDUCED TO ZERO FROM THE ORIGINAL SETTING.
Condensate Drain
The condensate drain (G) must not be modified or blocked.
Blockage of the condensate drain, caused by debris or freezing,
can cause automatic shutdown of the boiler.
If freezing is suspected and the pipe run is accessible an attempt
may be made to free the obstruction by pouring hot water over
the exposed pipe and clearing any blockage from the end of the
pipe. If this fails to remedy the problem the assistance of a Gas
Safe Registered Engineer or in IE a Registered Gas Installer
(RGII) should be sought.
Escape of gas
Should a gas leak or fault be suspected contact the National Gas
Emergency Service without delay. Telephone 0800 111 999
Do NOT search for gas leaks with a naked flame.
Cleaning
For normal cleaning simply dust with a dry cloth.
To remove stubborn marks and stains, wipe with a damp cloth
and finish off with a dry cloth.
DO NOT use abrasive cleaning materials.
Maintenance
The appliance should be serviced at least once a year by a Gas
Safe Registered Engineer or in IE a Registered Gas Installer
(RGII).
Approx. flow temperatures for the boiler thermostat settings are:
Knob Setting Flow Temperature
oCoF
Minimum 30 86
Maximum 82 180
F. CH thermostat knob.
G. Condensate drain.
H. Pressure gauge.
J. DHW thermostat knob.

POINTS FOR THE BOILER USER
Note. In line with our current warranty policy we would ask that you check through the following guide to identify any
problems external to the boiler prior to requesting a service engineers visit. Should the problem be found to be other than
with the appliance we reserve the right to levy a charge for the visit, or for any pre-arranged visit where access is not
gained by the engineer.
TROUBLESHOOTING - TYPICAL NON PRODUCT FAULTS
Problem Solution
Boiler is not working for
central heating or hot water.
• Check there is power to the boiler – switch (A) in the ON position and ‘
0
’displayed on the
controls.
•If‘
0
’ not displayed then not a boiler fault – contact your installer/service company.
Boiler is not working for
central heating or hot water
and the display shows ‘
L:AL:A
L:AL:A
L:A
’
(flashing).
• Press reset button (D) for 2 seconds, the boiler should then re-light. If fault recurs this indicates
an overheat condition. The boiler should be turned off and your installer contacted.
• Check if ALL radiators have thermostatic radiator valves fitted. If they have contact your
installer.
Boiler is not working for
central heating or hot water
and the display shows ‘
H:AH:A
H:AH:A
H:A
’
(flashing).
• Check pressure gauge on boiler shows a minimum of 1 bar. If not re-pressurise via the filling
loop to 1 bar (if unsure contact your installer), turn off the tap on the filling loop and turn the on/
off switch (A) off and then back on again to reset the boiler. If unable to do so or if the pressure
continues to drop after filling then contact your installer.
• Check if ALL radiators have thermostatic radiator valves fitted. If they have contact your
installer.
Boiler is not working for central
heating or hot water but
attempts to fire by going
through 3 ignition attempts.
Display shows ‘
L : FL : F
L : FL : F
L : F
’(flashing).
• Press reset button (D) for 2 seconds to repeat ignition sequence.
• Check gas supply (try another appliance – cooker/fire etc.) – If no gas supply then not a boiler
fault – contact gas supplier.
• Check condensate pipe is not blocked or frozen. If blocked clear blockage – if not possible to
check contact your installer.
Boiler will not fire for central
heating.
• Check external programmer is set to an ‘ON’ period.
• If already set to an ‘ON’ period then check the programmer by setting to continuous if boiler then
fires – Contact your installer to rectify the programmer.
• Check room thermostat by turning fully up, If ‘0’ is not displayed on the user controls then
contact your installer.
Boiler comes on for domestic
hot water without a tap being
opened - the display shows
‘D’.
• Check for dripping / dribbling taps or showers – turn fully off.
• Check for leaks from the domestic hot water pipework and if found contact your installer.
Boiler fires occasionally for
approx. 2 minutes - the
display shows ‘t’.
• This is a normal function of the boiler to periodically pre heat the plate heat exchanger to
optimise delivery time for domestic hot water to taps or showers.
The nature of all combination boilers is to heat up water directly from the incoming mains water supply directly through the boiler to
supply domestic hot water at the stated flow rates, (as shown in the boiler installation instructions), to achieve a 35oC temperature
rise. As the ambient temperature of the cold main varies during the summer and winter months it is likely in the colder winter months
that the flow rate will need to be reduced at the outlet taps to achieve the same temperatures achieved in the warmer summer
months. This is not a fault with the appliance but is relevant to the varying temperature of the incoming cold mains water
supply.
1
3
4
2
5
6
7
Wolseley Consumer Helpline 0870 849 8057
The code of practice for the installation,
commissioning & servicing of central heating systems
Andere Handbücher für C22/24
1
Dieses Handbuch passt für folgende Modelle
2
Inhaltsverzeichnis
Andere Evo HE Kessel Handbücher
Beliebte Kessel Handbücher anderer Marken

Vaillant
Vaillant uniSTOR VIH SW GB 500 BES Bedienungsanleitung

Radijator
Radijator BIO max 23.1 Bedienungsanleitung

Brunner
Brunner BSV 20 Bedienungsanleitung

Buderus
Buderus Logamax GB062-24 KDE H V2 Bedienungsanleitung

Potterton
Potterton 50e Datenblatt

UTICA BOILERS
UTICA BOILERS TriFire Bedienungsanleitung














