FibroPool FH135 Leitfaden

V.23.02 FIBROPOOL USA

1. WARNING
TO DO:
●Please install the unit in compliance with local CODES regulations and standards;
●Please use a solid base, such as 2 pieces of 16” x 16” x 4” concrete blocks or an equipment
base of 16” x 32 inches minimum size
●Confirm power voltage and frequency; 110-125 volts, 60 Hz 20 Amps
●If the heater is within 50 feet of the breaker box, use 12 AWG gauge wire (12-2+ Ground) and
20 Amp breaker on a GFCI protected outlet
●If the heater is 50-150 feet from the breaker box, use 10 AWG wire (10-2+Ground) and 20
Amps GFCI breaker
●The heater must be BONDED to a ground rod, using #8 AWG bare copper wire
●An external timer can be used, be sure it I an outdoor Appliance type, minimum 15 amps
Inductive
●1 1/2” schedule 40 PVC OR 1 ½” or 1 ¼” corrugated filter connection hoses OR 1 5” Intex
hoses must be used to connect plumbing
●WATER AND ELECTRICITY DON’T MIX PLEASE USE ALL PRECAUTIONS
●This heater is made of mostly metal alloys and may have sharp edges Please use gloves
while handling it
●Keep a minimum of 6 feet distance between the heater and the pool wall
●Fibropool FH135 is weatherproof and designed to be outdoors, but is not splash-proof Choose
a location away from splashing from the pool
NOT TO DO:
●Do NOT install this heater where there may be flammable gas
●Do NOT install this heater in an enclosed room Without adequate air supply, performance will
be severely limited If the unit is installed in a closed area or limited space, please consider the
size of room and ventilation to prevent suffocation caused by refrigerant leakage
●Do NOT try to lift the unit by yourself The FH135 weighs about 100 lbs It is a 2 person
handling size and weight
●Do NOT install below eaves of the roof, where water pours onto it
●DO NOT SHORTCUT ANY SAFETY PROCEDURES
V.23.02 FIBROPOOL USA

System Specifications
1. Specifications
Model FH135
82'F Air 82'F Water 82% RH
Max Heating capacity (Btu/h) 34,700
Max Power input (Btu/h) 7200
COP 5 56
60'F Air 75'F Water 65%RH
Heating capacity (Btu/h) 33440
Power input (Btu/h) 8360
COP 4 01
Power supply 110-125V/60Hz
Max power input (Btu/h) 7200
Max current (A) 15 7
Setting temperature range (Heating) 60°F~99°F
Setting temperature range (Cooling) 50°F~82°F
Running (Air) temperature range 45°F~115°F
Refrigerant type/quantity (Oz) R410A/ 16 Ozs
Air side heat exchanger Hydrophilic fin exchanger
Water side heat exchanger Titanium tube heat exchanger
Water flow (gpm) 33 GPM
Net dimension LxWxH (inch) 37 x 14 x 25
Packing dimension LxWxH (inch) 41 x 17 x 33
Net weight (lbs) 78 lbs
Packing weight (lbs)98
Noise level dB(A) 47
Water proof level IPX4
Water pipe connection PVC Sch 40 1-1/2”
Inlet/Outlet
The technical specification of our heat pumps is provided for informational purpose only We
reserve the right to make change without notice in advance
Performance varies greatly depending on the weather conditions
1 Ratings based on US Dept Of Energy guidelines, 82-82-82 / 80-80-80/ 78-78-78
2 US Dept Of Energy recommends pool water temperatures 78, 80, or 82 Degrees
3 FH 135 is engineered and optimized based on US Dept Energy recommendations
4 We do not calibrate or size the heaters above 82'F pool water temperatures
5 55 dB noise at 10 feet, complies with Directives EN ISO 3741 and EN ISO 354
V.23.02 FIBROPOOL USA

1. Unit Dimensions
Model: FH 135
Dimensions are in Inches
V.23.02 FIBROPOOL USA

1. Exploded View
1 Grill Panel 9 Baffle plate 17 Base Frame
2 Fan 10 Water flow switch
3 Corner Bracket 11 Titanium heat exchanger 19 Fan Motor
4 Protective grill 12 Corner panel 20 Fan Bracket
5 Protection grill 13 Flip Cover
6 Evaporator coil 14 Terminal Cover
7 Electrical box 15 Cooper manifold
8 Top panel 16 Compressor
V.23.02 FIBROPOOL USA

Installation Instructions
WARNING: Installation must be performed by a qualified person
This section is provided for information purposes only and may vary depending on your
location, regulations, and available space for installation
1. Pre-Requirements
Required equipment for installation of heat pump:
Suitable power outlet, 110-125 volts, GFCI protected outlet
PVC pipe and fittings OR Corrugated filter connection hoses and necessary adapters, Pipe
cleaner/ primer, Medium Bodied Glue
Electrical tools, and a multi-meter
An equipment pad, 16” x 32” x 4” thick or 2 pieces of concrete blocks, 16 x 16 x 4 inches each
2. Location
Please consider the following when choosing a location for the heat pump:
1 Make sure the heater is not directly below roof drains, such as a gutter drain, or eaves
2 Be sure that the heater does not submerge in water in heavy rain
3 Be sure to install the drain adapters into the heater and attach the hose to direct the
condensation water Heater will produce gallons of water from condensation daily
4 Confirm the unit is in well-ventilated conditions and that the fan discharge grill vent is not
blocked (fan blows outwards )
5 Keep at least 12 inches of clearance on the two short sides and the long radiator side
6 Keep at least 3 feet of clearance on the fan side of the heater
7 Keep the unit as far as possible out of the reach of children and within 25 feet of the pool
V.23.02 FIBROPOOL USA

DRAIN ADAPTERS
Please install the drain adapters beneath the heater prior to installation You can attach 5/8” hose
to the adapters to direct the condensation water
PLUMBING
·On a typical installation on a pool with a small pump, such as ½, ¾ hp pump with 1 1/2”
PVC or flexible hoses, only the plumbing IN from the BOTTOM and OUT from the TOP pipe
connection is necessary
·For stronger systems (those with 1 5 HP and larger pumps and 2 inch plumbing systems) a
bypass system should be installed
·** A BYPASS SYSTEM IS NOT NECESSARY FOR ABOVE GROUND POOLS****
·If the heat pump is connected to a filtration circuit with a by-pass valve: We suggest to open
the bypass 50% then adjust down to achieve the lowest flow rate into the heater without
triggering error messages (EE-3, PL, EE1) This will give enough water to the heater without
restricting the flow The IN and OUT difference should be 1-5° Fahrenheit If the difference
is too great, increase the water flow through the heater for optimal heating
·The old system BYPASS path usually consists of 3 valves The New FIBROPOOL BYPASS
VALVE is just 1 valve This makes it possible to adjust water flow passing through the heat
pump
V.23.02 FIBROPOOL USA

1. Installation of a Single Heater
2. Parallel Installation for 2 Units
Throttled bypass valve, 50% open
V.23.02 FIBROPOOL USA

PIPE C NNECTI NS
1. FH 135 Features 1 1/2” SAE machine threads They are NOT the typical pipe threads You
can use the included unionized fittings with o-rings WITHOUT thread tape, or you can use
the conical hose adapters WITH thread tape
2. All fittings and pipes used must be 1 1/2” Sch 40 (Schedule 40) PVC pipe If using
corrugated flexible filter hoses, try to use the 1 ½” diameter hoses
3. Tighten all fittings by hand only If using the threaded hose adapters with thread tape, give
a ¼ turn with pliers after hand tight Excessive tightening will crack fittings
4. A minimum of 6 inches of straight pipe must be used before any elbows/fittings etc
5. Please support the pipes in the air, as gravity will eventually bend and break the fittings
6. If using flexible hoses, be sure to tighten the clamps well
7. Be sure to check your fittings and glue them properly, using pipe cleaner and a good grade
Medium bodied glue
8. Heaters have heat exchanger coils, therefore they increase back pressure
9. If your pool pump is larger than 1 horsepower, you should use a bypass valve This will help
water flow of your system to continue as original plumbing You simply need a 3 way valve,
and a Tee Refer to diagrams for the bypass set up
10. If you have 2 inch plumbing, use our 2 inch bypass valve and a 2 inch TEE, then use
reducers to 1 1/2” pipe to connect to the heater This way you will not compromise the water
flow
11. Be sure that WATER IN pipe is connected to the BOTTOM, and WATER OUT pipe is on
TOP Reversal will result in flow error code PL
Hard PVC Adapters Corrugated Filter Hose Adapters Intex Integrated hose
adapters
V.23.02 FIBROPOOL USA

ELECTRICAL C NNECTI NS
Power Supply Wires Size
Model Power Supply Wires
Power Supply Breaker Size Plug rating
FH 135 110-125V/60Hz 20 Amps 20 Amps
➢Step 1: Remove the 8 screws that are holding down the top lid of the heater ( yellow
stickers pointing to them). All adapters etc are inside the heater contained in a bag.
➢Step 2: Remove the bag and reinstall the lids 8 screws hand tight.
➢Step 3: Plug in the power cord of the heater and reset the GFCI by pushing the TEST
and RESET buttons.
➢FH 135 requires equipotential bonding. Please connect an #8 AWG bare copper wire to a
ground rod. This is required for safety and corrosion prevention of the heater’s metal
chassis.
V.23.02 FIBROPOOL USA
Inhaltsverzeichnis
Andere FibroPool Wärmepumpe Handbücher
Beliebte Wärmepumpe Handbücher anderer Marken

Mitsubishi Electric
Mitsubishi Electric PUZ-SWM60VAA Bedienungsanleitung

Dimplex
Dimplex LI 16I-TUR Benutzerhandbuch

Carrier
Carrier WSHP Open v3 Kurzanleitung zur Einrichtung

TGM
TGM CTV14CN018A Bedienungsanleitung

Carrier
Carrier 38MGQ Series Bedienungsanleitung

Kokido
Kokido K2O K880BX/EU Fehlerbehebungshandbuch