Installing Detectors and other Devices on Detection Circuits
Locate and install the heat/smoke detectors or other devices by following the manufacturer’s
instructions.
Field Wiring
Suitable 12-18 AWG cable should be used for all field wiring, per the NFPA or other International
standards. Secure the field wiring with the appropriate hardware for the application, per local
codes. Take care not to pinch, break, or cut the field wiring while routing. The field wiring should
be routed starting at the Module, then to the pre-determined location of the first Heat/Smoke
Detector or Relay Operated Device on the circuit. Connect to the Control Module using the screw
terminal connectors provided. Connect to each component by following the Manufacturer’s
instructions. Repeat the routing process to each additional component on the circuit. Connect
the provided 4.7K ohm End of Line Resistor to the last component on the circuit by following the
Manufacturer’s instructions. Connect the provided 4.7K ohm End of Line Resistor to the Module
whenever a Zone is not used.
Devices that utilize the dry contact relays must be installed using the Common (C) and Normally
Open (NO) contacts.
Electrical Connections
Connect the main input voltage (9-32V DC) to the Control Module terminals labeled “V DC IN 1”.
Connect the backup power source to the Control Module terminals labeled “V DC IN 2”.