Flagro FLE-150 Bedienungsanleitung

OPERATING INSTRUCTIONS MANUAL
FLE-150
INDUSTRIAL / COMMERCIAL ELECTRIC HEATER
(OPERATOR MUST RETAIN FOR FUTURE REFERENCE)
Suitable for indoor or outdoor installation / Unvented / Unattended Type
26 Benfield Drive, St.Catharines, Ontario Canada L2S 3V5
(P) 905-685-4243 - (F) 905-685-0113

FLE-150 OPERATING INSTRUCTIONS MANUAL
GENERAL HAZARD WARNING:
FAILURE TO COMPLY WITH THE PRECAUTIONS
AND INSTRUCTIONS PROVIDED WITH THIS
HEATER, CAN RESULT IN DEATH, SERIOUS
BODILY INJURY AND PROPERTY LOSS OR
DAMAGE FROM HAZARDS OF FIRE, EXPLOSION
BURN ASPHYXIATION, OR ELECTRICAL SHOCK
ONLY PERSONS WHO CAN UNDERSTAND AND
FOLLOW THE INSTRUCTIONS SHOULD USE OR
SERVICE THIS HEATER.
IF YOU NEED ASSISTANCE OR HEATER
INFORMATION SUCH AS AN INSTRUCTIONS
MANUAL, LABEL, ETC. CONTACT THE
MANUFACTURER
WARNING: FIRE, BURN, INHALATION
AND EXPLOSION HAZARD, KEEP SOLID
COMBUSTIBLES, SUCH AS BUILDING
MATERIALS, PAPER, OR CARDBOARD, A SAFE
DISTANCE AWAY FROM THE HEATER AS
RECOMMENDED BY THE INSTRUCTIONS
NEVER USE THE HEATER IN SPACES WHICH DO
OR MAY CONTAIN VOLATILE OR AIRBORNE
COMBUSTIBLES, OR PRODUCTS SUCH AS
GASOLINE SOLVENTS, PAINT THINNER, DUST
PARTICLES OR UNKNOWN CHEMICALS
WARNING: NOT FOR HOME OR
RECREATIONAL VEHICLE USE

Introduction
You have just received an FLE-150 150kW Electric Construction Heater manufactured by Flagro Industries.
Use: The FLE-150 Electric Construction Heater is designed for temporary heat only.
The heater may be installed indoors or out and used to bring 100% outdoor air, or heat
and re-circulate building air. The FLE-150 is designed to heat large spaces, buildings
and machines without worrying about on site fuel.
Quality
: The FLE-150 is built with the highest quality of components, giving our
customers the confidence they deserve in a Flagro product.
Convenience:
The FLE-150 gives our customers the flexibilty of a 60kW/90kW/150kW heat setting.
The heater is equipped with a; fan speed inverter control that provides optimum temperature rise
by adjusting blower output at each heat setting. Colour coded Cam Lock power connections
for easy installation. Remote thermostat option available.
Safety
Always verify that you have proper voltage supply. (480V) It is important to check
the wiring connections inside the heater before plugging in the Cam Locks.
Use a meter to measure volt supply to each cam lock.
Work on the internal systems should only be attempted by a certified electrician and
only when power has been disconnected and can not be reconnected to the heater.
Grounding
The heater is supplier with a cam lock system with a grounding connection and is indicated with a "G"
on the cam lock panel. The heater is also supplied with a grounding nuts found on all panels.
It is very important to double check that all grounding connections are properly secure.
Clearance from Combustibles
The discharge temperature of these units may reach very high temperatures. Maintain minimum
distance from combustible materials as follows:
Top: 6 Inches
Bottom: 6 Inches
Sides: 6 Inches
Discharge: 15 FT

MAINTENANCE
1Every heater should be inspected before each use, and at least annually by a
qualified service person
2The appliance must be kept clear and free from combustible materials,
gasoline and other flammable vapors and/or liquids
3The flow of ventilation air must not be obstructed.
Be sure to check the fan assembly and ensure the motor and blade
are operating properly.
4Compressed air may be used to keep components free of dust and dirt
build up.
Pre-Start Checklist
1
Heater must be level and lockable wheels must be in the lock position
2
Make sure blower switch and both heat selection switches are in the
"OFF" positions
3
Make sure the air intake is free from any obstruction(s)
4
Make sure the heater oulet is free from any obstruction(s)
5
Make sure the heater is properly grounded
6
Check power supply voltage and ampacity

START UP INSTRUCTIONS
1Determine power source - 480V (confirm power source is correct)
2Remove top cover and inspect all wiring
(once complete, secure top cover to heater using the same hardware)
3Connect Flanged Camlocks to female camlocks ( colour coded)
Connect camlocks as follows:
Red A
Black B
Blue C
Ground G
3 PHASE UNIT CONNECTION
4Turn on power supply
5Pull "Master" button to the out position
6Determine "Manual" or Remote Thermostat (if remote, set desired temperature)
7Turn Blower on/off switch to the "ON" position
(The blower will start and the green air flow light will come on)
8Turn on heater settings as desired
( 150kW= 60kW & 90kW combined)
Failure to have proper air flow will cause unit to overheat and shut down
The green light should come on and air should be pushed through the outlet port
Check to see that only the green light is on.
Caution: Heater body panels will get very hot

Notes:
Speed inverter is pre-set for optimum air flow/temperature rise.
Based on kW selection, blower will adjust speed. See Chart below
HEAT SETTING
BTUH
CFM
TEMP. RISE
NOISE RATING
150 kW 512,000 5300 138F 79 DB
90 kW 307,000 4650 101F 76 DB
60kW 205,000 4100 67F 73 DB
FAN ONLY 6800 N/A 85 DB
SHUTDOWN
1
Move all heat control setting to the "OFF" position
2
Leave Fan in the "ON" position for 3-5 minutes
3
Turn Fan OFF
( blower is preset to run for 30 seconds before coming to a complete stop)
4
Push Master button "IN"
5
Shut off all power source
6
Disconnect all power sources
7
Store heater

26 Benfield Dr. St.Catharines, Ontario Canada L2S 3V5
(O) 905-685-4243 (F) 905-685-0113
HEATER SPECIFICATIONS
MODEL FLE150
Power Requirements
480V
MAXIMUM INPUT (KW)
512,000 btu
BLOWER
7 1/2 H.P.
TEMPERATURE RISE
(above ambient)
60KW 67 F
90KW 101 F
150 KW 138 F
AMP DRAW
MOTOR 7 AMPS
60KW 64 AMPS
90KW 97 AMPS
150KW 161 AMPS
DB (noise level)
FAN ONLY 85
60KW 73
90KW 76
150KW 79
INLET SIZE
16" Dia.
OUTLET SIZE
20" Dia.
(Designed for 20" Dia. Ducting)
DIMENSIONS
40 X 58 X 33
H X L X W (IN.)
WEIGHT
560 LBS
AIR CIRCULATION
6800 CFM

FLE-150– PARTS LIST
FLE-1501 (480 VOLT)
FLE-1501A (575 VOLT)
150KW RESISTOR ELEMENT
FLE-1502
FAN BLADE ASSEMBLY
VARIALBLE SPEED DRIVE
7.5 P MOTOR
FLE- 1503 (480 VOLT)
FLE- 1503A (575VOLT)
FLE-1504 (480 VOLT)
FLE-1504A (575 VOLT)
FUSES
FLE-1509 - 125 Amp Class T
FLE-1510 - 90 Amp Class T
FLE-1511 – 10 Amp Class CC
FLE-631 – ½ Amp Class CC
FLE-632 - 5 Amp AGC Glass
TRANSFORMER
FLE-627 – 480V
FLE-627A – 575V
CONTACTOR
FLE-1507 – 90 amp
(2 PER UNIT)
GROUNDING BLOCK
FLE-621
RELAY
FLE-626
(2 PER UNIT)

FLE-150 PARTS LIST
FLE-1512
AIR PROVING SWITC IG LIMIT
(250-F)
2 POSITION SWITC
FLE-633
60KW
90KW
T ERMOSTAT/MANUAL
BLOWER ON/OFF
EMERGENCY STOP BUTTON
FLE-634
GREEN AIR PROVEN LIG T
FLE-636 FLE-635
IG LIMIT/AIR PROVEN LIG T
T ERMOSTAT
FV-414B
N/C CONTACT BLOCK
FLE-639
(3 PER UNIT)
N/O CONTACT BLOCK
FLE-640
(7 PER UNIT)
FLE-1513

FLE-150 PARTS LIST
W EELS
FLE-609 – 6” LOCKABLE
FLE-610 – 6” RIGID
FLE-611 – BLUE
FLE-612 – BLACK
FLE-613 – GREEN
FLE-614 - RED
CAM-LOCK - PANEL
CAM-LOCK DETAC ABLE
FLE-615 – BLUE
FLE-616 – BLACK
FLE-617 – GREEN
FLE-618 - RED
SNAP COVERS - PANEL
FLE-611A – BLUE
FLE-612A – BLACK
FLE-613A – GREEN
FLE-614A - RED
INLET GUARD
FLE-1514