Gemu SideStep Profibus DP Bedienungsanleitung

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
1/42
GEMÜ SideStep®Motorized Actuator
Industrial OPEN/CLOSE Profibus DP
Status 06.04.09
from version 1.0.6.0
GB OPERATING INSTRUCTIONS

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
2/42
CONTENTS
1. TECHNICAL DATA - GEMÜ SIDESTEP PROFIBUS DP 3
2. ELECTRICAL CONNECTIONS 3
2.1. GEMÜ SideStep industrial OPEN/CLOSE Profibus DP 3
2.2. RS-485 4
2.3. Profibus DP status LED 4
2.4. Supply voltage 4
2.4.1. 24V DC supply voltage 4
2.4.2. 120V 50/60Hz or 230V 50/60Hz supply voltage 4
3. WIRING IN THE PROFIBUS SYSTEM 5
4. SERIAL WIRING IN THE BUS SYSTEM 5
5. BUS WIRING VIA STUB 6
6. DIFFERENT CONFIGURATION MENU 6
7. CYCLIC PROFIBUS DATA 7
7.1. Set value and digital input 7
7.2. Valve position 7
7.3. Digital output 7
7.4. Parameter data: Parameters / Actions / Errors 8
7.4.1. No action 8
7.4.2. Change parameters 8
7.4.3. Request parameters 9
7.4.4. Read error list 10
7.4.5. Amount of active errors and readout of the active error 11
7.4.6. Amount of active warnings and readout of the actice warnings 12
7.4.7. Trigger action in the SideStep 12
7.4.8. Quit TravelTimeError 13
7.4.9. Quit Field bus Event 13
7.4.10. NoInit 14
7.4.11. Clear Error List 15
7.4.12 Set Default 15
7.4.13. Init valve 16
7.4.14. GoClose 16
7.4.15. GoOpen 17
8. EXTERNAL DIAGNOSTIC ERRORS 18
9. PARAMETER NUMBERS 19
10. CONFIGURATION EXAMPLE USING SIEMENS S7 23

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
3/42
1. Technical Data - GEMÜ SideStep Profibus-DP
Protocol flow
GSD data file G9ASSind.GSD
PNO-ID 0x2079
Baud rate 9.6 baud
19.2 baud
93.75 baud
187.5 baud
500 baud
1.5 Mbaud
3 Mbaud
6 Mbaud
12 Mbaud
Profibus address 26
(Default setting)
2. Electrical connections
2.1. GEMÜ SideStep industrial OPEN/CLOSE Profibus DP
Connection Pin Signal name
X1 1 Uv, L1 / L+ supply voltage
Connector plug 2 Uv, N / L- supply voltage
3 n.c.
4 n.c.
5 n.c.
6 n.c.
PE conductor
Connection Pin Signal name
X3 1 n.c.
M12 plug 2 RxD/TxD-N
B coding 3 n.c.
PB in 4 RxD/TxD-P
5 Shield
Connection Pin Signal name
X4 1 BUS-VDC, +5V DC
M12 socket 2 RxD/TxD-N
B coding 3 DGNG
PB out 4 RxD/TxD-P
5 Shield

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
4/42
2.2. RS-485
2.3. Profibus DP status LED
Profibus DP status LED
Red light – no bus connection
No light – bus connection ok
No function at Profibus DP design
2.4. Supply voltage
2.4.1. 24V DC supply voltage
Plug Pin Signal name Wiring
internal external
X1 1 Uv, L+ supply voltage 24V DC power
supply
X1 2 Uv, L- supply voltage
2.4.2. 120V 50/60Hz or 230V 50/60Hz supply voltage
Plug Pin Signal name Wiring
internal external
X1 1 Uv, L1 supply voltage AC power
supply
X1 2 Uv, N supply voltage
RxD/TxD-N
VP +5
DGND
RxD/TxD-P
1234
5
6789
~

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
5/42
3. Wiring in the Profibus system
4. Serial wiring in the bus system
With a transmission rate ≥1.5 Mbaud.
390
Ω
390
Ω
220
Ω
390
Ω
390
Ω
220
Ω
VP +5
DGND
VP +5
DGND
Shield
Protection
ground
Protection
ground
Slave
With transmission rates
≥1.5 Mbaud no wiring with
drop cables
Profibus
terminating
resisto
r

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
6/42
5. Bus wiring via drop cable
With a transmission rate ≤1.5Mbaud.
6. Different configuration menu
The GEMÜ SideStep with Profibus DP has the following expanded configuration menu
compared to the standard SideStep:
DP Adr
Determines the Profibus address of the actuator.
PwrOnT.Out
Defines the time between error recognition and message when the actuator is switched
on.
Profibus
terminating
resisto
r
Service
1SetBasics
2 SetFunction
3SetCalibration
4Return
6
SETUP
Communication
5
Fieldbus
5.2
IR-Port
5.1
DP adrr 26 Return
PwrOnT.Out

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
7/42
7. Cyclic Profibus data
Input data: (Profibus ÅSideStep)
Addr. 0 Addr. 2 Addr. 3
2 bytes 1 byte 8 bytes
Valve position Dig. Out Parameters / Actions / Errors (see page 9)
Output data: (Profibus ÆSideStep)
Addr. 0 Addr. 1
1 byte 8 bytes
Set value and digital input Parameters / Actions / Errors (see page 9)
7.1. Set value and digital input
Profibus ÆSideStep
Set value Digital Input bit 7 6 5 4 3 2 1 0
1 byte Stop valve X X 0 0
Open valve X X 0 1
Close valve X X 1 0
Valve moves to X X 1 1
position Pref Dir
Digital input 1 0 1 X X
Digital input 2 1 0 X X
Digital input 1 + 2 1 1 X X
7.2. Valve position
Profibus ÅSideStep
0..1000
Valve position
2 bytes
7.3. Digital Output
Profibus ÅSideStep
Digital Output bit 7 6 5 4 3 2 1 0
1 byte Digital output 1 0 1
Digital output 2 1 0
Digital output 1 + 2 1 1

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
8/42
7.4. Parameter data: Parameters / Actions / Errors
SideStep ÅÆProfibus
Parameters / Actions / Errors:
Toggle Para
code
Para
ID
Para
value
1
byte
1
byte
2
bytes
4
bytes
8 bytes
If the same information is sent more than once, the data record needs to be changed via
the toggle byte.
7.4.1. No action
When using the “N” (NOP) instruction, no action is carried out. The response is another
NOP instruction.
Inquiry from the master:
0xYY 0x4E (“N“) 0x00, 0x00 0x00, 0x00, 0x00, 0x00
1 byte 1 byte 2 bytes 4 bytes
Response of the SideStep:
0xYY 0x4E (“N“) 0x00, 0x00 0x00, 0x00, 0x00, 0x00
1 byte 1 byte 2 bytes 4 bytes
7.4.2. Change parameters
The “S“ (SET) instruction enables the change of a parameter in the SideStep via the
Profibus. As a response, the SideStep returns the SET instruction with the changed
parameter value. If the value is higher than the valid range, an external diagnostic error
with code 0x21 is generated; if below, the error generated has code 0x20.
Where the parameter does not exist, the diagnostic error triggered has code 0x22, and the
value returned is 0.
In case of a parameter change, the new value of the parameter is returned to the master
together with a SET instruction.
Where the parameter does not exist, the value returned is 0.

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
9/42
Inquiry from the master:
0xYY 0x53 (“S“) ID Value of the parameter
1 byte 1 byte 2 bytes 4 bytes
Response of the SideStep:
0xYY 0x53 (“S“) ID Value of the parameter
1 byte 1 byte 2 bytes 4 bytes
The individual parameters of the GEMÜ SideStep are on page 19.
Ex: The Mode parameter needs to be changed to Manual.
0xYY 0x53 (“S“) ID Value of the parameter
Mode Manual
0xYY 0x53 0x64 0x00, 0x00, 0x00, 0x02
7.4.3. Request parameters
The “G“ (GET) instruction is used to request from the SideStep the value of a parameter
via the Profibus. The SideStep responds with a GET instruction containing the parameter
value.
Where the parameter does not exist, an external diagnostic error with code 0x22 is
triggered.
Inquiry from the master:
0xYY 0x47 (“G“) ID2 0x00 0x00 0x00 0x00
1 byte 1 byte 2 bytes 4 bytes
Response of the SideStep:
0xYY 0x47 (“G“) ID Value of the parameter
1 byte 1 byte 2 bytes 4 bytes
When the parameter value in the GEMÜ SideStep changes, it is
immediately sent to the Profibus master. There is no need to
continuously request the parameter.

ACTRONIC® Profibus DP Operating instructions
SideStep® Industrial OPEN/CLOSE
10/42
7.4.4. Read error list
The error list is requested using the “E“ (Error List) instruction.
Inquiry from the master:
0xYY 0x45 (“E“) Serial num-
ber of error
in the list
0x00, 0x00, 0x00, 0x00
1 byte 1 byte 2 bytes 4 bytes
The first error is requested with 0x00 0x00
Response of the SideStep:
0xYY 0x45 (“E“) Serial num-
ber of error
in the list
Error information
1 byte 1 byte 2 bytes 4 bytes
Attention:
•When a new error occurs, the serial numbering of the listed errors changes.
Error 0 then becomes Error 1, Error 1 becomes Error 2, etc.
•Once the error list is full, the oldest error in the list is deleted.
•If no entry on the required number is found in the error list, an external
diagnostic error with code 0x34 is triggered. In this case the response value
is 0xFF 0xFF 0xFF 0xFF
•With number 0 the current error can be monitored
•If there is no error in the error list, error 0x00 0x00 0x00 0x00 is displayed