Genetec Synergis IX SY-SIX-CTRL-DIN Bedienungsanleitung

Synergis IX Web Enabled DIN
Rail Controller
SY-SIX-CTRL-DIN
Installation Manual

SY-SIX-CTRL-DIN | Synergis IX Web Enabled DIN Rail Controller | Installation Manual
Last Updated September 2018 2
The contents of this guide are furnished for informational use only and are subject to change without notice.
Genetec assumes no responsibility or liability for any errors or inaccuracies that may appear in the
informational content contained in this guide.
Genetec reserves the right to revise and improve its products as it sees fit. This document describes the state
of a product at the time of document’s last revision, and may not reflect the product at all times in the future.
In no event shall Genetec be liable to any person or entity with respect to any loss or damage that is incidental
to or consequential upon the instructions found in this document or the computer software and hardware
products described herein. The use of this document is subject to the disclaimer of liability found in the
end-user license agreement.
This publication may not be copied, modified, or reproduced in any form or for any purpose, nor can any
derivative works be created therefrom without Genetec’s prior written consent.
Copyright © 2018 Genetec.

SY-SIX-CTRL-DIN | Synergis IX Web Enabled DIN Rail Controller | Installation Manual
Last Updated September 2018 3
Contents
Introduction ............................................................................................................................. 5
Installation Requirements ...................................................................................................... 6
Grounding Requirements ....................................................................................................... 7
Safety Grounding .......................................................................................................................................... 7
Earth Ground Connection ............................................................................................................................. 7
Mounting .................................................................................................................................. 9
Removal ....................................................................................................................................................... 9
Connections .......................................................................................................................... 10
Power Requirements .................................................................................................................................. 10
Encrypted Module Network ........................................................................................................................ 11
Module Wiring ..................................................................................................................................... 12
End of Line (EOL) Resistors ............................................................................................................... 12
Telephone Dialer ........................................................................................................................................ 12
Ethernet 10/100 Network Interface ............................................................................................................. 13
Configuration ........................................................................................................................ 14
Logging In for the First Time ....................................................................................................................... 14
Registering Your Controller ........................................................................................................................ 14
Configuring the IP Address ......................................................................................................................... 15
Temporarily Defaulting the IP Address ....................................................................................................... 15
Defaulting a Controller ................................................................................................................................ 16
Door Access Control ............................................................................................................ 17
Wiegand Reader Connection ..................................................................................................................... 17
Multiplex Wiegand Reader Connection ...................................................................................................... 18
RS-485 Reader Locations .......................................................................................................................... 18
RS-485 Reader Connection (Entry Only) ................................................................................................... 19
RS-485 Reader Connection (Entry/Exit) ..................................................................................................... 19
Door Contact Connection ........................................................................................................................... 20

SY-SIX-CTRL-DIN | Synergis IX Web Enabled DIN Rail Controller | Installation Manual
Last Updated September 2018 4
Lock Output Connection ............................................................................................................................. 21
Programming the Onboard Reader ............................................................................................................ 22
Inputs ..................................................................................................................................... 23
Resistor Value Options ............................................................................................................................... 24
Trouble Inputs ............................................................................................................................................. 25
Outputs .................................................................................................................................. 27
Bell/Siren Output ........................................................................................................................................ 27
Relay Outputs ............................................................................................................................................. 28
Reader Outputs .......................................................................................................................................... 28
LED Indicators ...................................................................................................................... 29
Power Indicator ........................................................................................................................................... 29
Status Indicator ........................................................................................................................................... 29
Fault Indicator ............................................................................................................................................. 29
Ethernet Link Indicator ................................................................................................................................ 29
Modem Indicator ......................................................................................................................................... 30
Reader Data Indicators ............................................................................................................................... 30
Bell Indicator ............................................................................................................................................... 30
Relay Indicators .......................................................................................................................................... 30
Input Indicators ........................................................................................................................................... 31
Mechanical Diagram ............................................................................................................. 32
Mechanical Layout ................................................................................................................ 33
Technical Specifications ...................................................................................................... 34
Current and Validation Example ................................................................................................................. 35
New Zealand and Australia .................................................................................................. 36
European Standards ............................................................................................................. 37
FCC Compliance Statements ............................................................................................... 39
Industry Canada Statement ................................................................................................. 42

SY-SIX-CTRL-DIN | Synergis IX Web Enabled DIN Rail Controller | Installation Manual
Last Updated September 2018 5
Introduction
The Synergis IX Web Enabled DIN Rail Controller is the central processing unit of the Genetec Synergis IX
System. It communicates with all system modules, stores all configuration and transaction information,
processes all system communication, and reports alarms and system activity to a monitoring station or remote
computer.
Flexible module network architecture allows large numbers of modules to be connected to the RS-485 Module
Network. Up to 250 modules can be connected to the Synergis System in any combination to the network up
to a distance of 900M (3000ft). Communication beyond this distance requires the use of a RS-485 Network
Extender
The current features of the Controller include:
Internal industry-standard 10/100 Ethernet
32 Bit advanced RISC processor with 2Gb total memory
8 high security monitored inputs
NIST Certified AES 128, 192 and 256 Bit Encryption

SY-SIX-CTRL-DIN | Synergis IX Web Enabled DIN Rail Controller | Installation Manual
Last Updated September 2018 6
Installation Requirements
This equipment is to be installed in accordance with:
The product installation instructions
The National Electrical Code, ANSI/NFPA 70
The Canadian Electrical Code, Part I, CSA C22.1
The Local Authority Having Jurisdiction (AHJ)

SY-SIX-CTRL-DIN | Synergis IX Web Enabled DIN Rail Controller | Installation Manual
Last Updated September 2018 7
Grounding Requirements
An effectively grounded product is one that is intentionally connected to earth ground through a ground
connection or connections of sufficiently low impedance and having sufficient current-carrying capacity to
prevent elevated voltages which may result in undue hazard to connected equipment or to persons.
Grounding of the Synergis system is done for three basic reasons:
1. Safety
2. Component protection
3. Noise reduction
Safety Grounding
The object of safety grounding is to ensure that all metalwork is at the same ground (or earth) potential.
Impedance between the Synergis system and the building scheme ground must conform to the requirements
of national and local industrial safety regulations or electrical codes. These will vary based on country, type of
distribution system, and other factors. The integrity of all ground connections should be checked periodically.
General safety dictates that all metal parts are connected to earth with separate copper wire or wires of the
appropriate gauge.
Earth Ground Connection
The DIN Rail enclosure and the DIN Rail modules must be grounded to a suitable single-point earth ground
connection in the installation. A minimum 14AWG solid copper wire (or thicker, in accordance to local
authorities) shall be used from the Synergis system's earth connection points.
The DIN Rail enclosure includes an earth ground single-point link connection via the metallic enclosure. This
single-point link is the Synergis system's earth ground. All modules that have earth ground connections and
that are installed in the same enclosure shall be connected to this single point. A single-point earth ground
connection avoids the creation of ground loops in the system and provides a single reference point to earth
ground.

SY-SIX-CTRL-DIN | Synergis IX Web Enabled DIN Rail Controller | Installation Manual
Last Updated September 2018 8
Controller
Earth Ground
Link connection
Dialer’s Earth
Ground Connection
PRT-RDM2-DIN
PRT-PSU-DIN
V-
Power Supply
Reader Expander
PRT-PSU-DIN
Input Expander
Output Expander
V-
AC Mains Wiring
DIN Rail Ground Connections (one or more cabinets installed in the same room)
DIN Rail Enclosure
Module Network
(RS-485 N+, N-, NA and NB)
Additional DIN Rail Enclosure (s)
DIN Rail Ground Connections (multiple cabinets in different rooms, sectors, or buildings)
DIN Rail Enclosure
Controller
Earth Ground
Link connection
Dialer’s Earth
Ground Connection
Module Network (RS-485 N+, N-, NA and NB)
PRT-RDM2-DIN
PRT-PSU-DIN
V-
Power Supply
Reader Expander
PRT-PSU-DIN
Input Expander
Output Expander
PRT-RDM2-DIN
Input Expander
PRT-PSU-DIN
Input Expander
Input Expander
V-
DIN Rail Enclosure DIN Rail Enclosure
Sector or Building #1 Sector or Building #2 Sector or Building #3
Note that the DIN Rail enclosure earth terminal is connected to the power supply V- terminal.
There must be only one single earth grounding point per system.

SY-SIX-CTRL-DIN | Synergis IX Web Enabled DIN Rail Controller | Installation Manual
Last Updated September 2018 9
Mounting
The Controller is designed to mount on standard DIN Rail either in dedicated DIN cabinets or generic DIN Rail
mounting strip.
When installing the Controller ensure that there is adequate clearance around all sides of the device and that
air flow to the vents of the unit is not restricted. It is recommended to install the Controller in a location that will
facilitate easy access for wiring. It is also recommended that the Controller is installed in electrical rooms,
communication equipment rooms, closets or in an accessible area of the ceiling.
1. Hook the lower tabs under the bottom edge of the DIN Rail.
2. Push the Controller against the DIN Rail mount until the upper tab clips over the upper rail.
Removal
The Controller can be removed from the DIN Rail mount using the following steps:
1. Insert a flat blade screwdriver into the hole in the tab at the top of the Controller.
2. Lever the tab up and rotate the unit off the DIN Rail mount.

SY-SIX-CTRL-DIN | Synergis IX Web Enabled DIN Rail Controller | Installation Manual
Last Updated September 2018 10
Connections
Power Requirements
Power is supplied to the Controller by a 12V DC power supply connected to the N+ and N- terminals. The
Controller does not contain internal regulation or isolation and any clean 12V DC supply is suitable for this
purpose. In a small installation this same power supply can be used to supply the module network as well,
provided the maximum load of the power supply is not exceeded.
Warning: Termination of wiring to the Controller while power is applied or the battery is connected
may cause serious damage to the unit and will VOID ALL WARRANTIES OR GUARANTEES.
Power the unit only after all wiring, configuration and jumper settings are completed.
A battery backup must be connected to the module network to provide a monitored supply. The battery plays
an important role in power conditioning and provides a continuous source of power in the event of a power
outage.
B+
B- LN
NAN+ N- NB
Controller Power Supply
Gel Cell Backup Batteries
NAN+ N- NB
V1+
V-
V1+ V1+ V1+ V1+ V1+
V- V- V- V- V-
To other modules
on network
Mains Input
+
-
+
-
To comply with EN 50131-1, a battery connected to a system must be monitored. If more capacity is
required, a single, larger battery must be used. Multiple batteries may be connected provided each
battery is separately monitored.
Inhaltsverzeichnis