GMI D1033D Bedienungsanleitung

D1000 Series - Intrinsically Safe Isolators ISM0102-1
D1000 Series
INSTRUCTION MANUAL
D1000 SERIES
DIN-RAIL MOUNTING
INTRINSICALLY SAFE ISOLATORS

Technology for safety
2 D1000 series - Intrinsically Safe Isolators
D1000 Intrinsically Safe Isolators
Mechanical features......................................................................................................................................................................... 3
D1000 Power Bus Enclosure........................................................................................................................................................... 4
Front Panel and PCB Removal........................................................................................................................................................ 6
Terminal Blocks Connection Data ................................................................................................................................................... 7
Mounting and Removing units from DIN-Rail .................................................................................................................................. 8
D1000 Series Configuration........................................................................................................................................................... 10
Installation of electronic equipments in cabinet ............................................................................................................................. 12
Placement of Isolators in cabinet................................................................................................................................................... 13
Heat dissipation in cabinets........................................................................................................................................................... 14
Calculation of radiant surfaces in closed cabinets......................................................................................................................... 15
Approvals and Certifications.......................................................................................................................................................... 16
Storage .......................................................................................................................................................................................... 16
Disposal......................................................................................................................................................................................... 16
Maintenance and Repair................................................................................................................................................................ 16
Index

Technology for safety 3
D1000 series - Intrinsically Safe Isolators
Mechanical features
Enclosure Characteristics
High channel density result from innovative circuit design using advanced surface mount components.
Single, dual or quad channel models.
Plug-in screw terminal blocks to secure termination up to 2.5 mm2.
Plug-in PCB can be removed for service or maintenance operations (see section “Front Panel and PCB Removing”).
High packing density
35 mm (Top Hat) DIN-Rail.
Ultra slim 4 channels 22.5 mm wide DIN-rail mounting modules.
6 mm per channel.
Up to 176 I/O channels per meter of DIN-rail.
Power Bus enclosure allows a significant reduction in cables, costs and space.
Front Panel and
Terminal Blocks tagging zone
Laser engraving on entire enclosure
to provide Intrinsic Safety parameters,
schematic diagrams, connections,
instructions
Aeration
Slots
Mounting
T35 DIN Rail according to EN50022
Dimensions
Width 22.5 mm
Depth 99.0 mm
Height 114.5 mm
Case material
PA66 - Polyamide (Nylon) 66
Blister packing size
Width 30.0 mm
Depth 120.0 mm
Height 120.0 mm
Terminals
Identification
LEDs for power,
status and fault
indication

Technology for safety
4 D1000 series - Intrinsically Safe Isolators
D1000 Power Bus Enclosure
Module Enclosure with
Power Bus Connector female Side
Module Enclosure with
Power Bus Connector male Side
Power Supply Voltage 12-24 Vdc can be applied to the module,
by connecting directly the voltage to the plug-in Terminal Block of
each module, or via the Power Bus System. The system consists
of a standard DIN-Rail and modules with Bus Connectors (female
on one side and male on the other). The maximum allowed powering
capacity is 8 Amp. It is always possible to remove modules, without
disconnecting the bus connection. When the Power Bus is used,
Supply Contacts on Terminal Blocks are omitted to avoid accidental
short circuits on the Power Bus. Cumulative Fault Alarm indication is
provided on the Bus connection. This signal is in common with the
supply and drives a remote indication, typically through a D1091S
module.
Power
Supply
DIN-Rail Anchor for terminal block
Side of the Power Bus DIN-Rail Stopper
B+ A - FLT - +
Modbus Fault
Modbus
+ - FLT A- B+
Power
Supply
Fault

Technology for safety 5
D1000 series - Intrinsically Safe Isolators
Module Enclosure with
Power Bus Male Termination Block
Plug - in terminal block male,
vertical out, for Power Bus
Plug - in terminal block male,
horizontal out, for Power Bus
Plug - in terminal block female,
horizontal out, for Power Bus
Image
Ordering Information:
Code
MCHP065
MCHP139
MOR016
MOR015
MOR017
MOR022
OPT1096
/ B
Description
DIN-Rail Anchor for terminal block side of the Power Bus
5 mm spacer for modules on DIN-Rail
DIN-Rail Stopper
Plug-in terminal block male, vertical out, for Power Bus
Plug-in terminal block male, horizontal out, for Power Bus
Plug-in terminal block female, horizontal out, for Power Bus
Kit for Bus Mounting: 2 x MOR016, 1 x MOR017,
1 x MOR022, 2 x MCHP065
Power Bus Enclosure
Power
Supply
B+ A - FLT - +
Modbus Fault

Technology for safety
6 D1000 series - Intrinsically Safe Isolators
Front Panel and PCB Removal
Slowly pull out Front Panel and PCB.
The PCB will slide on the enclosure
dedicated guides.
Front panel and PCB can be
plugged out by applying a slight
pressure on both sides using a tool.

Technology for safety 7
D1000 series - Intrinsically Safe Isolators
Terminal blocks connection data
Stripping
lenght
Grey terminal blocks
on Safe Area
Screwdriver
for Trimmers
4 x 1 mm
7 mm
Connection data
Conductor cross section solid From 0.2 mm² to 2.5 mm²
Conductor cross section stranded From 0.2 mm² to 2.5 mm²
Conductor cross section stranded, with ferrule without plastic sleeve From 0.25 mm² to 2.5 mm²
Conductor cross section stranded, with ferrule with plastic sleeve From 0.25 mm² to 2.5 mm²
Conductor cross section AWG From 24 to 12 AWG
Blue terminal blocks
On Hazardous Area

Technology for safety
8 D1000 series - Intrinsically Safe Isolators
Mounting and Removing units from DIN-Rail
Mounting
Removing
Fig. 1 Fig. 2
Fig. 3
To remove a barrier from the mounting rail, insert the blade screwdriver in the metallic part of the mounting foot and lever the spring catch open
against the side of the barrier casing (see Fig.3).
Push
To
engage
To mount Series D1000 on 35 mm DIN Rail, hook one side of the mounting foot over the lip of the rail and press down firmly on the barrier
(see Fig.1) to snap the other side of the mounting foot over the opposite rail lip (see Fig.2).
Metallic
Part
Spring
T35 DIN Rail
Screwdriver
T35 DIN Rail
T35 DIN Rail

Technology for safety 9
D1000 series - Intrinsically Safe Isolators
Fig. 5
Fig. 6
Fig. 7
T35 DIN Rail
T35 DIN Rail Dimensions (millimeters)
T35 DIN Rail
Pull and
removing
from Din-Rail

Technology for safety
10 D1000 series - Intrinsically Safe Isolators
PPC 1090 Pocket Portable Configurator
The PPC1090 is a small and handy Pocket Portable Configurator suitable to program configuration parameters of D1000 series modules like:
type of input Sensors, input and output Ranges, Burnout conditions, High/Low Alarm mode, Relay NE/ND, Alarm Trip Point, Hysteresis value and
ON/OFF Alarm delays. The Configurator is powered by the unit and can be plugged in without disconnecting the module.
Refer to specific module Instruction Manual for details on using the PPC1090
PPC 1092 Serial Adapter
The PPC1092 adapter is needed to interface the PC with D1000 Series modules for a complete configuration of Input, Output and Alarm
parameters. The package includes necessary cables and a USB to RS-232 Adapter; a CD-Rom with the SWC1090 Software is also provided.
The SWC1090 can also be downloaded from our website.
D1000 Series Configuration
The Pocket Portable Configurator type PPC1090 or PPC1092 is suitable to configure the “smart” barrier of D1000 series.
The PPC1090/PPC1092 unit is not ATEX, UL or FM approved and is only to be used in Safe Area/Non Hazardous Locations and prior to installation
of the isolator and prior to connection of any I.S. wiring. Do not use PPC1090/PPC1092 configurator in Hazardous Area/Hazardous Locations.
The PPC1090 configurator is powered by the unit (no battery power) when the telephone jack is plugged into the barrier (RJ12 6 poles connector
type with 1:1 connection). It has a 5 digit display, 4 leds and four push buttons with a menu driven configuration software and can be used in
Safe Area/Non Hazardous Locations without any certification because it plugs into the non intrinsically safe portion of circuit. The PPC1092 adapter
permits the configuration of the unit via a PC software program and acts as an interface for RS232 serial line and D1000 unit; it can be used in
Safe Area/Non Hazardous Locations without any certification because it plugs into the non intrinsically safe portion of circuit.
The main features of the converter can be easily configured, these are: type of input circuit, type of sensor, burnout operation, measuring range,
type of output and range, refer to the next section of Instruction Manual for a detailed description of configuration and menu options.
Andere Handbücher für D1033D
1
Dieses Handbuch passt für folgende Modelle
7
Inhaltsverzeichnis
Andere GMI Schalten Handbücher