8
PACKAGE GAS SPECIFICATIONS
(1) Units installed in Canada are certifed only to 4500 feet.
(2) Calculated external filter size based on air velocity of 300 ft/min. and applies to disposable filters only.
(3) Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit
breakers in accordance with the National Electrical Code and/or all local codes.
*PG15[24-37]***41AA
*PG152407041AA *PG153009041AA *PG153609041AA *PG153709041AA
COOLING COOLING CAPACITY, BTUH
CAPACITY HIGH STAGE 23,200 29,000 35,400 35,000
LOW STAGE N/A N/A 24,400 N/A
SEER / EER 15.0 / 12.0 14.5 / 12.0 15.0 / 11.0 14.5 / 12.0
HEATING BTUH INPUT (US) HIGH FIRE 69,000 92,000 92,000 92,000
CAPACITY OUTPUT (US) HIGH FIRE (Natural Gas) 55,000 73,500 73,500 73,500
OUTPUT (US) HIGH FIRE (LP) 50,000 69,000 69,000 69,000
BTUH INPUT (US) LOW FIRE 52,000 69,000 69,000 69,000
OUPUT (US) LOW FIRE (Natural) 41,500 55,000 55,000 55,000
OUTPUT (US) LOW FIRE (LP) 37,000 50,000 50,000 50,000
A.F.U.E. 80 80 80 80
RATED EXTERNAL STATIC (" w.c.) 0.50 0.50 0.50 0.50
TEMPERATURE RISE (°F) 35- 65 45- 75 45-75 45-75
PRESSURE SWITCH TRIP POINT (" w.c.) -.33" -.33" -.33" -.33"
UNIT VOLTAGE (NAMEPLATE) 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60
EL EC TRI C AL UNIT AMPS (TOTAL) 18.7 17.5 22.2 20.1
SP E CI FI C ATI ON MINIMUM CIRCUIT AMPACITY 22.1 21 26.5 24.2
MAXIMUM OVERCURRENT PROTECTION(3) 30 35 40 40
HEATING NUMBER OF BURNERS 3 4 4 4
SE C TI O N ORIFICE SIZE NATURAL 43 43 43 43
ORIFICE SIZE LP 55 55 55 55
COMPR ESSOR TYPE Scroll Scr oll Sc roll Scroll
RATED LOAD AMPS 13.5 14.1 16.7 16.7
LOCKED ROTOR AMPS 58.3 73 82 79
CONDENSER HORSEPOWER 1/6 1/4 1/4 1/4
FAN MOTOR RPM 815 830 1075 830
FULL LOAD AMPS 1.10 1.5 1.4 1.5
LOCKED ROTOR AMPS 1.7 3.0 2.9 3.0
CONDENSER BLADE DIAMETER (INCHES) 22 22 22 22
FAN NUMBER OF BLADES 3 3 3 3
CFM 2400 2700 2700 2700
CONDENSER FAC E AREA - SQ. FT. 12.3 12.3 12.3 12.3
COIL NUMBER OF ROWS 1 2 1 2
FINS PER INCH 22 16 22 16
EVAPORAT OR HORSEPOWER - NO. OF SPEEDS 1/2 - X-13 1/2 - X-13 1/2 - X-13 1/2 - X-13
BLOWER FULL LOAD AMPS 4.1 1.86 4.1 1.86
MOTOR LOCKED ROTOR AMPS N/A N/A N/A N/A
MOTOR SPEED TAP - COOLING T4 T3, T4 T3, T4 T3, T4
RPM / AMPS 724 / 1.21 960 / 3.06 640 / 0.98
960 / 3 .06 960 / 3.06
EVAPORAT OR DIAMETER X WIDTH (INCHES) 10 x 8 10 x 9 10 x 9 10 x 9
BLOWER RATED SCFM COOLING 845 1050 800 / 1225 1050
MAX EXTERNAL STATIC PRESS ("w.c.) 0.5 0.5 0.5 0.5
EVAPORAT OR FAC E AREA - SQ. FT. 4.33 4.33 4.33 4.33
COIL NUMBER OF ROWS 2 3 4 4
FINS PER INCH 14 14 14 14
FILTER SIZE - SQ. FT.(2) 2.7 4.2 4.2 4.2
DRAIN SIZE (INCHES) 3/4 3/4 3/4 3/4
HEATING PRIMARY LIMIT SETTING (°F) 160 160 160 160
LIMITS AUXILIARY LIMIT SETTING (°F) 150 150 150 150
ROLLOUT LIMIT SETTING (°F) 300 300 300 300
GENERAL EXPANSION DEVICE TXV 0.065 TXV TXV
INFORMATION REFRIGERANT CHARGE R-410A (Oz.) 81 102 99 112
POWER SUPPLY ENTRANCE SIZE (INCHES) 1 1/8 1 1/8 1 1/8 1 1/8
LOW VOLTAGE ENTRANCE SIZE (INCHES) 7/8 7/8 7/8 7/8
SHIPPING WEIGHT LBS. 439 475 480 480
OPERATING WEIGHT LBS. 417 453 458 458