HELVAR 458/CTR8 Bedienungsanleitung

Helvar | Data is subject to change without notice. www.helvar.com i
Installation and User Guide
458/CTR8 8-Channel Ballast Controller Module

www.helvar.com
ii Helvar 458/CTR8 8-Channel Ballast Controller Module: Installation and User Guide
Introduction 1
Installation 2
1. Attach the module to a chassis 2
2. Connect power and load cables to module sockets 3
3. Make control connections 4
4. Replace the chassis cover 4
5. Power on the unit 4
Load types 5
Control Panel 5
Control Panel functions 5
Control Panel LCD Display 6
Control Panel Keypad 6
Adjusting channel and output levels
with the Control Panel Keypad 7
Navigating the menu with the Control Panel Keypad 7
Physical selection 8
Menu options 9
Main menu 9
Menu options details 10
Error messages 15
Dimensions (mm) 15
Technical specifications 16
Contents
Section Page

1Helvar | Data is subject to change without notice.
Introduction
The 458/CTR8 is an eight-channel digital ballast controller module capable of controlling 0–10V, 1–10V,
DSI®, DALI broadcast or PWM loads. It has both a DALI and an SDIM/DMX interface, and therefore can be fully
integrated into a DIGIDIM or an Imagine router system. It can also be used on the TouchPanel or on standalone DALI or
DIGIDIM systems.
Note: DALI and SDIM/DMX must not be connected simultaneously.
Chassis modules
The 458/CTR8 module is attached to the 458M1, 458M2 or 458M3 chassis. The chassis modules are supplied with
control module by-pass connectors, and can be fully installed and wired prior to fitting of the control module(s). Thus,
all electrical installation, testing and powering up of the lighting circuits can be carried out prior to the fitting of the
control modules, which prevents possible damage to the control modules due to circuit overload or faults or to the use
of high-voltage insulation testing equipment.
LCD display and keypad
The front of the module is equipped with an LCD display and keypad to set basic configuration parameters and provide
basic control of channel and output levels. For information, see ‘Control Panel’ on page5.
Channels and load protection
The module has eight high-inrush relays, rated at 16 A per channel.
Note: The correct chassis load protection must be chosen to ensure that the required channel ratings are achieved, but
not exceeded.
DSI®is a registered trademark of Tridonic GmbH.
Attachment
knob
LCD Display
Heat sink
Grille
Keypad
Module mains
supply connector
Attachment
knob
Load
connection
sockets
Terminal
block
provided
with
458Mx Chassis
Override,
SDIM/DMX
connections
DALI
connections
Terminal
block
provided
Control
output
connections
Terminal
blocks
provided
Control
Panel

2 Helvar 458/CTR8 8-Channel Ballast Controller Module: Installation and User Guide
Installation
Loosen
knobs
Blanking
plate
Unscrew and remove the blanking plate(s) from the chassis.
Note 1: 458M1: 1 blanking plate
458M2: 2 blanking plates
458M3: 3 blanking plates
Note 2: The diagrams on this page show the 458M1/4S10 Chassis.
Covers and knockouts are removed from the 458M2 and 458M3 in a
similarway.
1.2 Remove chassis blanking plates
For details, refer to the 458Mx Chassis Installation Guide.
1.1 Remove chassis cover
Partially unscrew the two knobs on the module to reveal the pins.
1.3 Loosen attachment knobs
Attach the module to the chassis by slotting the pins of the module to the
mounting bracket.
1.4 Slot module pins into mounting bracket
Screw the knobs to the mounting bracket to secure the module.
1.5 Tighten knobs
1. Attach the module to a chassis
Mounting, environmental and clearance requirements
Mounting
• Attach the 458/CTR8 to a 458M1, 458M2, or 458M3 chassis that is mounted vertically on a flat surface.
Environment
• The ambient temperature must be between 0°C and +40°C.
• Air humidity must be between 0% and 90% (noncondensing).
• The area must be adequately ventilated.
• Do NOT install this product in a damp location.
Clearance
• For effective ventilation, ensure that there is adequate space around the combined chassis and module(s): 50 mm
above, below and on both sides. Refer to the mounting dimensions and clearance diagrams in the 458Mx Chassis
Installation Guide.
• When a Helvar control module (e.g. 458/CTR8) is attached, the grilles must NOT be obstructed.
For further information, refer to the Helvar 458Mx Chassis Installation Guide.
Warning: Before attaching the module and making any connections, make sure that the mains supply is isolated.
Important: The module may be controlled by either DALI or SDIM/DMX, but DALI and SDIM/DMX must not be connected
simultaneously.

3Helvar | Data is subject to change without notice.
Connect the mains control supply as shown below. The load output cables from the 458M chassis will
be plugged into the chassis bypass terminals. Unplug the cables, and then connect them to the module channel terminals.
Note: The diagram on this page shows the 458M1 chassis. Cable connection is similar for the 458M2 and 458M3.
2. Connect power and load cables to module sockets
1
2
3
4
5
6
7
8
TO OUTPUT 6
TO CH6 MCB
CTRL
1
2
3
4
5
6
7
8
OUTPUTS
MCB BLOCK
TO CH1 MCB
TO OUTPUT 1
N
L
TO OUTPUT 2
TO CH2 MCB
TO OUTPUT 4
TO CH4 MCB
TO OUTPUT 5
TO CH5 MCB
TO OUTPUT 7
TO CH7 MCB
TO OUTPUT 8
TO CH8 MCB
TO OUTPUT 3
TO CH3 MCB
SDIM/DMX
cable loom
Bypass
terminals
Output
control
terminals
SDIM/
DMX
1
0 V
2
5
7
0 V
0 V
6
8
3
0 V
4
DALI
DA+
DA–
OVR
0 V
A
0 V
SCN
B
TERM
Override
Connect
external
switch
foroverride
operation
Link for
termination
Override and SDIM/DMX

4 Helvar 458/CTR8 8-Channel Ballast Controller Module: Installation and User Guide
3.1 DALI connections
If connecting to a DIGIDIM system, use the DA+ and DA– terminals of the DALI connector.
3.2 Override connections
If you want to provide output level override functionality, wire a switch between the ‘0 V’ and ‘OVR’ terminals of the SDIM
or DMX connector. Switch closure sets the light level of all output channels to the override level.
3.3 SDIM and DMX connections
If connecting to a Helvar Imagine system, plug in the connector of the SDIM/DMX cable loom to the SDIM/DMX
terminals. This is attached to the DIN-rail inside the chassis.
If the module is at the end of the SDIM/DMX cable, wire a link between the ‘TERM’ and ‘B’ connections of the SDIM/DMX
terminals to enable the cable termination.
Note:
The module can be used for 0–10 V Source,
1–10V Sink, PWM+, PWM– (reverse), DALI
Broadcast, and DSI®Control.
Output
control
terminals 1–10 V Ballast
DALI / DSI®/ PWM Ballast
3.4 Output control connections
Connect the required output control connections to the output control terminals of the module. The following diagram
shows an example.
4. Replace the chassis cover
Replace the chassis cover, using the original screws.
5. Power on the unit
Power up the module by switching on the MCBs.
The Control Panel LCD Display will show the Main Display Screen. For details, see ’Main Display Screen’ on page6.
3. Make control connections
Refer to the connection diagrams on the previous page.
Ensure that all the necessary control connections have been made correctly and securely.
Warning: Ensure segregation between mains cabling and other connections.
DALI and 1–10 V ballast connections must be considered as potentially live.

5Helvar | Data is subject to change without notice.
Load types
Each channel of the 458/CTR8 control module can be configured to operate in any of the following
modes:
• 0–10 V → source 20 mA
• 1–10 V → sink 100 mA
• DSI®(Digital Signal Interface) → source 100 mA
• PWM (Pulse Width Modulation)→ source 100 mA
• DALI broadcast → source 100 mA
Control Panel
Control Panel functions
The Control Panel is used to view and adjust:
• Relay and output channel levels
• Various relay and output parameters
SDIM connection
Example: to Helvar 920 Routers, or to Helvar TouchPanel.
Adjust the following parameters with the Control Panel:
• Channel pairing
• SDIM addresses
Other parameters can be set using Designer software.
DMX connection
Example: to Helvar 920 Routers, or to third party lighting
desk.
Adjust the following parameters with the Control Panel:
• DMX addresses
• Channel pairing
• Output mode
• Minimum fade time
• Override level
• Switch-on level
Other parameters can be set using Designer software.
DALI connection
Example: to Helvar 920 Routers.
Adjust the following parameters with the Control Panel:
• Channel pairing
• Minimum fade time
• Override level
Other parameters can be set using Designer software.
Control Panel
DALI standalone connection with
Toolbox software
Adjust these parameters with the Control Panel:
• Channel pairing
• Minimum fade time
• Output mode
• Override level
Other parameters can be set using Toolbox software.
DALI standalone connection
This allows basic out-of-box scene recall, modify and
store from DALI control panels. Other settings can be
changed with the module Control Panel.
Note: If SDIM or DMX is connected and you change
lighting levels or recall scenes on the
Control Panel, then, after a short period of time,
the levels revert to those being sent by the SDIM/
DMX master.
Keypad
LCD Display

6 Helvar 458/CTR8 8-Channel Ballast Controller Module: Installation and User Guide
Control Panel LCD Display
SDIM/DMX Activity
and DALI Power/
Activity Indicator
Channel(s)/
output(s) level %
Channel numbers
Channel
Levels
Indicators
Control Panel Keypad
Use the Control Panel Keypad to:
• Set output channel levels.
• Navigate the system menus to adjust module settings.
Channel(s)/output(s) level %
The percentage shown is the level of the currently selected channel(s) or output(s).
‘ALL’ is displayed here if all channels or outputs are selected simultaneously but are set to different levels.
Main Display Screen
The Main Display Screen appears:
• When the 458/CTR8 is powered on.
• After 60 seconds of inactivity on the Control Panel.
• After exiting the Control Panel options.
SDIM/DMX Activity and DALI Power/Activity indicator
This indicator in the top left-hand corner of the Control Panel LCD Display indicates SDIM/DMX activity or DALI power/
activity:
• For SDIM/DMX it is normally off, and flashes on intermittently for activity.
• If DALI power is on, then the indicator is on. It flashes to indicate DALI activity.

7Helvar | Data is subject to change without notice.
Adjusting channel and output levels
with the Control Panel Keypad
1. (From the Main Display Screen):
Press either RIGHT or LEFT to access the relay and output (option)
channel levels.
2. Step left or right through channels/outputs.
The selected channel(s) or output(s) are shown by a flashing bar or
‘o’ (to indicate 0% light level).
3.
Adjust lighting level percentage (%) for the selected channel(s).
4.
Return to the Main Display Screen.
Follow these steps to adjust channel and output levels.
Navigating the menu with the Control Panel Keypad
Follow these steps to access and navigate the menus.
1. (From the Main Display Screen):
Press UP or DOWN to access the menu options.
2.
Scroll through main options.
3.
Select an option (access option screen).
4.
Adjust parameters.
5.
Step among different parameters in options screens.
6. Return to previous menu.
Return to the Main Display Screen (from the main menu).

8 Helvar 458/CTR8 8-Channel Ballast Controller Module: Installation and User Guide
Physical selection
Physical selection mode is activated using a Helvar remote control unit. It allows you to group loads
and controls together without the use of programming software. For details, refer to the equipment instructions.
Follow these steps to identify a piece of equipment using physical selection mode.
1.
–Put the piece of equipment (e.g. router, sensor, etc.) into ‘physical
selection mode’ (refer to the manufacturer’s instructions).
2. (From the Main Display Screen):
Press either RIGHT or LEFT to access the relay and output channel
levels.
3.
Step left or right through channels to select the channel that you
want to use for physical selection.
4.
Press UP or DOWN to physical select the channel.
5.
– Repeat steps 3 and 4 for each channel, as necessary.
6.
–Once identified, end ‘Physical selection mode’ for the piece(s) of
equipment (refer to the manufacturer’s instructions).
Inhaltsverzeichnis
Andere HELVAR Steuereinheit Handbücher
Beliebte Steuereinheit Handbücher anderer Marken

Festo
Festo Compact Performance CP-FB6-E Stücklistenhandbuch

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Bedienungsanleitung

JS Automation
JS Automation MPC3034A Bedienungsanleitung

JAUDT
JAUDT SW GII 6406 Series Kurzanleitung

Spektrum
Spektrum Air Module System Bedienungsanleitung

BOC Edwards
BOC Edwards Q Series Bedienungsanleitung