HELVAR OB-1501 Bedienungsanleitung

Default Settings
Installation Guide
1. Features and Connections
OB-1501 iDim Orbit
The OB-1501 iDim Orbit with five movement detectors is a standalone, flush-mounted sensor that provides easy
installation and configuration of lighting control applications.
This document describes how to connect the sensor and how to mount it into a ceiling. For information on how to
configure it, see the iDim Orbit App Guide.
DALI 2
N
L2
L1’
DALI 1
MANUAL SWITCH
Connections
Manual switch
interface. (For details,
see section 3.3 on
page5.)
N: Neutral
: Earth
L2: Live in
L1: Switched live
Out of the box, the sensor has the following default settings for profiles 1 and 2:
• DALI channel 1 output: DALI broadcast
• DALI channel 2 output: Mimics DALI channel 1
• Relay output: Mimics DALI channel 1
• Detection mode: Presence
• On level: 100 %
• Occupancy time-out: 20 min
• Power save light level: 30 %
• Transition time-out: 5 min
• Bright-out: Disabled
• Daylight harvesting: Disabled
Status LED
PIR movement detectors
Light sensor
1
Helvar | Data is subject to change without notice. www.helvar.com

• Scheduler: Disabled
• Exit delay: 2 min
• Switch input 1: Common
• Switch input 2: Channel 1 switch control
• Switch input 3: Channel 1 switch control
• Switch input 4: Relay on/off
• Switch input 5: Channel 2 switch control
• Switch input 6: Channel 2 switch control
You can modify these settings with the iDim Orbit app. For information, see the iDim Orbit App Guide.
2. Coverage
2.8 m
⌀15 m
2.8 m
6.7 m
100°
Presence Detection Coverage
Daylight Harvesting Coverage
140°
Due to the nature of PIR technology, when someone walks directly towards the centre of the sensor, the detection
distance from the sensor is reduced. The point at which the sensor will detect movement is affected by site-specific
conditions, such as speed of movement, clothing and air temperature. Hence it is not possible to guarantee the point at
which the sensor will trigger the loads when someone walks directly towards the centre of the sensor.
When someone walks ‘across’ the detection area, the sensor range is greater than when someone walks towards the
centre of the sensor. Therefore, in applications where occupants are free to move in all directions, such as classrooms
and offices, the detection range shown in the preceding figure can be used when planning sensor positions.
2
Helvar OB-1501 iDim Orbit: Installation Guide

To mount the OB-1501 iDim Orbit flush into a ceiling, complete the following steps:
1. Mount the mains connector as shown in section 3.1,‘Mounting the mains connector’, below on this page.
2. Mount the required DALI connectors as shown in section 3.2,‘Mounting the DALI connectors’, on page4.
3. If required, mount the input connector for the manual switch as shown in section 3.3,‘Mounting the input connector
for the manual switch’, on page5.
4. Plug the mains connector and the DALI connector(s) into the sensor.
5. If required, plug the input connector for the manual switch into the sensor.
6. Mount the sensor into the ceiling as shown in section 3.4,‘Mounting the sensor into the ceiling’, on page5.
7. Power the sensor up.
8. Download the iDim Orbit app to your iOS device (iPod Touch, iPhone or iPad).
9. Connect the iDim Orbit app to the required OB-1501 iDim Orbit via Bluetooth®Smart™.
10. Configure the sensor using the app. The default passcode is 00000. For information, see the iDim Orbit App Guide.
3. Installation
Installation Notes
3.1. Mounting the mains connector
• Position the sensor so that the occupants of the room are normally inside the detection zone.
• Do not fix the sensor to an unstable or vibrating surface.
• Do not install the sensor within 1 m of any lighting, forced air heating, or ventilation equipment.
• The external supply must be protected. External protection must not exceed 16 A Type C MCB.
Solid cables:
Push the stripped cable until it hits
the backstop.
Stranded cables:
a. Push down the required clamp
with a 2.5mm screwdriver.
b. Insert the stripped cable until it
hits the backstop.
c. Remove the screwdriver to close
the clamp.
Pull the prelatched strain-relief
housing over the cable.
Strip 8mm of the live, neutral and
earth cable insulation.
8 mm
1. 2. 3.
N: Neutral
: Earth
2 | L: Live in
1 | L‘: Switched line
3
Helvar | Data is subject to change without notice. www.helvar.com

Latch the strain-relief housing on
the plug/socket. Note the ‘TOP’
inscription.
Snap together the upper and
bottom parts of the strain-relief
housing.
Tighten the strain-relief screw with
a 2.5 mm screwdriver.
4.
5. 6.
3.2. Mounting the DALI connectors
Latch the wired connector onto the
base of the strain-relief housing.
Strip 8mm of each of the cable
insulation.
8 mm
Push down the strain-relief clamp
with your finger.
Push down the strain-relief
clamp with a 2.5 mm screwdriver
alternately on both sides.
Latch the top of the strain-relief
housing.
Solid cables:
Push the stripped cable until it hits
the backstop.
Stranded cables:
a. Push down the required clamp
with a 2.5mm screwdriver.
b. Insert the stripped cable until it
hits the backstop.
c. Remove the screwdriver to close
the clamp.
1. 2. 3.
4. 5. 6.
4
Helvar OB-1501 iDim Orbit: Installation Guide

1 2
54
3
6
a. Push down the required clamp
with a 2.5 mm screwdriver.
b. Insert the stripped conductor
until it hits the backstop.
3.4. Mounting the sensor into the ceiling
Push the sensor
into the ceiling void
Then centre it about the hole
as required
Strip 8mm of each of the cable
insulation.
8 mm
3.3. Mounting the input connector for the manual switch
Input function (selectable in the app)
Switch input*Single-pole switch Double-pole switch†
1 Common Common
2 DALI 1 switch control‡DALI 1 on/raise
3 DALI 1 switch control‡DALI 1 off/lower
4 Relay on/off (Single-pole switch only)
5 DALI 2 switch control‡DALI 2 on/raise
6 DALI 2 switch control‡DALI 2 off/lower
*Switch inputs are functional extra-low voltage (FELV).
†Two-position, centre-biased retractive switch.
‡Switch control enables on/off and dimming control from a single-
pole retractive switch.
1. 2.
c. Remove the screwdriver to close
the clamp.
1. 2. 3.
⌀83 mm – 86 mm
5
Helvar | Data is subject to change without notice. www.helvar.com

4. Wiring Schematic
DA+
DA-
L
N
DA+
DA–
L
N
DA+
DA–
L
N
DA+
DA–
L
N
L
N
DA+
DA-
L
N
DA+
DA–
L
N
DA+
DA–
L
N
DA+
DA–
1
2
3
4
5
6
L
N
L1
L2
N
DALI DRIVER
DALI DRIVER
DALI DRIVER
DALI 2
MAINS
iDIM ORBIT
CONNECTIONS
NONDIMMABLE
DRIVER
NONDIMMABLE
DRIVER
MAX. 16 A
SWITCHED LIVE
(Earth not required)
DALI DRIVER
DALI DRIVER
DALI DRIVER
DALI 1
MAX. 40 mA
(20 DRIVERS)
TO OTHER
LUMINAIRES
SWITCH CONTROL
OF DALI 2 USING
SINGLE-POLE
RETRACTIVE
SWITCHES
ON/RAISE & OFF/LOWER
CONTROL OF DALI 1
USING A DOUBLE-POLE
RETRACTIVE SWITCH
SWITCH CONTROL
OF RELAY USING
A SINGLE-POLE
RETRACTIVE SWITCH
Either physical
wiring arrangement
can be used.
5 or 6
SWITCH INPUTS
TO OTHER
LUMINAIRES
MAX. 40 mA
(20 DRIVERS)
You can use either single-pole or double-pole switches to control DALI channels. This is configured
via the iDim Orbit App. The default is for ‘switch control’ using single-pole switches. For details, see
the iDim Orbit App Guide.
As an example, the following diagram shows:
• A single point of control (switch inputs 2 and 3) using a double-pole switch for DALI channel 1
• Two points of control (switch inputs 5 and 6) for DALI channel 2 using single-pole retractive switches connected in
parallel
• A single point of control using a single pole switch on the relay channel (switch input 4)
6
Helvar OB-1501 iDim Orbit: Installation Guide

Helvar Ltd
Hawley Mill
Hawley Road
DARTFORD
DA2 7SY
UNITED KINGDOM
www.helvar.com
Doc. 7860354, issue 1, 2016-08-03
Dimensions (mm)
5. Technical Data
Connections
Mains: 4-pole removable connector
block with strain relief
Cable diameter: 9mm – 13mm
mains rated
Cable section: 0.5mm² – 4mm²
solid; 0.5mm² – 2.5mm²
stranded
Power
Mains supply: 100 VAC – 240 VAC (nominal)
85 VAC – 264 VAC (absolute)
50 Hz – 60 Hz
Power
consumption:
Nominal: 0.9 W
Maximum: 2.5W
DALI power: 2 × 40 mA DALI power supply
2 × 2-pole removable connector
blocks with strain relief
Cable diameter: 3.8mm –
8.2mm mains rated
Cable section: 0.25mm²
– 1.5mm² solid; 0.25mm² –
1.0mm² stranded
External protection: Max. 16 A Type C MCB
Relay loads: Limited by external protective
device.
Switch inputs: 5 × retractive (momentary)
switch plus common input
Switch inputs are functional
extra-low voltage (FELV).
Cable section: 0.08mm²
– 1.5mm² solid; 0.08mm² –
1.0mm² stranded.
Max. length: 50m.
Communications: DALI broadcast
Mechanical data
Mounting hole
diameter:
83mm – 86mm
Recommended
clearance depth:
115mm plus cable bending
radius
Material (casing) Flame-retardant ABS
Colour: White RAL 9003
Weight: 261 g
IP code: IP40
Operating conditions
Ambient
temperature:
0 °C to +50 °C
Note: The temperature difference
between the detection target and
the background must be at least
4 °C.
Relative humidity: Max. 90 %, noncondensing
Storage
temperature:
–10 °C to + 70 °C
Conformity and standards
EMC: EN 301489-1
EN 55015
EN 61547
Safety: IEC 60669-2-5
Environment: Complies with WEEE and RoHS
directives.
FCC: Contains FCC ID: T7VPAN17.
⌀93
33
48
115
⌀
102
⌀
82,8
7
Helvar | Data is subject to change without notice. www.helvar.com
Dieses Handbuch passt für folgende Modelle
1
Inhaltsverzeichnis
Andere HELVAR Sicherheitssensor Handbücher

HELVAR
HELVAR digidim 314 Bedienungsanleitung

HELVAR
HELVAR 314 Tilting Bedienungsanleitung

HELVAR
HELVAR Digidim 313 Bedienungsanleitung

HELVAR
HELVAR 311 Bedienungsanleitung

HELVAR
HELVAR Digidim 317 Bedienungsanleitung

HELVAR
HELVAR 318 Bedienungsanleitung

HELVAR
HELVAR digidim 319 Bedienungsanleitung

HELVAR
HELVAR digidim 313 Bedienungsanleitung

HELVAR
HELVAR digidim 317 Bedienungsanleitung

HELVAR
HELVAR Digidim 311 Bedienungsanleitung