ABOUT THESE INSTRUCTIONS
The EGIP system must be installed in accordance with these installation instructions. Failure to do so
may result in damage to the unit, injury or even death.
Please ensure all pages are read prior to attempting installation or calling our technical team. Ta.
Siting the main panel.
Firstly choose a suitable mounting position for the control unit, mount the unit away from sources of
extreme heat, ensure the panel is located in a position where mechanical damage is unlikely and
where it can be easily accessed for use and maintenance.
Fix the panel using the marked enclosure holes only, take care not to damage the internal wiring or
PCB of the unit when drilling.
Field wiring
Output terminals to the gas valve carry mains voltage (230v ac nominal). APS, fire, Estop, auxiliary,
gas pressure switch and early warning interlock wiring is 24v DC.
The current edition of the IEE Wiring Regulations should be strictly adhered to, wiring and connections
should be made by a suitably qualified electrician or competent person.
Intelligas recommends the use of FP200 or similar type of wiring for the mains, fixed wiring
installation.
Any CO2 detectors should be wired in a flexible, small core cable. Cat 5 data cable or telephone cable
is not suitable. Burglar alarm cable is preferable.
Please follow the first fix wiring schedule set out below
From spur to panel - 2 core + earth 1.5mm2
From panel to gas valve - 2 core + earth 1.5mm2
Air pressure switch or fan interlock device - 2 core 1.0mm2
Emergency stop switches - 2 core 1.0mm2
Gas pressure switch (if fitted) - 2 core 1.0mm2
Gas detectors - 6 core alarm cable per detector (only 3 cores used)
Do not make or break connecons to the pcb while the mains is connected