Johnson Controls Zone Terminal Montageanleitung

© 1992 Johnson Controls, Inc. 1
Part No. 24-7766-9
Installation Sheet
Issue Date 0392
lntroduction Page 3
●
Application Details 3
●
Theory of Operation 3
●
Downloading Options 7
Installation Procedures 13
●
Tools Needed 13
●
Physical Dimensions 13
●
Environmental Information 13
●
Connecting the Zone Terminal 14
●
Installing the Inserts 14
●
Positioning the ZT in the Controller Tower 15
●
Physical Installation of Wall Mountings and Bases 16
●
Connecting the ZT 18
Troubleshooting Procedures 23
●
Troubleshooting Chart 23
●
Internal Diagnostic Errors 24
Zone Terminal

2 Zone Terminal

Zone Terminal 3
lntroduction
The Zone Terminal is a hand-held or wall-mounted person/machine
interface for the Metasys Application Specific Controllers. It has the
versatility to connect to a controller in several ways, and allows the user to
monitor or adjust set points and time scheduling within a specific zone.
The Zone Terminal is used to monitor or adjust set points and for time
scheduling of occupied, warmup/cooldown, or shutdown zone conditions.
It connects to:
●a VAV/UNT through a TE-6100 Zone Sensor
●an AHU directly
●an AHU through a Function Module Kit or a Relay Kit
●an AHU or UNT through an M100C Actuator
The Zone Terminal is designed as an easy-to-use hands-on device with
which you can:
●quickly identify an alarm and its location
●monitor and adjust up to 18 analog points
●monitor 18 binary points
●extend a daily time schedule using Occupied Extend
●add or modify daily, holiday, and temporary time schedules
For specific Theory of Operation details, refer to the Zone Terminal
section of the HVAC PRO User’s Manual.
The ZT uses a liquid crystal display (LCD) divided into three sections
from top to bottom. Each display includes:
●five, seven-segment digits
●decimal points
●colon
To the left of the display are 18 cursors (●) and triangles (▲), 6 per
display. The cursors indicate current position in the respective display.
When flashing, the triangles indicate an alarm condition in the
corresponding analog points.
Application Details
Theory of
Operation
Displays

4 Zone Terminal
The right side of the ZT display includes 18 pairs of binary indicators—a
bar ( | ) for On, and a circle (❍) for Off. These symbols flash when the
respective binary point is in alarm.
Five LED’s located in the bottom panel include four green Mode
Indicators and one red Alarm Indicator. The Alarm Indicator LED flashes
when any analog or binary point is in alarm.
Figure 1: The Zone Terminal
Refer to Figure 1 to locate each of the seven ZT keys.
Key Description
Display Key 1, 2, 3 Moves the cursor through insert items
Operating Mode
Selector
Moves the LED to the desired operating mode:
Monitor, Adjust, Time Schedule, Password
(↑
↑↑
↑) or (↓
↓↓
↓)Adjust Up or Down changes the numbers in the
displays
Enter Commits adjustments
ENTER
FAN STATUS
ECON ENABLE
TEMP OCC
WARMUP MODE
CLG LOCKOUT
HTG LOCKOUT
A/C LIM OPN
CHECK FAN
CHECK CLG
CHECK HTG
CHECK ECON
DIRTY FILTR
FAN
COOL STG #1
COOL STG #2
HEAT STG #1
HEAT STG #2
OCCUPIED
OUTDOOR AIR
ZONE TEMP
STATIC STEPT
MIXED AIR LL SP
COOL SET PT
HEAT SET PT
WARMCOOL ADJ
ACT CLG SP
ACT HTG SP
DISCH TEMP
CLG % ON
HTG % ON
ECON % OPEN
MIN POS % OPN
ROOFTOP ZTU
INSERT 12
ON OFF
Display
Key
1
Mode
Selector
Panel
Mode
Selector
Key
2
MAP1RT4
Display Cursor Dot On/Off Status
3
Operating Mode Indicator
Up/Down Arrow Keys
Door
Display Item List Alarm Triangle
ALARM
NIGHT HTG STPT
NIGHT CLG STPT
Display Area 11
Display Area 21
Display Area 31
Alarm Light
MONITOR
ADJUST
TIME SCHEDULE
PASSWORD
Keys

Zone Terminal 5
●AHU, UNT, or VAV controller with 24VAC transformer
●AS-ZTU100 Zone Terminal comes with a 6-pin telephone-style coiled
cord. Also included are four inserts: one Time Schedule Overlay
(remove the paper backing), and three clear inserts with set point labels
(remove protective plastic backing).
Note: The UNT/VAV inserts match common configurations right out of
the box. The ZT matches the most-used AHU configuration:
Mixed Air Single Path.
●TE-6100 Zone Sensor
●AS-FMK100 Function Module Kit
●AS-RLY100 Relay Kit or M100C Actuator
●AS-ZTUWMB Wall Mount Base
●AS-ENC100 Enclosure
●AS-ZTUUMB Utility Mounting Base With Screws
●AS-ZTUBAG Carrying Case
●AS-CBLPRO-1
●IBM compatible computer or laptop
●WS-SWHPRO-3 HVAC PRO Release 3
●clear overhead transparency film for the customized inserts
●AS-CBLCON-0 or AS-AHU101 and AS-FMK100
!
CAUTION: The ZT must be plugged into a 6-pin telephone-type
jack. Plugging the ZT into an 8-pin jack destroys the
8-pin receptacle and prevents the ZT from powering
up.
Note: AS-CBLPRO-1must be used to download the ZT.
AS-CBLPRO-0is not compatible for downloading.
ZT configuration and downloading are done with a software program
called ZT PRO which is part of the HVAC PRO software, Rev. 3. This
easy-to-use tool configures, commissions, and downloads the ZT’s data
base. The program runs on an IBM® PC/XT/AT, PS/2, or any 100%
compatible computer. Figure 2 is an overview of the ZT configuration and
downloading process. Refer to the HVAC PRO User’s Manual for specific
information on configuration and downloading the Zone Terminal.
Required Hardware
for Operation
Optional Hardware
for Operation
Required for
Downloading
Software

6 Zone Terminal
Figure 2: Overview—Configuring and Downloading the ZT
DWNLDZT
Select Zone Terminal From Main HVAC PRO Menu
Start HVAC PRO
Define ZT Configuration Load File
which must be executed from ZT.
●
Press F2 and select up to three display files.
●
Press F2 and select Weekly and Holiday Schedules
●
Press F2 and select display file which corresponds to appropriate controller.
●
Select hardware parameters.
●
Specify Password Access Numbers.
Select Download ZT
●
Unplug cable from ZT AS-CBLCON-0. Reset switch to normal.
●
Select the desired load file to download..
●
Attach cable to ZT AS-CBLCON-0 and AS-CABLEPRO-1 connection.
●
Set switch at AS-CBLCON-0 to Download.
Exit HVAC PRO
●
Select the communication port.
Select Configure ZT Files
●
Define display files for single or multiple controllers.
●
Define weekly schedules.
●
Define holiday schedules.
press any key to return to Main ZT PRO Menu. (
PC
is displayed
at ZT during download; resets when download is complete.)
●
When
Download Complete
message is displayed on the screen,
●
Print the Insert and photocopy onto an overhead transparency.

Zone Terminal 7
!
CAUTION: Any changes in the configuration of the AHU and
UNT/VAV must be up-dated in the Zone Terminal.
Failure to download the ZT after configuration
changes to the AHU and UNT/VAV prevents access
to the ZT Operating Modes.
The following section presents options available for hardware connections
necessary to complete the downloading process. The section includes:
●Using AS-CBLCON-0 or
●Downloading Without an ASC Controller (using AS-CBLCON-0) or
●Job site Downloading with a UNT or VAV (using AS-CBLCON-0) or
●Job site Downloading Without AS-CBLCON-0
Use AS-CBLCON-0 for multiple connections of related equipment. The
switch on the AS-CBLCON-0 must be in the download position. The red
LED is indication of 24 VAC power. The green LED shows Zone Bus
transmissions from the controller. If this LED is off, the Zone Bus wire is
open. If this LED is ON solid, the Zone Bus is shorted to COMMON.
CBLCON2
Switch must be
in Download
position. 88
666
Figure 3: AS-CBLCON-0
Downloading
Options
Using AS-CBLCON-0

8 Zone Terminal
Although the program reminds you to put the AS-CBLCON-0 switch in
the correct position, if the switch is in the wrong position, or if the wrong
CBLPRO is used, downloading does not occur. You must use AS-
CBLPRO-1. The following error prompt appears on the screen.
ZT PRO - Version 01.00
Building Object File to Download
ZT Establishing Communication
ZT error (18) -- Invalid or No response from ZT
ZT Download Failed, Strike 1 - Trying Again
ZT Establishing Communication
ZT error (18) -- Invalid or No response from ZT
ZT Download Failed, Strike 2 - Trying Again
ZT Establishing Communication
ZT error (18) -- Invalid or No response from ZT
ZT Download Failed, Strike 3 - You’re Out
Return Switch on CBLCON to Normal Position
Press any key to Continue
<Esc>Cancel <F7>View

Zone Terminal 9
To download a ZT for a VAV/UNT through the TE-6100 Zone Sensor
(Figure 4), use a AS-CBLCON-0, AS-CBLPRO-1, and a laptop.
Notes: It is assumed that 24 VAC power has been applied to the
controller.
The AS-CBLCON-0 switch must be in the download position.
Option 1: Job Site
Downloading With
UNT/VAV Using
CBLCON-0
BINARYINANALOG INPUTS BINARYOUTPUTS ANA OU T
ANALOG INPU TS
ANALOGI NPUTS
COMMON
BI NA RY COM
PWR
IN
24V
AC
BIN ARY OUTPUT
24VACTO LOADS
AS - UNT 101 - 0
DWN
L
LAPTOP
AS-CBLCON-0
UNT or VAV
TE-6100
88
666
ZONE TERMINAL
AS-CBLPRO-1
Figure 4: Job Site Downloading With UNT/VAV Using AS-CBLCON-0

10 Zone Terminal
Download the ZT without an AS-CBLCON-0 by using an AHU and an
FMK (Figure 5). When downloading through an AHU, the AHU102
Logic Board assembly must be removed before the download process
begins. It is assumed that 24 VAC power has been accessed through a
transformer or controller.
Figure 5: Job Site Downloading Without AS-CBLCON-0
Option 2: Job Site
Downloading
Without
AS-CBLCON-0
ZONE TERMINAL
LAPTOP
DWNLD4
Note: Zone Bus wiring from
AHU must be connected
to the FMK. XFR100 or any
24VAC transformer
Open Door
24 VAC
AHU
24 VAC, COM
+ Zone Bus
AS-CBLPRO-1
Note: AHU102 Logic Board
must be removed to download.
Inhaltsverzeichnis
Andere Johnson Controls Aufnahmegeräte Handbücher

Johnson Controls
Johnson Controls Frick QUANTUM LX Bedienungsanleitung

Johnson Controls
Johnson Controls Metasys Integrator MIG3500 Series Bedienungsanleitung

Johnson Controls
Johnson Controls LDATFL2S01 Bedienungsanleitung

Johnson Controls
Johnson Controls S300 Series Montageanleitung

Johnson Controls
Johnson Controls R45 Series Service-Handbuch
Beliebte Aufnahmegeräte Handbücher anderer Marken

Strymon
Strymon NIGHTSKY Bedienungsanleitung

Mitsubishi Electric
Mitsubishi Electric 16CH DIGITAL RECORDER DX-TL5000U Bedienungsanleitung

Tews Technologies
Tews Technologies TPMC465 Bedienungsanleitung

Honeywell
Honeywell Excel 50 Bedienungsanleitung

SeaLevel
SeaLevel COMM+8.LPCI Bedienungsanleitung

Arturia
Arturia AUDIOFUSE STUDIO Bedienungsanleitung