JUMO DELOS SI Bedienungsanleitung

JUMO DELOS SI
Electronic Pressure Switch with Display
B 40.5052.0
Operating Manual
2009-06-15/00526948


Contents
1 Typographical conventions ...................................................... 5
1.1 Warning signs ..............................................................................................5
1.2 Note signs ....................................................................................................5
2 Description ................................................................................ 6
2.1 General .........................................................................................................6
3 Identifying the instrument version ........................................... 7
3.1 Nameplate ....................................................................................................7
3.2 Block diagram ..............................................................................................7
3.3 Type description ..........................................................................................8
3.4 Accessories ................................................................................................10
4 Electrical connection .............................................................. 11
4.1 Installation instructions ..............................................................................11
4.2 Color assignment of M12 x 1 round plug ..................................................11
4.3 Terminal assignment for output 470 ..........................................................12
4.4 Terminal assignment for output 471 ..........................................................12
4.5 Terminal assignment for outputs 475, 476, and 477 .................................13
5 Mounting .................................................................................. 14
5.1 General information ....................................................................................14
5.2 Dimensions of electronic pressure switches .............................................16
5.3 Dimensions of process connections, not front-flush .................................17
5.4 Dimensions of process connections, front-flush .......................................18
6 Operation ................................................................................. 21
6.1 Controls ......................................................................................................21
6.2 LC display ..................................................................................................21
6.3 Levels .........................................................................................................22
6.4 Parameter ...................................................................................................23

Contents
7 Commissioning ....................................................................... 26
7.1 Getting started ...........................................................................................26
7.2 Unlocking the instrument (code entry) .......................................................27
7.3 Cancel operation ........................................................................................28
7.4 Selecting the unit of the measured value (Uni.P) .......................................28
7.5 Setting the zero point (offset) (Off.P) ..........................................................31
7.6 Setting the filter time constant (damping) (DamP) .....................................32
7.7 Setting the output signal (S.TyP) ................................................................32
7.8 Setting scaling ............................................................................................33
7.9 Setting the error signal (S.Err) ....................................................................36
7.10 Setting the switching function (B.Fct) ........................................................37
7.11 Setting the switching point (B.SP) .............................................................39
7.12 Setting the reset point (B.RSP) ..................................................................40
7.13 Setting the switching difference (hysteresis) (B.HYS) ................................40
7.14 Setting the switching delay (B.DLY) ...........................................................41
7.15 Setting the display alignment (D.Dir) ..........................................................41
7.16 Setting the display unit (D.Uni) ...................................................................42
7.17 Displaying the version of the operating device software (SW.Di) ..............43
7.18 Displaying the version of the signal stage software (SW.Si) ......................43
8 Calibration ............................................................................... 44
8.1 Setting the zero point (offset) .....................................................................44
9 Setup program ........................................................................ 45
9.1 Function .....................................................................................................45
9.2 Start the setup program .............................................................................46
10 Eliminating errors and faults .................................................. 48
10.1 Possible errors ...........................................................................................48
11 Instrument description ........................................................... 49
11.1 Technical data ..........................................................................................49

5
1 Typographical conventions
1.1 Warning signs
1.2 Note signs
Danger
This symbol is used when there may be danger to personnel if the
instructions are ignored or not followed correctly!
Caution
This symbol is used when there may be damage to equipment or data if the
instructions are ignored or not followed correctly!
Caution
This symbol is used where special care is required when handling components
liable to damage through electrostatic discharge.
Note
This symbol is used to draw your special attention to a remark.
abc1Footnote
Footnotes are remarks that refer to specific points in the text. Footnotes
consist of two parts:
Marking in the text and the footnote text.
The markers in the text are arranged as sequential superscript numbers.
✱Action instruction
This symbol indicates that an action to be performed is described.
The individual steps are marked by this asterisk.
Example:
✱Loosen Phillips-head screws.

6
2 Description
2.1 General
❏Depending on its design, the instrument measures relative or absolute
pressure in
liquid and gaseous media.
❏The pressure is displayed digitally.
❏Depending on the design, the following outputs are available:
- 1 PNP switching output
- 2 PNP switching outputs
- 1 PNP switching output + 1 analog output 4 ... 20 mA 1
- 1 PNP switching output + 1 analog output 0 ... 20 mA 1
- 1 PNP switching output + 1 analog output 0 ... 10 V 1
❏The instrument is also available in a design for use at elevated medium
temperatures.
❏The instrument can be adjusted directly on site or can be configured via PC
with a setup program.
(1)
The protection type specified for the device (See section 11.1 "Technical
data", page 49) can only be achieved with the control opening (1) closed.
1The output is freely configurable.

7
3 Identifying the instrument version
3.1 Nameplate
on the
pressure switch
3.2 Block diagram
1optional
DELOS SI
0...250 mbar
DC 12...30 V
4...20 mA/OC: 250 mA
F.-Nr.: 001234567801008350123
}
Made in Germany
www.jumo.net
405052/000
TN 12345678
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(1)
(2)
(3)
(4)
Type
Part number
Measuring range
Power supply voltage
(5)
(6)
(7)
Output signal
Manufacturing number
Date of manufacture
(year and calendar week)
Type 405052
Pressure
Power supply
12 30 V DC?
Switching output 2
Open collector
Interface
Setup program
Display
2 x 4 characters, 2 colors
Analog output
0 (4) 20 mA oder 0 10 V??
Switching output 1
Open collector
Rotary encoder
To operate: turn and press
(1)
(1)

3 Identifying the instrument version
8
3.3 Type description
(1) Basic type
405052 JUMO DELOS SI
Electronic Pressure Switch with Display
(2) Basic type extension
000 None
004 For elevated medium temperatures up to 200°C 1
999 Special design
(3) Nominal (rated) measuring range
Measuring range - pressure
452 0 ... 400 mbar relative pressure
454 0 ... 1 bar relative pressure
457 0 ... 4 bar relative pressure
459 0 ... 10 bar relative pressure
461 0 ... 25 bar relative pressure
463 0 ... 60 bar relative pressure
Measuring range - vacuum
447 -400 ... 400 mbar relative pressure
449 -1 ...1 bar relative pressure
481 -1 ... 3 bar relative pressure
483 -1 ... 9 bar relative pressure
485 -1 ... 24 bar relative pressure
Measuring range absolute pressure
486 0 ... 400 mbar absolute pressure
488 0 ... 1 bar absolute pressure
491 0 ... 4 bar absolute pressure
493 0 ... 10 bar absolute pressure
495 0 ... 25 bar absolute pressure
506 0 ... 60 bar absolute pressure
(4) Output
470 1 x PNP switching output
471 2 x PNP switching output
475 1 x PNP switching output + analog output 4 ... 20 mA,
three wires 2
476 1 x PNP switching output + analog output 0 ... 20 mA,
three wires 2
477 1 x PNP switching output + analog output 0 ... 10 V,
three wires 2
1Front-flush only for process connection.
2Factory setting - the output is freely configurable.

9
3 Identifying the instrument version
(5) Process connection
Not front-flush
504 G 1/2
511 1/4-18 NPT
521 G 1/4 to DIN 3852 T11
523 G 1/2 to DIN 3852 T11
998 Suitable for connecting to pressure measuring instrument
Front-flush
571 G 3/4
575 G 3/4 seal positioned in front
576 G1 seal positioned in front
603 Tapered adapter with groove nut, to DIN11 851, DN204
604 Tapered adapter with groove nut, to DIN11 851, DN254
606 Tapered adapter with groove nut, to DIN11 851, DN404
607 Tapered adapter with groove nut, to DIN11 851, DN504
612 Clamp to DIN 32 676, DN204
613 Clamp to DIN 32 676, DN254
616 Clamp to DIN 32 676, DN504
623 Small flange connection4
652 Tank connection with groove union nut4, DN25
997 JUMO PEKA (EHEDG-certified)3
998 Suitable for connecting to pressure measuring instrument
(6) Process connection material
20 Stainless steel 316L
(7) Electrical connection
36 Round plug M 12 x 1
(8) Measuring system filling medium
01 FDA-compliant oil
99 Special filling medium
(9) Extra codes
000 None
591 Throttle in pressure channel
624 Free of oil and grease
691 Cast version
(1) (2) (3) (4) (5) (6) (7) (8) (9)
Order code /------/
Sample order 405052 / 000 - 459 - 471 - 504 - 20 - 36 - 1 / 000
3For matching process connection adapter see data sheet 40.9711
4For measuring ranges up to 25 bar only

3 Identifying the instrument version
10
3.4 Accessories
Sales No. Designation
40/00404585 4-pin cable connector (straight) M 12 x 1 with 2-m PVC cable
40/00409334 4-pin angle box M 12 x1 with 2-m PVC cable
40/00522384 Setup program
40/00507861 Connecting cable (only required for programming with the
setup program)
70/00456352 PC interface line including USB/TTL converter and
adapter (USB connecting cable) 1
1Please order a connecting cable as well.