OPERATING INSTRUCTIONS
1. Identify the wall outlet or fixture for which the breaker must
be determined.
2. Safely check that the outlet or fixture is live.
3. Plug in the transmitter. Its LED will light if it is receiving power.
4. Move to the breaker panel with the receiver.
5. Turn on the receiver by pressing, but not holding, the power button.
You will hear a beep and see its LED lit.
6. Position the receiver perpendicularly on the breakers in the panel
with the power button pointing up.
7. Slowly scan all breakers in the panel once. Ignore any beeps
or indications, as the receiver is learning the panel.
8. Scan all breakers a second time. This time, the receiver will beep
and illuminate the green arrow only at the correct breaker.
9. Power off the receiver by pressing and holding the power button.
Return to the outlet or fixture and remove the transmitter.
NOTE: All appliances or equipment on the circuit being tested should be
unplugged to help reduce the possibility of erroneous readings.
OPTIONAL ACCESSORIES
(Cat. No. 69411)
GENERAL SPECIFICATIONS
• Operating Voltage: 90 – 120V AC
• Operating Frequency: 50 – 60Hz
• Tracking Distance: Up to 1000 ft. (305 m)
• Operating Temperature: 32°F – 104°F (0°C – 40°C)
• Relative Humidity: 50%
• Altitude: < 6562 ft. (2000 m)
• Environment: For indoor use only
• Power: 9 volt alkaline battery
• Auto Power Off: Approximately 4 minutes
• Transmitter Dimensions: 2.8" x 1.9" x 1.2" (7.11 x 4.83 x 3.04 cm)
• Receiver Dimensions: 6.0" x 2.0" x 0.9" (15.24 x 5.08 x 2.29 cm)
• Transmitter Weight: 1.6 oz. (45 g)
• Receiver Weight: 3.2 oz. (91 g)
• Sensitivity: Indication at 0.16" (4 mm) distance from a wire
carrying 120V AC.
• Safety Rating: UL listed
WARNINGS
To ensure safe operation and service of the tester, follow these instructions.
Failure to observe these warnings can result in severe injury or death.
• Understand the risks of working around live voltage.
• Turn off power before inspecting, applying, or removing
the transmitter (when using the optional 'Leads Adapter').
• Exercise extreme caution around live, bare wires, especially
in an open breaker panel.
• Consult with an experienced electrician when necessary.
• Other equipment or devices attached to the circuit being tested could
interfere with the tester. Clear the circuit before testing.
A
Light Fixture Adapter:
Screw this adapter into an empty light socket.
Make sure the fixture is live. Plug in the
transmitter and follow the instructions
starting at step 4.
B
Leads Adapter:
Carefully attach leads to the correct wires.
Plug in transmitter to adapter. Follow the
instructions starting at step 4.
Exercise extreme caution around live wires.
Digital Circuit Breaker
Finder
ET300
UP
Micro-Processor
Controlled
7