Connections
1. Connect the main air supply to the 1/8" NPT
Port “M”.
2. Provide a supply of clean, dry, 20-30 psig
(38–207 kPa) control air.
3. Connect the input signal , start-point, pressure to
Port “S”
4. Connect the branch Port “B” to the actuator.
Adjustments and Calibration
1. Apply 20 psi to Port “M”
2. Apply the desired start-point pressure to Port “S’
3. Turn the start-point adjustment dial until the
actuator begins to move.
Example:
A start-point of 4 psi with a 5 psi span spring will
yield an operating range of 4–9 psi.
Maintenance
No routine maintenance is required.
Each component is designed and manufactured for
reliability and performance. Careful installation and