Level 2 Commercial Charging Station
Perfect for facility managers of office, multi-residential,
retail, education, hospitality, and other business
locations. LEDVANCE PHASE EV Level 2 Commercial
Charging Station is offered in wall mounted units or a
free-standing pedestal where two units can be
mounted side-by-side or back-to-back. With powerful
software integration from AmpUp, LEDVANCE PHASE
EV combines performance and value to deliver fast
charging at an affordable price.
WARNING
−WARNING: TO AVOID FIRE, SHOCK OR DEATH, TURN OFF POWER at the circuit breaker or fuse and test
that the power is off before wiring! Do not remove circuit protective devices or any other component until power
is turned off.
−WARNING: TO AVOID FIRE, SHOCK OR DEATH, carefully read the charging instructions in your vehicle’s
manual before charging and heed the following warnings:
−DO NOT put your fingers into the vehicle connector.
−DO NOT use this product if the flexible power cord is frayed, has broken insulation or any other signs of damage.
−DO NOT use this product if the enclosure or the EV connector is broken, cracked, open, or shows any other
indication of damage.
−WHEN USING THIS DEVICE AROUND CHILDREN, supervise closely.
−TO REDUCE THE RISK OF FIRE, CONNECT ONLY TO A CIRCUIT PROVIDED WITH BELOW AMPERES
maximum branch circuit over-current protection in accordance with the National Electrical Code NFPA 70®, and
the Canadian Electrical Code, Part I, C22.1.
Models
Circuit Breaker Rating
EVC48ALVL2C1, EVC48ALVL2C1WH,
EVC48ALVL2C1GY
60A
−DO NOT operate charger in temperatures outside its operating range of -22°F to 122°F (-30°C to 50°C)
Please Read All Instructions Before Attempting Installation

Page 2of 22
Contents
INTRODUCTION
Safety Precautions
3
Compliance
3
What’s Included
4
Tools You Will Need
4
Specifications
5
Unit Parts
6
INSTALLATION
Get Started
7
Installing the Mounting Plate
8
Preparing the Charger
9
Mounting the Charger
10
Electrical Wiring
11
Current Adjustment
11
Closing the Charger
12
Installing the Holster and Cable Hanger
13
How to Setup WiFi Connection
14
OPERATION
Status Light Bar
16
Charger Screens
16
Charging
19
Troubleshooting
19
Warranty
21

Page 3of 22
Safety Precautions
IMPORTANT:
READ CAREFULLY BEFORE INSTALLING THE CHARGER. RETAIN FOR FUTURE REFERENCE.
GENERAL:
Upon receipt of the charger, thoroughly inspect for any freight damage which should be brought to the
attention of the delivery carrier.
Compliance
FCC Statement:
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant
to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can
be determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
•Reorient or relocate the receiving antenna.
•Increase the separation between the equipment and receiver.
•Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
•Consult the dealer or an experienced radio/TV technician for help.
Industry Canada (IC) Statement:
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the
following two conditions: (1) this device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts
de licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas produire
de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le
brouillage est susceptible d'en compromettre le fonctionnement.

Page 4of 22
MPE (Maximum Permissible Exposure) Requirements
To satisfy FCC / IC RF exposure requirements, a separation distance of 20 cm or more should be
maintained between the antenna of this device and persons during device operation.
To ensure compliance, operations at closer than this distance is not recommended.
Les antennes installées doivent être situées de façon à ce que la population ne puisse y être exposée à
une distance de moins de 20 cm. Installer les antennes de façon à ce que le personnel ne puisse
approcher à 20 cm ou moins de la position centrale de l’ antenne.
La FCC des États-Unis stipule que cet appareil doit être en tout temps éloigné d’au moins 20 cm des
personnes pendant son fonctionnement.
Changes or modifications not expressly approved by the party responsible for compliance could void the
user's authority to operate the equipment.
What’s Included
- 1 x charger
- 1 x cable hanger
- 1 x charge coupler holster
- 1 x M25 cable strain relief (cable gland)
- 1 x M32 cable strain relief (cable gland)
- 8 x M5 wall anchors w/screws (for holster & hanger)
- 3 x M6 wall anchors w/screws (for charger wall mount)
- 1 x T20 25mm tamper-proof Torx® bit, 1/4in hex
Tools You Will Need
- 1/4 in hex bit driver
- Phillips screwdriver (#2)
- Wire cutter & stripper
- Crimping pliers
- Drill or hammer drill

Page 5of 22
Specifications
FEATURES AND FUNCTIONS
Charging mode
Level 2
Vehicle connection
SAE J1772 (Type 1 connector)
Cable length
25ft
Display
4.3in LCD w/charging status light bar
COMMUNICATION
Interfaces
4G, WiFi, Ethernet
SIM card
Super SIM card (shipped installed)
User authentication
RFID, QR Code, App
Back-end protocol
OCPP 1.6, upgradeable to OCPP 2.0.1
Software upgrade
Over-the-air (OTA)
Software provider
AmpUp
ELECTRICAL DESIGN
Power supply voltage
AC level 2, 208/240V
Rated frequency
60Hz
Rated current
Up to 48A –16/32/40/48 amp selectable
Power output
Max 11.5kW
Input connection
Hardwired –terminal lug screws
Primary wire gauge
8AWG
Power requirements
208V (single phase), 240V (single or split phase)
Metering
Revenue grade embedded metering ± 1% accuracy
Ground fault protection
Standard
Over voltage protection
Standard –6kV surge suppression
Over current protection
Standard
GENERAL DESIGN
Environmental rating
NEMA 4 enclosure (UL50E), IK08 impact protection
Ingress protection
IP66
Dimensions (H x W x D)
16.34” x 9.45” x 5.59” (415mm x 240mm x 117mm)
Weight
19.8-22 lbs. (9-10kg)
Operating temp
-22°F to 122°F (-30°C to 50°C)
Storage temp
-40°F to 167°F (-40°C to 75°C)
Cooling
Natural cooling –fanless
Paint
UV protection
CERTIFICATIONS AND STANDARDS
Standards
ETL (UL2594, UL2231, UL1998, UL991)
EMC
FCC Part 15 Class B
ENERGY STAR (EVSE v1.1)
Yes
California Type Evaluation Program (CTEP)
In progress
Warranty
5-Year warranty

Page 6of 22
Unit Parts
1. Fuse
2. Debug serial port
3. Download interface
4. 485 interface
5. CAN interface
6. USB interface
7. Coin cell battery
8. Dip switch control
9. TF card holder
10. Ethernet interface (RJ45)
11. PF pulse interface
12. SIM card interface
13. Power switch
14. Input L1
15. Input L2
16. Input Ground
17. Cable Ground
18. Reserved interface
19. CP interface
20. RS485 interface A
21. RS485 interface B
22. Cable L2
23. Cable L1

Page 7of 22
Get Started
Step 1: Subscribe to a Software Charging Plan
The site host, property manager, or the owner must go to https://payments.ampup.io to subscribe to a
software charging plan. A software charging plan is required to access the Community Manager portal
where you will be able to customize various features that are included with your plan. We recommend
completing this step before or on installation day, prior to activation for a smooth progression. You will
receive login credentials via email for AmpUp Community Manager (https://community.ampup.io/login)
after the charger is installed and activated.
Step 2: Site & Charger Registration
Before or on installation day, register chargers with the AmpUp system,
so you can easily bring them online during installation. Scan the QR
code on the Installer Quick Start Guide or go to
https://register.ampup.io.
Step 3: Install the Charger
Follow the steps below to install and power up your charger(s). Then
confirm connectivity for each unit.
Step 4: Activate the Charger
This charger has a pre-installed super SIM card that will
automatically detect and connect to the nearest cellular network
once it is connected to power. On mobile or web, simply open the
registration email that you received from AmpUp titled “EV Charger
Registration Complete” and tap on “Start Verification”. Scan the
“Scan to Charge” QR code on the charger to complete the verification process. Call AmpUp at 833-692-
6787 to confirm activation.
AmpUp will reach out to the site-host (customer / charger operator) for onboarding to manage their
charger and handle support requests and questions within the next 30 minutes to an hour. You will also
get login credentials for the AmpUp Community Manager.
Your charger(s) can be installed and operational within the same day if you follow the steps above. The
site-host must subscribe to a charging plan before or on installation day.
Still have questions? The AmpUp team is ready to help. Call 833-692-6787.

Page 8of 22
Installing the Mounting Plate
1. Remove the 2 screws –one on each side of the charger to detach the wall mounting plate from the
charger.
2. Place the wall mounting plate against the wall as a template as shown in the diagram below and mark
the 3 mounting holes. (Suggested height from the ground to the bottom holes is approximately 45.28
inches.)
3. Drill the 3 holes with an appropriate sized bit and secure the wall mounting plate using the included
M6 wall anchors and screws.
If installing with a pedestal, please
see separate Pedestal
Installation Instructions.
MIN
MAX

Page 9of 22
Preparing the Charger
1. Remove the cover frame from the front of the charger by unscrewing the 2 screws on top and 1 screw
from the bottom of the charger.
2. Once the 3 screws are removed, carefully lift the cover outward and up to detach the cover frame.
3. Remove the 6 screws to take off the access panel cover.
For Rear Wiring
Remove the rear plug(s) by loosening the hex nut in a counterclockwise direction. Then use the same plug to
cover the hole at the bottom of the charger. Use the included cable strain relief to run the wiring to the charger.
For Bottom Wiring
Use the included cable strain relief to run your wiring up from the bottom of the charger.

Page 10 of 22
Mounting the Charger
1. Align the charger to the wall mounting plate and hang it as shown in the illustration below.
2. Secure the charger to the wall mounting plate with the 2 original screws.
For rear wiring installation, use the
included cable strain relief and feed the
power supply wires through the rear port
with enough length to connect the wires to
the terminals.
Strain relief must be installed for IP
rating.