Outdoor Installation.
2
Therma V R32 Installation.
•Prepare a strong and level base.
•Place on 3 anti vibration feet, & anchor to base.
•Ensure the unit is 300mm from the wall.
•The flow & return connections are 1” male.
•Fit flexi hoses, full bore isolation valves, on the back of the unit.
•Recommend - Additional 400 micron “Y” strainer, external
•Use a through wall insulation kit, this allows for thermal insulation within the wall.
•All pipework to be 28mm copper or 32mm multi layer composite pipe.
•Allow for condensate to feed into a soakaway, tray or soil stack.
•Recommend: Magnetic Cleaner & Flow Setter.
•Water volume:- 25L for single fan unit, 50L for double fan unit(Buffer Tank)