MARLO MR M Series Bedienungsanleitung

MR 150M–1050M
SINGLE –SYSTEM 4
MX-III CONTROLLER
COMMERCIAL WATER CONDITIONERS
INSTALLATION, OPERATION,
AND MAINTENANCE MANUAL
MODEL NO:
SERIAL NO:
DATE INSTALLED:
DEALER:
COMPLETE FOR FUTURE REFERENCE:
Marlo Incorporated
2227 South Street
P.O. Box 044170
Racine, WI 53404-7003
www.Marlo-Inc.com
A2170381 8-313 R3
FOR MODELS MANUFACTURED
FROM OCTOBER 2017

MR 150M–1050M SINGLE – MXIII CONTROLLER
2
IMPORTANT PLEASE READ:
• Warranty of this product extends to manufacturing defects.
• The information, specications and illustrations in this manual are based on the latest information available at the time of printing.
The manufacturer reserves the right to make changes at any time without notice.
• This product should be installed by a plumbing professional on potable water systems only.
• This product must be installed in compliance with all local and state and municipal plumbing and electrical codes. Permits may be required at
the time of installation.
• If operating pressure exceeds 100 psi a pressure reducing valve must be installed. If operating pressure drops below 30 psi a booster
pump must be installed.
• Do not install the unit where temperatures may drop below 32°F or rise above 100°F.
• A prelter should be used on installations in which free solids are present.
• A constant voltage of 120V/60Hz (unless otherwise specied) must be supplied to the controller to maintain proper function.
• Union or ange ttings are recommended at the control valve’s inlet, outlet, and drain connections
• If distance of drain line is over a 10 ft. vertical or 25 ft. horizontal run, increase drain line one pipe size over that provided on the control valve.
• Do not make a direct connection to the drain. Provide an air gap of at least four times the diameter of the pipe to conform to sanitation codes
and to permit observation of the ow.
PLEASE CIRCLE AND/OR FILL IN THE APPROPRIATE DATA FOR FUTURE REFERENCE:
Softener Model: MR _____________
System Size: Single/Twin/Triple/Quad
Meter Size: ________________
Conguration: Timeclock/Twin Alt/Parallel/Progressive
Unit Capacity: ________________ Grains
Feed Water Hardness: ________________ Grains
Treated Water: ________________ Gallons/Liters
BW/Regen Time ________________ AM/PM or OFF
Additional Notes: _______________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________
_____________________________________________________________________________________________

MR 150M–1050M SINGLE – MXIII CONTROLLER
3
TABLE OF CONTENTS
SYSTEM INFORMATION
Product Warranty...........................................................................................................................................................1
General Arrangement Drawings ...................................................................................................................................2
Dimension Width ...........................................................................................................................................................3
Specication Table ........................................................................................................................................................4
Wiring Diagram..............................................................................................................................................................5
Tubing Diagrams ...........................................................................................................................................................6
INSTALLATION
General Installation........................................................................................................................................................9
Piping Installation ..........................................................................................................................................................9
Resin & Gravel Loading ..............................................................................................................................................10
Brine Tank Installation ................................................................................................................................................ 11
OPERATION
Start-Up Instructions ...................................................................................................................................................12
Volume Remaining/Batch Calculation .........................................................................................................................13
General Softener Operation ........................................................................................................................................14
Flow Diagrams.............................................................................................................................................................15
Brine Maker Operation ................................................................................................................................................16
Features of the MX III Controller .................................................................................................................................17
User Mode Programming Flow Chart..........................................................................................................................18
Network Communication Cables and Connections .....................................................................................................22
Controller Display Screen Examples...........................................................................................................................23
Programming Parameters ...........................................................................................................................................24
Master Mode Programming Flow Chart.......................................................................................................................25
Diagnostic Mode Programming Flow Chart.................................................................................................................35
MAINTENANCE
MX III Replacement Parts............................................................................................................................................38
Replacement Valves....................................................................................................................................................39
Aquamatic Valve Repair Kits .......................................................................................................................................40
2536 Flow Sensor........................................................................................................................................................41
Brine Tank Assemblies ...............................................................................................................................................42
Error Codes ................................................................................................................................................................44
Troubleshooting...........................................................................................................................................................45

MR 150M–1050M SINGLE – MXIII CONTROLLER
1
COMMERCIAL AND INDUSTRIAL PRODUCT WARRANTY
Marlo Incorporated warrants all water treatment products manufactured and/or distributed by it to be free from defects
in materials and workmanship for a period of one (1) year from installation or 18 months from the date of shipment
whichever comes rst. Fiberglass pressure vessels are warranted against defects in materials and workmanship for a
period of ve (5) years from the date of shipment.
If during that period any products shall be proven to the Marlo Incorporated’s satisfaction to be defective, those
products will be replaced FOB factory or the price refunded at the Marlo Incorporated’s option.
Marlo Incorporated’s obligations for non-performance, defects, or any damage caused by its products or their use,
and buyer’s exclusive remedy therefore, shall be limited to product replacement or refund and shall be conditioned
upon Marlo Incorporated’s receiving written notice together with a demand for such replacement or refund.
The foregoing warranty is exclusive and in lieu of all other expressed or implied warranty (except of title)
including but not limited to implied warranty of merchantability and tness for particular purpose.
Marlo Incorporated will not be subject to and disclaims the following:
1. Any other obligations or liabilities arising out of breach of contract or out of warranty.
2. Any obligations whatsoever arising from tort claims (including negligence and strict liability) or arising under other
theories of law with respect to products sold or services rendered by Marlo Incorporated or any undertakings, acts,
or omissions relating thereto.
3. All consequential, incidental, and contingent damages.
Labor charges, charge backs or handling charges are excluded from Marlo Incorporated’s warranty provisions.
COMMERCIAL AND INDUSTRIAL WATER SOFTENER GUARANTEE
Under normal operating conditions:
1. The softener euent shall be zero soft as determined by a soap test.
2. The loss of softening resin through attrition during the rst three (3) years shall not exceed 3% per year.
3. The softening resin shall not be washed out of the system during backwash.
4. The color and turbidity of the softener euent shall not be greater than the incoming water.

MR 150M–1050M SINGLE – MXIII CONTROLLER
SYSTEM INFORMATION
2
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
DATE
FRAC.
DRN.
APP'D.
DEC.
DRAWING NO.
SCALE
FILE ID.
SHEET
REV.
OF
MR SINGLE WATER SOFTENER SYSTEM NXT
GENERAL ARRANGEMENT
MR SINGLE NXT
11
Anthony
5/25/2011
REVISIONS
NO. BY REMARKS
INCORPORATED
DATE
BRINE TANK
BT DIAMETER
MINERAL TANK
MT DIAMETER
INLET=_________
OUTLET=_______
PIPE SIZES
INJECTOR=_______
DRAIN=__________
H=_______
MT=_______
DIMENSION TABLE
BT=_______
MR-______________
W=_______
L=_______
H
L
W
INLET
30-100 PSIG
OUTLET
BY-PASS VALVE
(NORMALLY CLOSED)
INLET ISOLATION
VALVE
OUTLET ISOLATION
VALVE
BRINE INJECTOR RAW WATER INLET
30-100 PSIG
BACKWASH FLOW
CONTROLLER
DRAIN
STRAINER
OPTIONAL WATER
METER
NOTES:
ALL PIPING, FITTINGS, ETC SHOWN WITH DASHED LINES
ARE PROVIDED BY OTHERS.
GENERAL PLUMBING CONNECTIONS ARE SHOWN FOR
CLARITY ONLY.
MINERAL TANKS SMALLER THAN 36" DIAMETER HAVE
HANDHOLES.
OVER FLOW
TO DRAIN
CONTROLLER

MR 150M–1050M SINGLE – MXIII CONTROLLER
SYSTEM INFORMATION
3
DIMENSION CHART
MODEL PIPE SIZE DIMENSION TABLE
INLET/OUTLET DRAIN INJECTOR HEIGHT WIDTH LENGTH
MR-150-1 1 1
2.0-050 6’-0”
2’-5”
7’-4”
MR-150-1-1/4 1-1/4 1 2’-6”
MR-150-1-1/2 1-1/2 1 2’-6”
MR-150-2 2 1 2’-10”
MR-210-1-1/4 1-1/4 1
3.5-075 6’-1”
2’-8”
8’-0”
MR-210-1-1/2 1-1/2 1 2’-8”
MR-210-2 2 1 3’-0”
MR-210-2-1/2 2-1/2 1 3’-1”
MR-300-1-1/2 1-1/2 1
5.0-075 6’-4”
3’-2”
9’-0”
MR-300-2 2 1 3’-6”
MR-300-2-1/2 2-1/2 1 3’-7”
MR-300-3 3 1 3’-8”
MR-450-1-1/2 1-1/2 1
5.0-075 6’-10”
3’-2”
9’-6”
MR-450-2 2 1 3’-6”
MR-450-2-1/2 2-1/2 1 3’-7”
MR-450-3 3 1 3’-8”
MR-600-1-1/2 1-1/2 1-1/2
7.0-100 7’-5”
3’-8”
11’-3”
MR-600-2 2 1-1/2 4’-0”
MR-600-2-1/2 2-1/2 1-1/2 4’-1”
MR-600-3 3 1-1/2 4’-2”
MR-750-2 2 1-1/2
7.0-100 8’-5”
4’-0”
11’-3”MR-750-2-1/2 2-1/2 1-1/2 4’-1”
MR-750-3 3 1-1/2 4’-2”
MR-900-2 2 2
10.0-100 7’-10”
4’-6”
12’-6”MR-900-2-1/2 2-1/2 2 4’-7”
MR-900-3 3 2 4’-8”
MR-1050-2 2 2
10.0-100 8’-10”
4’-6”
13’-2”MR-1050-2-1/2 2-1/2 2 4’-7”
MR-1050-3 3 2 4’-8”

MR 150M–1050M SINGLE – MXIII CONTROLLER
SYSTEM INFORMATION
4
SPECIFICATION CHART
SYSTEM SIZE
MODEL 150 210 300 450 600 750 900 1050
VALVE SIZE (IN)
1141221412222122223122223122223 2 223 2 223 2 223
MAX CAPACITY (KILOGRAINS) 150 210 300 450 600 750 900 1050
MIN CAPACITY (KILOGRAINS) 100 140 200 300 400 500 600 700
FLOWRATE (GPM)
SERVICE - CONTINUOUS (GPM)
32 42 45 57 41 64 80 115 68 92 140 165 63 82 120 140 72 110 140 175 90 140 160 105 150 188 95 135 173
SERVICE - PEAK (GPM)
55 78 69 97 57 86 110 160 92 125 190 230 90 115 170 190 94 125 190 250 116 190 230 133 218 279 124 210 259
BACKWASH & FAST FLUSH
(GPM) 10 15 20 20 30 30 45 45
BRINE DRAW & RINSE (GPM) 2.5 3.5 5 5 7 7 10 10
TIMER
SETTINGS
BACKWASH & FAST FLUSH (MIN) 10 10 10 10 10 10 10 10
BRINE DRAW & RINSE (MIN) 60 60 60 60 60 60 60 60
FAST FLUSH (MIN) 6 6 6 6 6 6 6 6
SOFTENER TANK
SIZE (IN) 20x54 24x54 30x54 30x60 36x60 36x72 42x60 42x72
GRAVEL (LBS) 100 200 300 300 400 400 600 600
RESIN (FT3)5 7 10 15 20 25 30 40
FREEBOARD (IN) 24 24 27 20 23 27 20 25
BRINE SYSTEMS
EQUIPMENT
TANK SIZE 24x50 24x50 24x60 30x60 39x60 39x60 42x60 50x60
MAX SALT STORAGE (LBS) 700 600 600 1000 1900 1700 1900 2300
INJECTOR CODE 2.0-050 3.5-075 5.0-075 5.0-075 7.0-100 7.0-100 10.0-100 10.0-100
INJECTOR COLOR RED WHT BLUE BLUE RED RED WHT WHT
SALT
SALT DOSAGE- MAX (LBS) 75 105 150 225 300 375 450 525
SALT DOSAGE- MIN (LBS) 30 42 60 90 120 150 180 210
BRINE VALVE FLOAT HEIGHT - MAX 12 19 26 26 19 26 26 19
BRINE VALVE FLOAT HEIGHT - MIN 3 8 9 9 8 9 9 8

MR 150M–1050M SINGLE – MXIII CONTROLLER
SYSTEM INFORMATION
5
WIRING DIAGRAM
MODEL 48 STAGER
WITH MARLO LOGO
MX III CONTROLLER WIRING
B1046050
MRP
VB
5/24/11
NTS 1 1
B1046050 5
1. 10/23/12 KCA SENSOR WIRES WERE WIRED TO
TERMINALS 7,8 & 9 RESPECTIVELY.
ADDED AUX RELAY WIRING.
2 8/26/13 MRP ADDED SOLENOID TO DRAWING
3. 9/29/15 KCA VARIOUS UL CHANGES.
4. 11/3/17 JH VARIOUS UPDATES
1 2 3 4 5 6 7 8 9 10
Seqn Item Number Qty Description
1
2
3
4
TRANSFORMER 40VA 120V/24VAC (T40F3)
A2242066 1
POWER CORD
XFMR
GROUND
A2173315
A2155115
A2090040
1
1
1
CONTROL NXT STAGER 48 W/SOLENOID
WIRE JOINT INSULATED #18-#12
CORD POWER 18/3 8FT 10A (1FD82)
SW1
SW2
TERMINALS
BLACK
SHIELD
BLACK
CLEAR
RED
BLACK
RED
RED
GREEN
RED
WHITE
BLACK
FLECK
SIGNET
CLACK
AUTOTROL
FLOW METER WIRING
BLK
RED
GRN
P-2
METER
CIRCUIT BOARD
(MOUNTED ON
INSIDE OF DOOR)
P-1
24VAC
RED
PURPLE
ORANGE
BLACK
WHT/BLK
YELLOW
RED
WHITE
BLK
RED
GRN
UPPER DRIVE
PURPLE
BLACK
ORANGE
BLACK
1
2
3
4
5
6
7
8
9
10
STAGER INTERNAL WIRING
(SEE ENCLOSURE ON RIGHT)
PROGRAM CAM
AUX CAM #1
STAGER MOTOR
24VAC 50/60Hz
4 WATT
N.O.
N.C.
N.O.
N.C.
C
C
BLUE
BLUE
STAGER
MOUNTED SCREW
GROUND
LUG
GROUND
SCREW
GREEN/YELLOW
GRN/YEL
SW2
SW1
(HOMING CAM)
(SWITCH HOUSING)
IS RED
(CYCLECAM)
SWITCHED HOT
NEUTRAL
BLACK
BLACK
P4
AUX
LOCKOUT
REMOTE START
GND
OPTIONAL REMOTE
SIGNAL START
SWITCH (N.O.)
OPTIONAL INTERLOCK
SWITCH (N.O.) CLOSED CONTACT
PREVENTS REGENERATION
-INPUT SIDE PULLED UP TO 32 VDC
CLOSED CONTACT
INITIATES REGENERATION
IF OPTION ENABLED
-INPUT SIDE PULLED UP TO 32 VDC
OPTIONAL MOTOR/PUMP ON DURING REGENERATION
OR CPO DEVICE ON DURING SERVICE (N.O. OUTPUT)
DRY CONTACT
24VAC/3A MAX. RESISTIVE
30VDC/3A MAX. RESISTIVE
LOWER
DRIVE
OPTIONAL SOLENOID VALVE ENERGIZED
DURING REGENERATION OR STANDBY
(P6 OUTPUT - 24VAC 50/60Hz, 1.0A MAX.)
CAN1 CAN2
P8
DEVICE T-9 T-10T-8
DC(-) DC(+)SIGNAL(S)
RED
RED
5A2169003 4MOUNTING FEET
P6
S-1
3
3
TORQUE TO lbs-in
TERMINAL RATING
5.3
USE GAUGE
WIRE ONLY
10 - 22
WHT
RED
ORG
BLK
WHT
BLK
GRN
11
120V
LINE IN
12
240V
LINE IN
13
208V
LINE IN
14
NEUTRAL
IN
WHT
OPTIONAL
AUX CAM #2
N.O.
N.C.
C
SW3
BLACK RED
GREENPULSE
RED
RED
BLU
YEL
BRN
RED
PURP
PURP
RED
BROWN
REMARKSBYNO. DATE
REVISIONS
5. 12/21/17 KA ADDED/MODIFIED WIRE COLORS.

MR 150M–1050M SINGLE – MXIII CONTROLLER
SYSTEM INFORMATION
6
TUBING DIAGRAM - VALVE NEST - MULTITANK - ASCO SOLENOID

MR 150M–1050M SINGLE – MXIII CONTROLLER
SYSTEM INFORMATION
7
TUBING DIAGRAM - VALVE NEST - MULTITANK - PARKER SOLENOID
Note: All valves normally open except optional valve 2A.
1
3
2
Flow
Solenoid Energized
1
3
2
Flow
Solenoid De-energized
Energized To Close
TheNXTStagercontrolcanoperateanoptional24VAC
solenoidtocontrolwhenatankisoffline.Thissolenoidis
electricallyconnectedtothe"lowerdrive"connectiononthe
circuitboard,andcontrolpressureisrunthroughthesolenoid
totheserviceoutletdiaphragmvalve.
Thesolenoidinstalledatthefactoryisauniversaltype.Itis
plumbedinanenergizetocloseconguration.
WhenatankentersRegenerationorStandbythesolenoidis
energized.Pressurefromsolenoidport1passestoport2.The
diaphragmvalve#2willclose.
WhenatankentersInServicethesolenoidisde-energized.
Theinletpressuretosolenoidport2isstopped.The
diaphragmvalveisventedthroughsolenoidport2toport3
(drain).Thevalve#2opens.