MASTERTHERM MasterLan pCO5 Bedienungsanleitung

REV. 12 (SW33)
MasterLan
INSTRUCTION MANUAL
pCO5/PGD1 DIGITAL CONTROLLER
HEAT PUMPS
MasterTherm
MASTERTHERM CZ s.r.o.
Václavské náměstí 819/43, 110 00 Praha 1
tel.:+ 420 311 516 567
e-mail: info@mastertherm.cz, www.mastertherm.cz

MasterLAN –INSTRUCTION MANUAL
Revison 1.1, Ing. Jiří Jiránek 2
TABLE OF CONTENTS:
1Introduction ...........................................................................................................................3
2Terms definition ....................................................................................................................3
3Hardware configuration.........................................................................................................3
3.1 pLAN address table .......................................................................................................4
3.2 Setting of the pCO pLAN address..................................................................................4
3.2.1 Protocol Set menu ..................................................................................................5
3.3 Setting of the pDG pLAN address..................................................................................5
3.4 Setting communication between pCO and pGD ............................................................5
3.4.1 Single controller unit ...............................................................................................6
3.4.2 Double controller unit..............................................................................................6
3.5 Setting summary............................................................................................................ 6
3.6 Wiring ............................................................................................................................7
3.6.1 MasterLAN wiring diagram .....................................................................................8
4Software configuration ..........................................................................................................9
4.1 Main Menu mask ...........................................................................................................9
4.2 Setting masks ................................................................................................................9
4.2.1 Master/Slave setting mask......................................................................................9
4.2.2 Master setting masks............................................................................................10
4.2.3 Source Control Masks ..........................................................................................13
4.2.4 OFFLINE configuration.........................................................................................14
4.2.5 Remote Functions ................................................................................................15
4.3 Control principle...........................................................................................................16
4.3.1 Proportional control (recommended) ....................................................................16
4.3.2 PI control ..............................................................................................................16
4.3.3 PID control............................................................................................................ 17
5Alarms MasterLAN masks ..................................................................................................17
6Additional notes ..................................................................................................................18
7Revision history ..................................................................................................................18

MasterLAN –INSTRUCTION MANUAL
Revison 1.1, Ing. Jiří Jiránek 3
1 Introduction
MasterLan is used for control of the multiple units installation. MasterLan requires specific
hardware and software configuration.
2 Terms definition
Explanation of some important terms and names used in the MasterLan description.
pCO5:
PLC controller used in the MasterTherm CZ heat pumps.
pGD1:
Semigraphical terminal used for communication with user. (pCO Graphic Display).
pLAN:
Carel based protocol dedicated for communication between pCO controllers and pGD displays.
(pCO Local Area Network). Principle of data transmision is based on RS485 standard.
pLAN address:
Address of each unit in the pLAN. Each pCO controller and pGD terminal has its own pLAN
address.
MasterLan:
MasterTherm heat pumps hardware and software solution used for multiple heat pumps
installation. Control is based on Master/Slave principle. One unit is configured like Master and
all other units are configured like Slaves. Maximum 16 compressor circuits could be controlled
in the MasterLan.
Single controller machine:
Heat pump with one refrigerant circuit and one pCO5 controller.
Double controller machine:
Heat pump with 2 compressor circuits, 2 controllers and 1 pGD terminal. Switching of the
display between 2 controllers is made by pressing PRG and ENTER keys simultaneously
3 Hardware configuration
Each compressor of the heat pump circuit is controlled by one pCO5 controller.
Single controller heat pump is also equipped with single pGD terminal. Double controller heat
pump is equipped with 2 pCO5 controllers and single pGD display, which is used for
communicating with both compressor circuits of the unit. Switching of the display between 2
controllers is made by pressing PRG and ENTER keys simultaneously. In the double heat
pump 2 controllers are already interconnected with pLAN protocol. Connection is made by 3
wires between terminals 61(Rx-/Tx-), 62(Rx+/Tx+) and 63(GND). Terminals are interconnected
with J11 pLAN connector of pCO5.
IMPORTANT: BEFORE ADDRESS SETTING IT IS ABSOLUTLY NECESSARY TO
DISCONNECT J11 pLAN CONNECTOR FROM ALL CONTROLLERS.

MasterLAN –INSTRUCTION MANUAL
Revison 1.1, Ing. Jiří Jiránek 4
3.1 pLAN address table
Single compressor units:
Unit type pCO controller
pLAN address
pGD terminal
pLAN address
Master 1 32
Slave 1 2 31
Slave 2 3 30
Slave 3 4 29
Slave 4 5 28
Slave 5 6 27
Slave 6 7 26
Slave 7 8 25
This text type is default factory setting.
Double compressor units:
Unit type pCO controller
pLAN address
pGD terminal
pLAN address
Master 1 32
Slave 1 2 -
Slave 2 3 31
Slave 3 4 -
Slave 4 5 30
Slave 5 6 -
Slave 6 7 29
Slave 7 8 -
This text type is default factory setting.
3.2 Setting of the pCO pLAN address
IMPORTANT: BEFORE ADDRESS SETTING IT IS ABSOLUTLY NECESSARY TO
DISCONNECT J11 pLAN CONNECTOR FROM ALL CONTROLLERS.
•Disconnect J11 connector from all pCO controllers
•Power ON the pCO controller
•Enter menu "Protocol Set"
•Set the address according to the table
•Repeat this procedure for all units controllers

MasterLAN –INSTRUCTION MANUAL
Revison 1.1, Ing. Jiří Jiránek 5
3.2.1 Protocol Set menu
List password mask and enter the OEM Expert password code. Enter menu and list "Protocol
Set", confirm ENTER and find following mask using UP key.
Jump with cursor to "pCO Address" and set address according to table above. Address is
changed immediately.
Use ESC to return to the menu.
3.3 Setting of the pDG pLAN address
Each pCO controller and pGD display address must be set according to the table above.
•Connect pGD display to the pCO controller
•Power ON pCO
•Press “UP”+“ENTER“+”DOWN” keys simultaneously until following display appears
•Use keys “UP”/”DOWN” to change address of the pGD according to the table above.
•Confirm selection pressing „ENTER“ key
3.4 Setting communication between pCO and pGD
This procedure requires correct setting of the pCO according to the pLAN address table.
Display address
Setting…………..: xx
I/O Board address:xx
↑↓
List
Edit

MasterLAN –INSTRUCTION MANUAL
Revison 1.1, Ing. Jiří Jiránek 6
3.4.1 Single controller unit
•Connect the pGD to the pCO controller
•Power ON the pCO, wait for pCO initialization, it takes cca 1 minute.
•Press “UP”+“ENTER“+”DOWN” keys simultaneously until following display appears
•Use keys “UP”/”DOWN” to change address of the pGD according to the pLAN address
table
•Confirm selection pressing „ENTER“ key
•Wait until I/O Board address appears beside “--” symbol
•Confirm pressing ENTER key, following screen will appear
•Pressing ENTER key, following screen will appear
•Set Trm1 address according to the unit You are setting, confirm ENTER
•Set type of terminal to “Pr”, confirm ENTER until You reach Yes/No array
•Change array to “Yes” and confirm ENTER
3.4.2 Double controller unit
Do procedure as for single compressor circuit, but set type of terminal to Shared, “Sh”. You
have to do it for both controllers in the unit.
3.5 Setting summary
•Disconnect all J11 terminals from all controllers
•Set pCO address for all controllers
•Set pGD address for all pGDs
•Set commincation between pCO and pGD
•Switch all controllers OFF
•Return J11 connectors to the pCO controllers
Display address
Setting…………..: xx
I/O Board address:xx
↑↓
List
Edit
Terminal config
Press ENTER
to continue
P:xx Adr Priv/Shared
Trm1 xx Pr
Trm2 xx --
Trm3 xx -- Ok? Yes

MasterLAN –INSTRUCTION MANUAL
Revison 1.1, Ing. Jiří Jiránek 7
3.6 Wiring
For correct function make wiring connection using twisted pair shielded cable between 61, 62
and 63 terminals of all electric control boards.
NOTE: For correct pLAN function at least one pGD must be installed.
Please see following wiring diagram for proper installation.

MasterLAN –INSTRUCTION MANUAL
Revison 1.1, Ing. Jiří Jiránek 8
3.6.1 MasterLAN wiring diagram

MasterLAN –INSTRUCTION MANUAL
Revison 1.1, Ing. Jiří Jiránek 9
4 Software configuration
For the access to the MasterLAN configuration You have to enter the OEM password.
4.1 Main Menu mask
MasterLAN masks could be found in the main mask loop, using the UP and DOWN keys from
„ICON“ mask.
Master Slaves 1 to 7
Compressor
status 0 - OFF
1 - ON
Heater
status
Slaves 8 to 15
4.2 Setting masks
To enter MasterLAN setting displays please press PRG button on the main MasterLAN display.
4.2.1 Master/Slave setting mask
MasterLAN control Enabled/Disabled
Unit in the MasterLAN system Compressor steps Heater steps
Master/Slave1/Slave2/…/SlaveX
You can Enable or Disable MasterLAN control on this mask. No more masks are available if the
unit is Slave.
Press ESC key for return to the main mask loop.

MasterLAN –INSTRUCTION MANUAL
Revison 1.1, Ing. Jiří Jiránek 10
4.2.2 Master setting masks
Using keys UP and DOWN you have access to the following masks.
Unit in the MasterLAN
system
Master/Slave1/Slave2
/........./Slave15
Yes/No Enabled/Disabled
Parameter: SP Range/F.: Unit Description
Compressor B440
-455
Enabled/Disabled
F: Enabled
- Allows compressor to be controlled by
MasterLAN control in Heating/Cooling
mode.
SHW Mode - Enabled/Disabled
F: Enabled
- Unit is enabled for SHW Mode. When
Disabled, unit will not run in SHW Mode.
Heater B460
-475
Enabled/Disabled
F: Enabled
- Enabling heater for MasterLAN control in
heating mode.
Online - Yes/No - If the unit is communicating in MasterLAN
network (unit is present and online).
Similar masks appearing for each unit .........
.
.
.