Mercury Security © 2014 MRDT DOC 10107-0023 REV 1.05 Page 7
7. Status, Off-line, LED/Buzzer, and Downloading Displays:
Status Display *:
Pressing the arrow and command keys simultaneously while MRDT is running in the normal mode will
display the summarized information for ten seconds.
Status Display example:
0000074582 1621B
485MSP1 38400 05
The top line contains the 10 digit serial number, firmware revision, and the hardware assembly version.
The bottom line contains the communication type, baud rate, communication address.
Communication type: Rdr Port, 485MSP1, or 485OSDP
Baud rate: 9600, 19200, 38400, or 115.2
Address = 00-31
Off-line Display *:
When the MRDT is not communicating to the SCP/EP controller communication port or the reader port,
the following will be displayed:
“ooo “
“ ooo”
If the SIO of the reader port that the MRDT is connected to is off-line with the SCP/EP controller, the
following will be displayed:
“…“
“…”
Bi-color LED/Buzzer:
The LED and buzzer are controlled by the LED and buzzer input except as noted below.
Firmware Downloading Display *:
If the MRDT is power up with corrupted or missing application code the following message is displayed:
FirmwareRequired The application code must be downloaded to the MRDT.
When the MRDT is receiving downloaded firmware the following will be displayed:
“Downloading x”(x = period, lower case o, and zero animatedly displayed in sequence).
When in either of the above modes, the LED flashes: 0.1 second Green, 0.1 second Off.
After firmware download has completed the PowerUp screen will appear and the MRDT will initialize.
8. Specifications:
The Display Terminal is for use in low voltage, class 2 circuits only.
Primary Power:
Voltage: 12 Vdc ± 15 %, must be filtered
Current: 175 mA (terminal only, does not include external reader)
Communication:
RS-485:
Serial I/O port: 4,000 feet (1220 meters) max. 22 or 24 AWG, 120 ohms impedance
Reader port: 2,000 feet (610 meters) max. 22 or 24 AWG, 120 ohms impedance
TTL: 500 feet (152 meters) max, 18 AWG