MGC RAXN-LCD Bedienungsanleitung

RAXN-LCD
Network Remote Annunciator Panel
LT-895 Rev 3
Feb 2018
Installation and Wiring Manual
MGC Network
Fire Control System
- System Normal -
Feb 21, 2018 2:21 PM
SIGNAL
SILENCE
FIRE
DRILL
SYSTEM
RESET
GENERAL
ALARM
ACKNOW-
LEDGE
LAMP
TEST
ENTER
TROUBLE
QUEUE
SUPV.
QUEUE
ALARM
QUEUE
MENU
CANCEL
INFO
MONITOR
QUEUE
A.C.
ON
PRE-
ALARM
GROUND
FAULT



1
Introduction
1.0 Introduction
MGC’s remote shared display is the RAXN-LCD. The RAXN-LCD provides a replica of the
main Fire Alarm Panel display at a remote location. It is equipped with a large 4 line x 20
character back-lit alphanumeric LCD display that uses a simple menu system complete with a
directional keypad and switches for Enter, Menu, Cancel and Info. The display expands with
up to a total of 41 frames made up of display adder modules and up to 7 RAXN-LCDs per
node, refer to figure below. The RAXN-LCD may be mounted in the BB-1000 (MMX-BB-1000)
Series backboxes, the BB-5008, BB-5014, BBX-FXMNS (MMX-BBX-FXMNS) and FX-LOC
(MMX-LOC) enclosures.
IPS-2424DS
Programmable
Input Switches
[2 Frames]
QAZT-5302DS
Zoned Paging and
Telephone Selector
[1 Frame]
QMT-5302N
Master Telephone
[1 Frame]
QMP-5101N
Master Paging
[1 Frame]
QMP-5101NV
Master Paging
[1 Frame]
QMT-5302NV
Master Telephone
[1 Frame]
FDX-008W/KI
Fan Damper
Controller
[1 Frame]
RAX-1048TZDS
Adder
Annunciator
[3 Frames]
AGD-048
Graphic
Driver
[1 Frame]
PTR-2000-1
Line Printer
RAXN-LCD
Annunciator
External RS-485
RS-485 from Main Fire Alarm Board
The RAXN-LCD can support up to a maximum of 41 frames
in any combination of annunciator type modules.
RS-232

2
Installation Instructions
2.0 Installation Instructions
The RAXN-LCD chassis is mounted with four HEX nuts. Figure below shows the RAXN-LCD
mounted into a BB-1001D/R (MMX-BB-1001D/R) backbox. Dimensions for height and
mounting hole locations change for the various backboxes as shown in the table below.
BACKBOX CAN BE MOUNTED
WITH STANDARD 4" X 4"
ELECTRICAL BOXES
BB-1001D/R BACKBOX IS SHOWN
RAXN-LCD ANNUNCIATOR
GB-1001RAXN GUARD BRACKET
B
12.75”
H
A
#6-32
HEXNUTS
1.85”
WALL
DOOR
BACKBOX
BACKBOX MODEL
HEIGHT
OF
BACKBOX
H (IN.)
WIDTH
OF
BACKBOX
(IN.)
HORIZONTAL
MOUNTING
HOLE DIM.
A (IN.)
VERTICAL
MOUNTING
HOLE DIM.
B (IN.)
BB-1001D/R(MMX-BB-1001D/R)
9.0” 12.75” 9.95” 7.5”
BB-1002D/R(MMX-BB-1002D/R) 18.0” 12.75” 9.95” 16.5”
BB-1003D/R(MMX-BB-1003D/R) 26.5” 12.75” 9.95” 24.9”
BB-1008D/R(MMX-BB-1008D/R) 33.0” 22.5” 9.95” 35.2”
BB-1012D/R(MMX-BB-1012D/R) 45.0” 22.5” 9.95” 52.0”

3
Jumper Settings
3.0 Jumper Settings
There are 3 jumpers located on the top left-hand side of the board position left to right as JW2, JW1 and
JW3.
Jumper Function
JW1 Left OPEN, used for hard reset
JW2 Jumpered (jumper installed) for watchdog timer
JW3 Left OPEN, if buzzer (located on the right-side of jumper JW3) is to be silenced.
i
Note: There are jumpers located in connectors P6 and P7. Remove these jumpers when
using adder modules beyond the first 13 frames. Refer to the Fire Alarm Panel
manual for further details.
RS-485 TERMINALS 24V POWER TERMINALS
SW1
LCD Display
Contrast Adjust
P5
P6 P7
P5 connects to rst set of display modules,
up to a total of 13 frames.
P6 is an expansion connector for the next
14 frames and P7 for the next 14 frames
beyond that for a total of 41 frames. RS-232 Port for
Printer Connection
Jumpers:
JW2, JW1, JW3
ALARM
QUEUE
SUPV.
QUEUE
TROUBLE
QUEUE
MONITOR
QUEUE
MGC Network
Fire Alarm Control System
- System Normal -
SIGNAL
SILENCE
GENERAL
ALARM
ACKNOW-
LEDGE
FIRE
DRILL
SYSTEM
RESET
LAMP
TEST
February 21, 2018 10:08 AM

4
DIP Switch Settings
4.0 DIP Switch Settings
Each RAXN-LCD Shared Display Annunciator needs to be assigned a unique address via the
DIP switches of SW1.
The RAXN-LCD SW1 DIP switches are set by selecting the active ON. The addresses
available for the RAXN-LCD are 33 to 39, inclusive. Set the address as follows in the table
below:
RAXN-LCD Address SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8
33 ON OFF OFF OFF OFF ON
Leave in “OFF”
position as
Factory Set.
34 OFF ON OFF OFF OFF ON
35 ON ON OFF OFF OFF ON
36 OFF OFF ON OFF OFF ON
Refer to Network Fire Alarm Manual as to whether addresses 37 to 39 are available
37 ON OFF ON OFF OFF ON
38 OFF ON ON OFF OFF ON
39 ON ON ON OFF OFF ON
RAXN-LCD Remote Annunciator Address Setting (DIP SWITCH SW1)
SW1
18
DIP SWITCH SETTINGS
ON
OFF
DIP switch SW1 is
used to set the
address of the
RAXN-LCD
DIP switches are for assigning an address to the RAXN-LCD. Binary addresses 33 to 39 are
available with the least significant bit being switch SW1-1 on the left and the most significant
bit being SW1-6. The ON setting is active binary. DIP switches SW1-7 and SW1-8 are not
used.
For example, address 33 is set by pushing DIP switch SW1-6 and SW1-1 to the ON position
and all the other DIP switches to the OFF position.
Refer to Network Fire Alarm Manual as to whether addresses 37 to 39 are available.

5
Wiring Instructions
5.0 Wiring Instructions
RS-485 Wiring
24 VDC
INPUT
-
+
-
+
24 VDC
OUTPUT
24 VDC POWER FROM FIRE ALARM MAIN BOARD
OR PREVIOUS ANNUNCIATOR
24 VDC POWER TO
NEXT ANNUNCIATOR
+
-
S
S
-
+
RS-485
INPUT
RS-485
OUTPUT
RS-485 TO NEXT ANNUNCIATOR
(TWISTED SHIELDED PAIR)
RS-485 FROM FIRE ALARM MAIN BOARD OR PREVIOUS
ANNUNCIATOR (TWISTED SHIELDED PAIR)
RAXN-LCDG
ALL CIRCUITS ARE POWER LIMITED
AND MUST USE TYPE FPL, FPLR, OR
FPLP POWER LIMITED CABLE
The RS-485 wiring to the
RAXN-LCD Display Module
is recommended to be
twisted shielded pair as
shown in the diagram to the
right. The RS-485 wire
gauge may be:
• 22 AWG up to 2000 ft.
• 20 AWG up to 4000 ft.
The RS-485 wiring from the
fire alarm control panel to
the annunciator(s) must be
point-to-point from the fire
alarm panel to the first
annunciator, then to the next
annunciator, and so on. No
star wiring or T-tapping is
allowed.
Each RAXN-LCD Shared
Display has a 120 ohm end-
of-line resistor on its RS-485
output terminals. This
resistor is removed on all except the last wired annunciator.
24V DC Wiring
The 24 VDC field wiring needs to be of an appropriate gauge for the number of annunciators
and the total wiring run length. Refer to the Current Drain for Battery Calculations on page 8
to calculate the maximum current for all annunciators summed together.
!
Accidentally connecting any of the 24 VDC wires to the RS-485 wiring will result in damage to
the annunciator and/or to the fire alarm control panel to which it is connected.
Total Maximum
Current for all
Annunciators
Maximum Wiring Run to Last Annunciator Max. Loop
Resistance
18AWG 16AWG 14AWG 12AWG
Amperes ft mft mft mft mOhms
0.12 1180 360 1850 567 3000 915 4250 1296 15
0.30 470 143 750 229 1200 366 1900 579 6
0.60 235 71 375 114 600 183 850 259 3
0.90 156 47 250 76 400 122 570 174 2
1.20 118 36 185 56 300 91 425 129 1.5
1.50 94 29 150 46 240 73 343 105 1.2
1.70 78 24 125 38 200 61 285 87 1.0

6
Cable Connections
6.0 Cable Connections
The RAXN-LCD may be utilized by itself in a remote location or within a larger enclosure
together with other display modules. It may also be used as part of a mass notification system.
Below is an example of a RAXN-LCD and aRAX-1048TZDS 48 LED Annunciator Display
module in a BB-1002D/R (MMX-BB-1002D/R) enclosure.
Connections
P2
RAX-1048TZDS Adder Annunciator or
IPS-2424DS Programmable Input Switches Module
POWER
TERMINALS
P1
P5
RAXN-LCD SHARED DISPLAY BOARD
RS-485
TERMINALS
SW1
ALARM
QUEUE
SUPV.
QUEUE
TROUBLE
QUEUE
MONITOR
QUEUE
MGC Network
Fire Alarm Control System
System Normal
February 21 2018 2:21PM
SIGNAL
SILENCE
GENERAL
ALARM
ACKNOW-
LEDGE
FIRE
DRILL
SYSTEM
RESET
LAMP
TEST
on the
RAXN-LCD Annunciator
P5: Connects to the RAX-
1048TZDS 48 LED Annunciator
module. This connector may
connect up to 13 frames of display
modules.
P6: Connects to next 14 frames (i.e.
frame 15 to 27) of display modules.
P7: Connects to next 14 frames (i.e.
frame 28 to 41) of display modules.
Terminals: Terminal wiring is
required for the RS-485 loop and the
24V DC power source. See Wiring
Instructions on page 5 for details.
SW1: DIP switch SW1 is used to set
the address for the RAXN-LCD. See
DIP Switch Settings on page 6 for
details.
Connections on the RAX-
1048TZDS 48 LED
Annunciator Display
Module:
P1: Connects to the main annunciator chassis RAXN-LCD P5.
P2: Connects to the next display module if used.
i
Note: The last annunciator must have a 120 ohm E.O.L. resistor connected to the RS-485
output terminals.
Inhaltsverzeichnis
Andere MGC Steuereinheit Handbücher
Beliebte Steuereinheit Handbücher anderer Marken

Festo
Festo Compact Performance CP-FB6-E Stücklistenhandbuch

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Bedienungsanleitung

JS Automation
JS Automation MPC3034A Bedienungsanleitung

JAUDT
JAUDT SW GII 6406 Series Kurzanleitung

Spektrum
Spektrum Air Module System Bedienungsanleitung

BOC Edwards
BOC Edwards Q Series Bedienungsanleitung