MTP MTP-1032 Bedienungsanleitung

MTP
Instruction Manual
Voltage Tester
Model MTP-1032
MTP Instruments
www. .com information@itm.com1.800.561.8187

Table of Content
1
Features
Page 1
2
Safety warnings
Page 1
3
Instrument layout
Page 2
4
Preparation for measurement
Page 3
4.1
Auto power-on / Self diagnostic test
Page 3
4.2
Trouble shooting
Page 4
5
Handy construction
Page 4
6
Measurement
Page 5
6.1
Voltage test (double pole test)
Page 5
6.2
Phase rotation test
Page 6
6.3
Continuity test
Page 7
6.4
Pen light function
Page 7
7
Battery replacement
Page 8
8
Specifications
Page 9
9
Cleaning and storage
Page 10
10
Safety symbols
Page 10
11
Measurement category
Page 10
12
Environment
Page 11
13
Ingress protection (IP) ratings
Page 11
Introduction
www. .com information@itm.com1.800.561.8187

Congratulations on the purchase of your Voltage Tester, Model MTP-1032. Careful use
of this meter will provide years of reliable service.
1. Features
Self-diagnostic test
AC and DC voltage tests up to 600V with LED
and LCD
Polarity indication
Phase rotation test
Continuity test
Auto-power ON/OFF
Pen light for illuminating measurement points
Probe clip for adjustable spacing between probes
Probe cover protects user and probe tips
IP64
Compact design (light-weight and portable)
2. Safety Warnings
This instruction manual contains warnings and safety rules which have to be noticed
by the user to ensure safe operation of the instrument and to maintain it in safe
condition. Therefore, read through these operating instructions before using the
instrument.
WARNING is reserved for conditions and actions that are likely to cause
serious or fatal injury.
CAUTION is reserved for conditions and actions that can cause injury or
instrument damage.
It is essential that the above instructions are adhered. Failure to follow the
above instructions may cause injury, instrument damage and/or damage to
equipment under testing.
1
www. .com information@itm.com1.800.561.8187

WARNING
Never make measurement on a circuit in which the electrical potential exceeds
600V. (While the measured voltage exceeds 600V, all the voltage display LED
light up).
Do not attempt to make measurement in the presence of flammable gases, as the
use of the instrument may cause sparking, which could lead to an explosion.
Never attempt to use the instrument if its surface or your hands are wet. (Do not
use in rainfall).
Keep your hands and fingers behind the barriers during measurements.
Never unlock and open the battery case during measurements.
Verify proper operation on a known source before taking action as a result of the
indication.
Never attempt to make any measurement in any abnormal conditions, such as a
broken case or exposed metal parts are present on the instrument or test probes.
Do not make any modification to the instrument.
Extreme caution when live circuit LED flashes or lights on.
Correct indication of LEDs is only guaranteed within a temperature range of -
10ºC up to 55ºC (<85% RH)
3. Instrument Layout
1) LEDs12//120/208/240/277/480/600V for voltage indication
2) LED 48V for voltage indication
3) L/R LEDs for phase rotation test
4) Power LED
5) Polarity indication LEDs for voltage
6) LCD
7) Continuity test / live circuit LED
2
www. .com information@itm.com1.800.561.8187

1. L1 probe -
2. L2 probe + (instrument probe)
3. Barrier
4. Pen light
5. Pen light switch
6. Battery case
7. Probe clip
8. Probe protection cover
4. Preparation for Measurement
4.1 Auto Power-on / Self Diagnostic Test
Auto Power-on
Short-circuiting the probes as follows powers on the instrument automatically and
goes into a self-diagnostic test.
Instrument may power on due to the influence of static charge.
3
www. .com information@itm.com1.800.561.8187

Self-diagnostic test
WARNING
Do not use the instrument when abnormality is found at self-diagnostic test.
Battery voltage is normal when power LED is lighting up.
When the battery voltage is below 2.4 ± 0.1V, power LED flashes or goes off.
Replace batteries according to section 7.
4.2 Trouble shooting
If the following problems occur, unlock the battery case according to section 7 in this
manual, and then lock it again 5 seconds later. Then perform the self-diagnostic test
(section 4.1).
Self-diagnostic test cannot be performed before/after use of the instrument.
Automatic power-off does not operate.
5. Handy Construction
With the L1 probe on the probe clip, user can change the spacing between probes
with one hand.
4
www. .com information@itm.com1.800.561.8187

6. Measurement
WARNING
Please refer to section 2 of this manual (Safety Warnings)
Self-diagnostic test should be done prior to measurements to confirm that LED
and buzzer works properly.
Verify proper operation on a known source before and after use.
Keep your hand and fingers behind the barriers on the probes during
measurements.
6.1 Voltage test (double pole test)
Connect both probes to the object under test.
The voltage is indicated by LEDs and LCD
Live circuit LED lights up: ≥7V
Voltage polarity is indicated in following manner:
Note
When the L2 probe + is the positive (negative) potential, the polarity indication LED
indicates "+DC" ("-DC").
5
www. .com information@itm.com1.800.561.8187

6.2 Phase rotation test
L LED and R LED for phase rotation test may operate on various wiring systems,
but effective testing result can be obtained only on three-phase 4-wire system.
Grasp the instrument firmly and connect both probes to the object under test.
(Grasp method shown as below).
Phase-to-phase voltage is indicated by each voltage LED.
R LED indicates that the field is rotating towards the right direction of the
"probe". With this connection, the motor will go in positive rotation.
Grasp Firmly!!!
L LED indicates that the field is rotating towards the left direction of the probe. With
this connection, the motor will go in negative rotation.
Grasp Firmly!!!
6
www. .com information@itm.com1.800.561.8187

The principle of measurement
The instrument detects the phase rising order regarding the user as EARTH.
Note
Function of this test may not be fully achieved if the insulation condition of user or of the
equipment under test is not enough.
6.3 Continuity test
WARNING
Make sure the object under test is not live
Instrument operates as follows when measuring continuity.
RX/Ω LED should be lighted and buzzer should sound continuously.
Note
In continuity mode, the instrument works in the same way as the self-diagnostic test.
6.4 Pen light function (Illuminating the measurement point)
Equipped pen light illuminates the measurement point in dimly lit area.
Pressing the pen light switch turns on the light.
Note
The light is available while the instrument is powered off.
Using the pen light shortens the battery life.
7
www. .com information@itm.com1.800.561.8187

7. Battery replacement
WARNING
Remove the probes from any testing point when opening the battery case
Batteries are dead when power LED flashes or goes off at self-diagnostic test defined in
section 4.1. Follow the procedure below and replace batteries with new ones (type IEC
LR03 1.5V).
Unlock the battery case with a coin-shaped object.
Pull out the battery case and replace the batteries. Insert new batteries according to
the engraving on the battery case.
Insert the battery case into the instrument and firmly lock the case again.
WARNING
Confirm that the battery case is properly locked prior to measurements.
8
www. .com information@itm.com1.800.561.8187
Inhaltsverzeichnis
Andere MTP Prüfgeräte Handbücher
Beliebte Prüfgeräte Handbücher anderer Marken

SMART
SMART KANAAD SBT XTREME 3G Series Bedienungsanleitung

Agilent Technologies
Agilent Technologies BERT Serial Bedienungsanleitung

Agilent Technologies
Agilent Technologies N3280A Bedienungsanleitung

Vernier
Vernier Go Direct Voltage Bedienungsanleitung

Lifeloc
Lifeloc R.A.D.A.R. Bedienungsanleitung

Fluke
Fluke T5-600 Bedienungs- und Montageanleitung

PCB Piezotronics
PCB Piezotronics 8159-0112A Bedienungsanleitung

BW Technologies
BW Technologies MicroDock II Bedienungsanleitung

Sun Nuclear
Sun Nuclear 1027 Bedienungsanleitung

Biomark
Biomark HPR LITE READER Bedienungsanleitung

Hioki
Hioki 3169-20 Bedienungsanleitung

Ashcroft
Ashcroft ATE-100 Bedienungsanleitung