Instructions
IMPORTANT NOTICE
All wirin should be carried out by a competent person or a qualified electrician and should be fitted to IEE 17th Edition Wirin reulations
BS7671:2008. The circuit should be isolated before carryin out any work. Failure to adhere to the instructions will invalidate the warranty.
Newlec Helpline: 0800 783 6909
IMPORTANT NOTICE
All wirin should be carried out by a competent person or a qualified electrician and should be fitted to IEE 17th Edition Wirin reulations
BS7671:2008. The circuit should be isolated before carryin out any work. Failure to adhere to the instructions will invalidate the warranty.
RPM 491
ADD GROUP TO PREADDRESSED DALI LUMINAIRES
Setup of existin luminaires on a DALI network is important even if some or all of the luminaires are not to be controlled by the
Newlec DALI Occupancy Detector currently bein installed. In settin up luminaires the DALI Occupancy Detector updates its list of
DALI addresses currently in use, so that those addressed are not allocated to new luminaires. To et the Occupancy Detector to setup
DALI luminaires:
1. Select the required roup on the DALI Occupancy Detector dip switches as per the Table 1 above.
2. You must turn lihts OFF with the remote first to operate and proram in this mode. To do this, point the remote control at the
DALI Occupancy Detector & press the override o button. While in override o the DALI Occupancy Detector LED flashes white.
3. Set the remote control to installer mode by pressin the hidden installer button inside the battery compartment, the remote control
LED illuminates red.
4. Point the remote control at the Occupancy Detector & press button ‘1‘. The detector will now search the network for luminaires that
have a DALI short address pre-prorammed.
5. Once the search is complete the lamps will pulsate. If you want the Occupancy Detector to control the pulsatin luminaire in
the roup, press the remote control brihtness up button for ‘YES‘ or brihtness down button for ‘NO‘. If ‘YES‘ is pressed the
luminaires ballast is updated with the DALI roup currently set on the Occupancy Detectors dip switches and it updates its address
list and controller list. This luminaire is now in the Occupancy Detectors roup. If ‘NO‘ is pressed only the address list is updated
and the Occupancy Detector will not control this luminaire in that roup selected. Please note twin fluorescent DALI luminaires will
only pulsate if both tubes are enaed in the fittin correctly and are both workin normally.
SET UP FOR BRAND NEW UNADDRESSED DALI LUMINAIRES
The Newlec DALI Occupancy Detector has the ability to do basic setup of brand new luminaires. With the ‘Add new luminaires‘
function, roup and scene information can then be prorammed into the ballast within the luminaire. When new luminaires are
addressed for the first time you must then complete the ‘Add roup to pre-addressed luminaires‘. N.B. If there are existin pre-
prorammed luminaires already on the network skip back to ‘Settin Group Mode‘ first before returnin to this section.
To put the Occupancy Detector into ‘Add new luminaires‘ mode:
PLEASE NOTE THESE INSTRUCTIONS MUST BE READ IN CONJUNCTION WITH THE REMOTE CONTROL INSTRUCTIONS
1. You must turn lihts o first with the remote to operate and proram in this mode. To do this, point the remote control at
the Newlec DALI Occupancy Detector & press the override o button. While in override o the Occupancy Detector LED
flashes white.
2. Set the Dipswitch with the roup number you wish to use for the Occupancy Detector .
3. Set the remote control to installer by pressin the hidden installer button inside the battery compartment, the remote control
LED illuminates red.
4. Point the remote control at the Occupancy Detector & press button ‘2‘ at the bottom of the remote control while the remote
LED is red. The Occupancy Detector will now search for uncommitted DALI ballasts and proram an unused DALI short address.
An uncommitted luminaire will flash up to 5 times. Durin this search the blue sinal LED on the Occupancy Detector will flash
repeatedly.
5. When the Occupancy Detector flashes red the search is completed and any correctly prorammed luminaires on the DALI
network system will be unaected. Once completed the newly setup luminaires can have a roup (see Add roup to‚ pre-
addressed luminaires) and a basic set of scenes (see ‘Set Scenes‘) prorammed into their ballasts.
Any correctly prorammed luminaires on the DALI network will be unaected. Once completed the newly setup luminaire(s)
can have a roup (see Add roup to pre-addressed luminaires.) and a basic set of scenes (see ‘Set scenes’) prorammed into
their ballasts.